HomeMy WebLinkAbout07/05/2022 - F211334-1068924,1068924,1068924,1068924,1070439Concrete Compression Test Report 5058 Brush Creek Rd. Fort Worth, TX 76119 (817)496-5600 Alpha Testing, LLC TBPE Firm No. 813 FIELD DATA Placement Location:PAVING Project Desc:CHICKEN N PICKLE GRAPEVINE OFF CHAMPAGNE BOULEVARD AND MERLOT AVENUE Our Report #:F211334-1068924-S1 CHICKEN N PICKLE 104 ARMOUR ROAD NORTH KANSAS CITY, MO 64116 ALEX STEHLATTN: Date Placed:6/28/2022 Time Placed:3:13 AM 5.00 2.6 79 88 Date Received:N/A Concrete Supplier:BURNCO Submitted By:Russell, Nicholas Plant Number:506 Delivery Ticket No.:50923385 144.8 Batch Time:2:22:00 AM Tested For: Lab No.: Cure Type: Date Tested: Age (Days): Max Load: Area: Sq. In.PSI: Cap Spec: CYLINDER COMPRESSION TEST RESULTS (ASTM C-231) Avg. Length Avg. Width Avg Depth/ Diameter Cast By:ALPHA Cured Specification:ASTM C-31 Mix ID:30U500BG Break Type: Sample Location:95 FT E OF NW CORNER PM:PAUL DELANEY Date Issued:07/05/2022 Specified Strength:3000 Result Air Content: Ambient Temp (F): Concrete Temp (F): Unit Weight: Slump (ASTM C-143): Weather: Wind: Clear Initial Curing Method:Protected Area, Covered with Lid Final Curing Method:Moist Room 185 7/5/2022 7 3317012.56 2640LABC-1231 8.00 N/A 4.003 186 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 187 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 188 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 189 8/23/2022 56 012.56LABC-1231 8.00 N/A 4.00 CC: Respectfully Submitted By:__________________________________________________________ of Alpha Testing, LLC Geotechnical Engineering * Construction Materials Testing * Environmental Engineering * Consulting 490884 Break Types: 1: Cone 2: Cone and Split 3: Columnar 4: Diagonal 5: Single Sided Fracture 6: Double Sided Fracture * = Specification out of spec Test Method: Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231, C173, C1064, C31, C1231 and C138. Compression strength tests per ASTM C39. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. This report shall not be reproduced except in full, without the prior written approval of Alpha Testing. Page 1 of 5 Concrete Compression Test Report 5058 Brush Creek Rd. Fort Worth, TX 76119 (817)496-5600 Alpha Testing, LLC TBPE Firm No. 813 FIELD DATA Placement Location:PAVING Project Desc:CHICKEN N PICKLE GRAPEVINE OFF CHAMPAGNE BOULEVARD AND MERLOT AVENUE Our Report #:F211334-1068924-S2 CHICKEN N PICKLE 104 ARMOUR ROAD NORTH KANSAS CITY, MO 64116 ALEX STEHLATTN: Date Placed:6/28/2022 Time Placed:4:20 AM 6.5 n/a 78 87 Date Received:N/A Concrete Supplier:BURNCO Submitted By:Russell, Nicholas Plant Number:506 Delivery Ticket No.:50923439 144.8 Batch Time:3:36:00 AM Tested For: Lab No.: Cure Type: Date Tested: Age (Days): Max Load: Area: Sq. In.PSI: Cap Spec: CYLINDER COMPRESSION TEST RESULTS (ASTM C-231) Avg. Length Avg. Width Avg Depth/ Diameter Cast By:ALPHA Cured Specification:ASTM C-31 Mix ID:30U500BG Break Type: Sample Location:90 FT N 95 FT E OF OF NW CORNER PM:PAUL DELANEY Date Issued:07/05/2022 Specified Strength:3000 Result Air Content: Ambient Temp (F): Concrete Temp (F): Unit Weight: Slump (ASTM C-143): Weather: Wind: Clear Initial Curing Method:Protected Area, Covered with Lid Final Curing Method:Moist Room 190 7/5/2022 7 3713012.56 2960LABC-1231 8.00 N/A 4.003 191 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 192 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 193 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 194 8/23/2022 56 012.56LABC-1231 8.00 N/A 4.00 Notes:Air meter didn't hold air CC: Respectfully Submitted By:__________________________________________________________ of Alpha Testing, LLC Geotechnical Engineering * Construction Materials Testing * Environmental Engineering * Consulting 490885 Break Types: 1: Cone 2: Cone and Split 3: Columnar 4: Diagonal 5: Single Sided Fracture 6: Double Sided Fracture * = Specification out of spec Test Method: Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231, C173, C1064, C31, C1231 and C138. Compression strength tests per ASTM C39. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. This report shall not be reproduced except in full, without the prior written approval of Alpha Testing. Page 2 of 5 Concrete Compression Test Report 5058 Brush Creek Rd. Fort Worth, TX 76119 (817)496-5600 Alpha Testing, LLC TBPE Firm No. 813 FIELD DATA Placement Location:PAVING Project Desc:CHICKEN N PICKLE GRAPEVINE OFF CHAMPAGNE BOULEVARD AND MERLOT AVENUE Our Report #:F211334-1068924-S3 CHICKEN N PICKLE 104 ARMOUR ROAD NORTH KANSAS CITY, MO 64116 ALEX STEHLATTN: Date Placed:6/28/2022 Time Placed:5:47 AM 6.50 n/a 77 86 Date Received:N/A Concrete Supplier:BURNCO Submitted By:Russell, Nicholas Plant Number:506 Delivery Ticket No.:50923489 146 Batch Time:4:56:00 AM Tested For: Lab No.: Cure Type: Date Tested: Age (Days): Max Load: Area: Sq. In.PSI: Cap Spec: CYLINDER COMPRESSION TEST RESULTS (ASTM C-231) Avg. Length Avg. Width Avg Depth/ Diameter Cast By:ALPHA Cured Specification:ASTM C-31 Mix ID:30U500BG Break Type: Sample Location:50 FT N 95 FTME OF SW CORNER PM:PAUL DELANEY Date Issued:07/05/2022 Specified Strength:3000 Result Air Content: Ambient Temp (F): Concrete Temp (F): Unit Weight: Slump (ASTM C-143): Weather: Wind: Clear Initial Curing Method:Protected Area, Covered with Lid Final Curing Method:Moist Room 195 7/5/2022 7 3058012.56 2430LABC-1231 8.00 N/A 4.001 196 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 197 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 198 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 199 8/23/2022 56 012.56LABC-1231 8.00 N/A 4.00 Notes:Air meter didn't hold air CC: Respectfully Submitted By:__________________________________________________________ of Alpha Testing, LLC Geotechnical Engineering * Construction Materials Testing * Environmental Engineering * Consulting 490886 Break Types: 1: Cone 2: Cone and Split 3: Columnar 4: Diagonal 5: Single Sided Fracture 6: Double Sided Fracture * = Specification out of spec Test Method: Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231, C173, C1064, C31, C1231 and C138. Compression strength tests per ASTM C39. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. This report shall not be reproduced except in full, without the prior written approval of Alpha Testing. Page 3 of 5 Concrete Compression Test Report 5058 Brush Creek Rd. Fort Worth, TX 76119 (817)496-5600 Alpha Testing, LLC TBPE Firm No. 813 FIELD DATA Placement Location:PAVING Project Desc:CHICKEN N PICKLE GRAPEVINE OFF CHAMPAGNE BOULEVARD AND MERLOT AVENUE Our Report #:F211334-1068924-S4 CHICKEN N PICKLE 104 ARMOUR ROAD NORTH KANSAS CITY, MO 64116 ALEX STEHLATTN: Date Placed:6/28/2022 Time Placed:8:35 AM 6.50 3.0 78 87 Date Received:N/A Concrete Supplier:BURNCO Submitted By:Russell, Nicholas Plant Number:506 Delivery Ticket No.:50923618 146 Batch Time:7:43:00 AM Tested For: Lab No.: Cure Type: Date Tested: Age (Days): Max Load: Area: Sq. In.PSI: Cap Spec: CYLINDER COMPRESSION TEST RESULTS (ASTM C-231) Avg. Length Avg. Width Avg Depth/ Diameter Cast By:ALPHA Cured Specification:ASTM C-31 Mix ID:30U500BG Break Type: Sample Location:45 FT N 35 FT W OF SW CORNER PM:PAUL DELANEY Date Issued:07/05/2022 Specified Strength:3000 Result Air Content: Ambient Temp (F): Concrete Temp (F): Unit Weight: Slump (ASTM C-143): Weather: Wind: Clear Initial Curing Method:Protected Area, Covered with Lid Final Curing Method:Moist Room 200 7/5/2022 7 2661012.56 2120LABC-1231 8.00 N/A 4.003 201 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 202 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 203 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 204 8/23/2022 56 012.56LABC-1231 8.00 N/A 4.00 CC: Respectfully Submitted By:__________________________________________________________ of Alpha Testing, LLC Geotechnical Engineering * Construction Materials Testing * Environmental Engineering * Consulting 490887 Break Types: 1: Cone 2: Cone and Split 3: Columnar 4: Diagonal 5: Single Sided Fracture 6: Double Sided Fracture * = Specification out of spec Test Method: Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231, C173, C1064, C31, C1231 and C138. Compression strength tests per ASTM C39. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. This report shall not be reproduced except in full, without the prior written approval of Alpha Testing. Page 4 of 5 Concrete Compression Test Report 5058 Brush Creek Rd. Fort Worth, TX 76119 (817)496-5600 Alpha Testing, LLC TBPE Firm No. 813 FIELD DATA Placement Location:FOOTING Project Desc:CHICKEN N PICKLE GRAPEVINE OFF CHAMPAGNE BOULEVARD AND MERLOT AVENUE Our Report #:F211334-1070439 CHICKEN N PICKLE 104 ARMOUR ROAD NORTH KANSAS CITY, MO 64116 ALEX STEHLATTN: Date Placed:6/28/2022 Time Placed:10:00 AM 8.00 2.6 80 85 Date Received:N/A Concrete Supplier:BURNCO Submitted By:Russell, Nicholas Plant Number:501 Delivery Ticket No.:50923653 142 Batch Time:8:32:00 AM Tested For: Lab No.: Cure Type: Date Tested: Age (Days): Max Load: Area: Sq. In.PSI: Cap Spec: CYLINDER COMPRESSION TEST RESULTS (ASTM C-231) Avg. Length Avg. Width Avg Depth/ Diameter Cast By:ALPHA Cured Specification:ASTM C-31 Mix ID:30W500BG Break Type: Sample Location:NE CORNER OF HOST SHACK PM:PAUL DELANEY Date Issued:07/05/2022 Specified Strength:3000 Result Air Content: Ambient Temp (F): Concrete Temp (F): Unit Weight: Slump (ASTM C-143): Weather: Wind: Partly Cloudy Initial Curing Method:Protected Area, Covered with Lid Final Curing Method:Moist Room 205 7/5/2022 7 2517012.56 2000LABC-1231 8.00 N/A 4.002 206 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 207 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 208 7/26/2022 28 012.56LABC-1231 8.00 N/A 4.00 209 8/23/2022 56 012.56LABC-1231 8.00 N/A 4.00 Notes:Test Results verbally reported to Foreman. CC: Respectfully Submitted By:__________________________________________________________ of Alpha Testing, LLC Geotechnical Engineering * Construction Materials Testing * Environmental Engineering * Consulting 490888 Break Types: 1: Cone 2: Cone and Split 3: Columnar 4: Diagonal 5: Single Sided Fracture 6: Double Sided Fracture * = Specification out of spec Test Method: Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231, C173, C1064, C31, C1231 and C138. Compression strength tests per ASTM C39. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. This report shall not be reproduced except in full, without the prior written approval of Alpha Testing. Page 5 of 5