GENERAC°
20/22/24 kW Specifications
Generator
Model
0007038-1
6007042-2 0007038-3
G007042-3
G007209-0
G007039-1
G007043-2 5007039.3
6007043-3
G007210-1
(20 kW9
(22 kA9 (20 kW)
(22 kW)
(24 it%)
rRated maximum continuous power capacity (LP)
26,B00Walls'
_ _
22,000Walls' 20,006Wills'
22,00d Wata'
24000WalIs'
Baled maximum continuous power capacity INS)
18,600 Watts'
19,500 Walls' 18,000walls'
19,500W2115'
21,000 Watts'
_Belot voltage
Bated maximum conlikeous load current-240 oils(tp/NG)
83.3/75.0
91.7/el3 63.3/75O
91.7/81.3
100/87.5
Total Harmonicgistorlloq
Lees than S%
Main line cir_cuil breaker -
90 amp
W0 Yn0 90 amp
100 amp
100 amp
Phase
9
Number of rotor poles
2
Bated AG frequency --
60 Hz
Power lector
1.0
Battery requirement (not included)
12 Volts,
Group 26R 540 CCA minimum or Group 35AGM 650 CCA minimum
Unit weight to/kg)
448/203
466/211 436/198
445/202
4551206
-11huyslons (L x tag H) In/cm
48 x 25 x 29/121.9 x 63.5 x 73.7
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load"
67
67 67
67
67
_. _ _. -' _
output in dB(Aj a123 it not with Oenemlar In Oulof-Tesl'" low -speed exercise mode"
55
57 55
57
57
_Sound
Exercise duration
5 min
Engine
Engine type
GENERAC G-Farce 1000 Series
Number of cylinders
2
Displacement
999 cc
Cylinderblock
Aluminumw/ cast iron sleeve
Valve arrangement
Overhead valve
Ignition system W
1.syS16
Solid -stale w/magneto
Govemor
Electronic
Compression mite
9.5:1
Slater
12VOC
:OrI capacity Including filler
Applox, 19 qt/ 1.8 L
Operating rpm
3,600
Fuel consumption
Natural gas 1131fir(ma/hr)
1/2 Load
204 (5,78) 228 (6.46) 164 (4.64) 203 (5.75)
Full Load
301 (8.52) 327 (9.26) 287 (8.13) 306 (8,66)
Liquid propane 0/hr (gable) [Oil
lt2 Load
87 (2.37)18.99) 92 (2.53) [9.57) 86 (2,36) J8951 92 (2,53) [9.57J
Full Load
130 (3,56) [13.481 142(3,90)[1477J 136 (3.74) [14,151 142 (3.90)114.77J
Note: Fuel pipe must he stand far full load. Required lust pressure to generator fuel
inlet at all load ranges - 3.5-7 in water column (0.87-1.74 kPa) for NG, 10-12 In cooler column (2.49-299 kPa) for LP
gas, For BTU content, mulliply Bs/hr x 2500 (LP) aft /hr x 1000 INS). For Megajoule content, mulliply m3/nr x 93,15 (LP) or m3/Ar x 37.26 (NO).
Controls
Two-line plain lexl multilingual LCO
Simple user Interlace for ease of operation.
Mode hunons AUTO
Automatic sad an uglily failure. Weekly, Ift-weakty, or Monthly selectable exerciser.
MANUAL
Start wim slater control, unit slays on. If utility falls, Transfer to load takes place.
OFF
Stops unit. Pourer is removed. Control and charger still operate.
Ready to Ruo/Malnlenance messages
Standard
inputs run hours Indicallon
Standard
Programmable start delay between 2-1500 seconds
Standard (programmable by dealer only)
'HlilityVoltage Loss/Relum to U11h7y adjustable (brownout sett
From 140471 V/190-216 V
Future Set Capable Exercaer/Exerclser Set Error warning
Standard
SunuAlarINMainleiwice'ldgs
50 evens each
Engine sieri sequence -
Cyclic cranking: 16 sec on, 7 real (90 sec maximum duration).
Sider loc&oul -
Stater cannot re-engage until sec after engine has slopped.
Smart Battery Charger
Standard
Charger FaulVMissing AC warning
Slandard
Law Battery/Battery Problem Protection and Battery Condition Indication
Standard
Automatic Voltage Begulallun wilt Over ano Under Voltage
Standard
_PrrileoAon
Under-F7equenc9/Overload%SlepperOvate umnt Prolection
Standard
Salary Fused%Fuse Pratilem Proleil7dn
Slandard
Automatic Low Oil Pressure/High Oil Temperature Shuldawn
Standard
Overcmnk/Overspead (@ 72 Hz)Apm Sense Loss Shuldawn
Standard
High Engine Temperature Shutdown
Standard
Internal FayhAnmrrec( Wiiiog aoteclian
Standard
Common external fault capablllly
Standard
Fieldupgadahle liriawa`re
Standard
"Sound levels are taken from the from of the generator. Sound levels taken from other sides of the generator may be higher depending on Insallalion parameters, Bating deBnNans -Standby: Applicable for supplying
emergency paver for the duration of Use utility power outage. No overload apabikq Is available
for this sling. (All ratings in accordance vda BS5514, IS03046 and OIN6271).' Maximum aawll amps and current are
subject to and Ilmled by such actors as fuel BTU/megajoule content, ambient temperature,alfitude,
engine power and condition, etc. Maximum power decreases appronmatety 3.5%tor each 1,00 it (304.8 m) above sea