HomeMy WebLinkAboutELEC2020-3076 ELECTRICAL PERMIT (VALUE)
(RA F aV IN Issue Date:August 27,2020
q PROJECT DESCRIPTION: RESTORE POWER"GREAT WOLF LODGE"
4, PROJECT# (817) 410-3010 www.mygov.us
ELEC-20-3076 Inspections Permits
City of Grapevine
LOCATION TENANT LEGAL
Grapevine,,T TX 76099 9
P.O.Box 100 Great Wolf Dr. Great Wolf Lodge Great Wolf Addition Of
X
(617)410-3165 Voice Grapevine, TX 76051 Grapevine Blk 1r Lot 1r
(817)410-3012 Fax
CONTRACTOR INFORMATION
Angiel Electrical Construction Corp County Tarrant
State ID#23982 Square Footage 500
9030 Directors Row VALUATION 2500.00
Dallas, TX 75247
(214)824-6369 Phone Zoning CC-Community Commercial
(214)821-9185 Fax FEES TOTAL=$57.00
(469)576-7614 Mobile
Electrical Permit Fee(VALUE} $ 57.00
OWNER PAYMENTS TOTAL=$57.00
Great Wolf Lodge Grapevine Llc Angiel Electrical Construction Corp(Paul A.
525 Junction Rd Ste 6000 Atkinson) ($57.00)
Madison, WI 53717-2153 Cc on 0812712020
NOTICES
AVAILABLE INSPECTIONS ALL work must be done in compliance with the 2005 NATIONAL ELECTRIC
� Electrical Service(required) CODE.
r Electrical Final (required)
PLAN SUBMITTAL:WHEN PLANS ARE REQUIRED BY CODES,
ORDINANCES, OR AS DETERMINED BY THE BUILDING OFFICIAL,THREE
(3)SETS OF PLANS SHALL BE SUBMITTED IN HARD COPY FORMAT.
ENGINEER SEALED PLANS AND CALCULATIONS SHALL BE SUBMITTED
AS REQUIRED BY CODES, ORDINANCES OR WHERE OTHERWISE
REQUIRED BY STATE LAW.
READ AND SIGN
I HEREBY CERTIFY THAT THE FOREGOING IS CORRECT TO THE BEST
OF MY KNOWLEDGE AND ALL WORK WILL BE PERFORMED ACCORDING
TO THE DOCUMENTS APPROVED BY THE BUILDING DEPARTMENT AND
IN COMPLIANCE WITH THE CITY OF GRAPEVINE CODES REGULATING
CONSTRUCTION. IT IS UNDERSTOOD THAT THE ISSUANCE OF THIS
PERMIT DOES NOT GRANT OR AUTHORIZE ANY VIOLATION OF ANY
CODE OR ORDINANCE OF THE CITY OF GRAPEVINE.
I FURTHER CERTIFY THAT ALL WORK THAT IS REQUIRED TO COMPLY
WITH ANY FEDERAL, STATE, AND/OR LOCAL LAW REGARDING ENERGY
CONSERVATION WILL BE PERFORMED IN ACCORDANCE WITH THOSE
LAWS,AND THAT VERIFICATION OF ENERGY CODE COMPLIANCE SHALL
BE SUBMITTED TO THE CITY UPON REQUEST.
BCS SWITCHGEAR, INC.
4790 Hwy 377 South MIR 24-Hour 888-599-0486
Krugerville, TX. 76227 Fax 940-365-1808
JOB ID# 20-145
LOW VOLTAGE CIRCUIT BREAKER - TEST REPORT
CUSTOMER GREAT WOLF LODGE DATE 08/27/20
LOCATION ELECTRIC ROOM/CHILLER PANEL ID# DWI MAIN
ROOM ID# ELECTRIC ROOM/CHILLER Breaker ID# NA
NAMEPLATE DATA
MFR. EATON SERIAL# 33SO1830 CHG na
TYPE ICCB/MDS4000 MECH TYPE AIR CONTROL CLOSE na
VOLTS 600 RCK TYPE FIXED VOLTAGE TRIP na
AMPS 4000 CUBICAL NA UV na
VISUAL INSPECTION
PRIMARY DISC. NA ITRIP MECH PASS INTERLOCKS NA
ARC-CHUTES PASS ICLOSING MECH NA SECONDARY DISC. NA
PHASE BARRIERS NA RACKING DEVICE DRAW OUT BELL ALARM L/O NA
PRIMARY CONTACTS NA LUBRICATION NA BLOWN FUSE IND. NA
CONTACT RESISTANCE RESULTS IN MICRO OHMS
A I 26 NO B 1 23 NO I C 24 ND
INSULATION TEST
A-GRND >1000MD B-GRND >1000MD C-GRND >1000MO
A-B >1000MD B-C >1000MD A-C >1000M4
A-OPEN >1000Mf1 B-OPEN >1000M0 C-OPEN >1000M0
OVERCURRENT TRIP DEVICE
TYPE TRIP UNIT DIGITRIP 520 SERIAL# NA CURVE#
FUNCTIONS LSIG RATING 4000 CT TAP 4000
NAMEPLATE DATA
LT P/U SETTING 0.5 IN P/U SETTING 2
LT DELAY 2 GF P/U SETTING 0.25
ST P/U SETTING 2.0 GF DELAY 0.5
ST DELAY 0.5
PRIMARY METHOD TEST RESULTS
TYPE TEST TESTAMPS RESULTS
CURVE SPECS A B C
LONG TIME 5.2 1 8 6000 7.159 1 7.020 1 7.160
PICKUP
SHORT TIM 0.39 1 0.50 12000 0.488 0.488 0.488
INSTANTANEOUS 6400.00 9600.00 8450.000 8395.000 1 8605.000
GROUND FAULT 0.39 0.5 3000 0 0 0
BREAKER IS ACCEPTABLE
REMARKS
TECH TRAVIS LANGER REV. 5
Engineered Power Services
C Engineered Power 972-268-1277
SERVICES
GROUND FAULT RELAY TEST REPORT
CUSTOMER: LOCATION: JOBNUMBER:
ANGEL ELECTRIC GREAT WOLF LODGE 20-145
DATE:
9030 DIRECTORS ROW 100 GREAT WOLF DRIVE 812712020
TESTED BY:
DALLAS TX 75247 GRAPEVINE TX Daniel Rivera
VOLTAGE: NEUT. RES.TO GRD.: SETTINGS SUPPLIED BY:
2771480 >3000MOHMS As Found
SWITCHBOARD: TEST EQUIP.ASSET#: CALIBRATION DATE:
4000 AMP MAIN BREAKER LEFT SERVICE NA 11011712020
As Found and As Lek settings Manufacture EATON Trip Unit DIGITRIP 520
Ir 1 1 Model DS4000
tr 4 4 Seriel 33SO830
Is 6 6 Phase to Ground Phase to Phase Main Circuit Breaker
is .3 OUT 3 OUT Phase A >3000M I 000M Phase A Line-Loadl >3000M
II 8 8 Phase B >3000M I B-C >3000M Phase B Line-Loadj >3000M
Ig 1200 1200 Phase C >3000M I C-A 1>3000M Phase C Line-Loal >3000M
tg 1 .2 ON 1 2 ON Insulation Resistance
150% 200% Main Breaker Contact
TEST RESULTS PICKUP AMPS CURRENT 150% TIME CURRENT 200% TIME
TEST RESULT TEST RESULT Resistance Measurement
AIN NO TRIP 2000A Phase A 26uohms
BIN NO TRIP 2000A Phase B 23uohms
C/N NO TRIP 2000A Phase C 24uohms
AIN TRIP TEST 1200A 1400A 0.429 2200A 0.245
BIN TRIP TEST 1200A 11400A 0.446 2200A 1 0.215
C/N TRIP TEST 11200A 11400A 1 0.545 L2200A 0.235
IS GROUND FAULT SYSTEM ACCEPTABLE ? YES
WERE EQUIPMENT GROUNDS & BONDING JUMPERS INSTALLED ? YES
WERE SERVICE ENTRANCE CONDUCTORS INSTALLED ? YES
WERE FEEDERS INSTALLED ? YES
NOTES:
TESTED WITH CB-832
BREAKER PASSED TESTING