Loading...
HomeMy WebLinkAboutORD 2023-081ORDINANCE NO. 2023-081 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF GRAPEVINE, TEXAS AMENDING CHAPTER 7 OF THE GRAPEVINE CODE OF ORDINANCES, BUILDINGS AND CONSTRUCTION, RELATING TO THE ADOPTION OF THE 2021 INTERNATIONAL BUILDING CODE AS PUBLISHED BY THE INTERNATIONAL CODE COUNCIL, ADOPTION OF THE 2020 NATIONAL ELECTRICAL CODE AS PUBLISHED BY THE NATIONAL FIRE PROTECTION ASSOCIATION, ADOPTION OF THE 2021 INTERNATIONAL RESIDENTIAL CODE AS PUBLISHED BY THE INTERNATIONAL CODE COUNCIL, ADOPTION OF THE 2021 INTERNATIONAL MECHANICAL CODE AS PUBLISHED BY THE INTERNATIONAL CODE COUNCIL, ADOPTION OF THE 2021 INTERNATIONAL PLUMBING CODE AS PUBLISHED BY THE INTERNATIONAL CODE COUNCIL, ADOPTION OF THE 2021 INTERNATIONAL FUEL GAS CODE AS PUBLISHED BY THE INTERNATIONAL CODE COUNCIL, ADOPTION BY REFERENCE THE SWIMMING POOL AND SPA CODE AS ADOPTED AND AMENDED BY THE STATE OF TEXAS; PROVIDING AMENDMENTS TO SAME; REPEALING CONFLICTING ORDINANCES; PROVIDING A SEVERABILITY CLAUSE; PROVIDING A PENALTY, NOT TO EXCEED TWO THOUSAND DOLLARS ($2,000.00); DECLARING AN EMERGENCY AND PROVIDING AN EFFECTIVE DATE WHEREAS, the City of Grapevine has previously adopted model codes for building, plumbing, electrical, mechanical, and fuel gas issued through Chapter 7 of the Code of Ordinance; and WHEREAS, the International Code Council has promulgated updated model codes, and recommends same for adoption by municipalities; and WHEREAS, the City wishes to update its model codes, including appropriate amendments thereto; and WHEREAS, the State of Texas has adopted a swimming pool and spa code to be enforced by municipalities; and WHEREAS, all constitutional and statutory prerequisites for the approval of this ordinance have been met, including but not limited to the Open Meetings Act and Chapter 211 of the Local Government Code; and WHEREAS, the City Council has determined that the passage of this Ordinance is ii " the best interests of the health, safety, and welfare of the public. OW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF G RAPEVINE, TEXAS: Section 1. That all matters stated hereinabove are found to be true and correct a rid are incorporated herein by reference as if copied in their entirety. Section 2. That Chapter 7, Buildings and Construction, Article I, Sections 7-1 through 7-3 are hereby deleted and replaced with the following: ARTICLE I. - IN GENERAL Sec 7-1. — BUILDING CODE The City of Grapevine hereby adopts the 2021 edition of the International Code Family consisting of the International Building Code, NFPA 2020 National Electric Code, International Residential Code, International Mechanical Code, International Plumbing Code, International Fuel Gas Code, and International Swimming Pool and Spa Code as adopted by the State of Texas with regional amendments as published by the International Code Council, Inc., save and except such portions as are deleted or amended by this ordinance, and the same are hereby adopted and incorporated as if fully set out in length herein. One copy of the 2021 edition of the International Code Family and the NFPA 2020 National Electrical Code shall be on file with the city secretary. From the date on which this ordinance shall take effect, the provisions thereof shall be controlling within the limits of the City of Grapevine and its extraterritorial jurisdiction. Sec 7-2. - Same —Conflict with other regulations. When any portion of this code conflicts with state law or any other code or ordinance adopted by the city, the most restrictive requirements shall apply. Sec 7-3. - Same —Amendments. Section 101.1 Title; change [NAME OF JURISDICTION} to read "City of Grapevine, TX" Section 101.4; change to read as follows: 101.4 Referenced codes. The other codes listed in Sections 101.4.1 through 101.4.8 and referenced elsewhere in this code, when specifically adopted, shall be considered part of the requirements of this code to the prescribed extent of each such reference. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be O rdinance No. 2023-081 2 considered to reference the amendments as well. Any reference to NFPA 70 or the Electrical Code shall mean the Electrical Code as adopted. Where the enforcement of a provision of this code would violate the conditions of the listing of appliances or equipment, the conditions of the listing and the manufacturer's installation instructions shall apply. Section 101.4.6; change to read as follows: 101.4.6 Energy. The provisions of the International Energy Conservation Code as adopted by the State of Texas shall apply to all matters {remainder of text unchanged). Section 101.4.7; change to read as follows: 101.4.7 Existing buildings. All matters regarding the repair, alteration, change of occupancy, addition to and relocation of existing buildings shall be governed by the existing building provisions adopted by the City and Zoning Ordinance. Section 101.4.8; add the following: 101.4.8 Electrical. The provisions of the Electrical Code shall apply to the installation of electrical systems, including alterations, repairs, replacement, equipment, appliances, fixtures, fittings and appurtenances thereto. Sections 103 and 103.1; amend to insert the Department Name: 103.1 Creation of enforcement agency. The Grapevine Building Services Department is hereby created and the official in charge thereof shall be known as the Building Official. Section 104.2.1 Section deleted. Section 104.10.1; Flood hazard areas. Section deleted. Note: Sections 104.2.1, 104.10.1, 110.3.12.1, 1612, and 3114 are all inter- connected related to flood hazard areas, and amendments or deletions should be considered as a whole. Section 105.2 Work exempt from permit; under sub -title entitled "Building" add text to items 1, 6, and 11 and delete item 2 as follows: Building: 1. One-story detached accessory structures used as tool and storage sheds, playhouses and similar uses, provided the floor area does not exceed 120 square feet (11 m2) require permits but are exempt from fees. Such structures Ordinance No. 2023-081 3 must comply with all provisions of the Zoning Ordinance relative to the zoning district. 2. {Deleted} 3.-5. {Remain Unchanged} 6. Sidewalks and driveways not more than 30 inches above grade, and not over any basement or story below; however, commercial drives, fire lanes and parking areas require permits. 7.-10. {Remain Unchanged} 11. Swings and other playground equipment accessory to detached one -and two- family dwellings; however, such structures must comply with all provisions of the Zoning Ordinance relative to height and setbacks. 12.-13. {Remain Unchanged} - Section 109 Fees, is hereby amended as follows: EXHIBIT "A" TABLE NO. 1-A BUILDING PERMIT FEES See attached Exhibit "A", Table NO. 1-A O rd i r—iance No. 2023-081 4 TABLE NO. I -A PERMIT FEES OR ALL BUILDING PERMITS EXCEPT FOR RESIDENTIAL DWELLNGS TOTAL VALUATION FEE $1.00 to $500.00 $50.00 $501.00 to $2,000.00 $50.00 for the first $500.00 plus $4.00 for each additional $100.00, or fraction thereof, to and including $2,000.00 $2,001.00 to $75.00 for the first $2,000.00 plus $16.00 for each additional $1,000.00, $25.000.00 or fraction thereof, to and including $25,000.00 $25,001.00 to $500.00 for the first $25,000.00 plus $13.50 for each additional $50,000.00 $1,000.00, or fraction thereof, to and including $50,000.00 $50,001.00 to $750.00 for the first $50,000.00 plus $8.25 for each additional $100,000.00 $1,000.00, or fraction thereof, to and including $100,000.00 $100,001.00 to $1,250.00 for the first $100,000.00 plus $6.25 for each additional $500,000.00 $1,000.00, or fraction thereof, to and including $500,000.00 $500,001.00 to $4,000.00 for the first $500,000.00 plus $5.50 for each additional $1,000,000.00 $1,000.00, or fraction thereof, to and including $1,000,000.00 $1,000,001.00 and $7,500.00 for the first $1,000,000.00 plus $5.00 for each additional u $1,000.00, or fraction thereof BUILDING PERMIT FEES FOR RESIDENTIAL DWELLINGS NEW ADDITIONS ALTERATIONS CONSTRUCTION R3 RESIDENTIAL DWELLINGS $ .55 / Square $ 1.00 / Square Foot $ 1.00 / Square Foot Foot TOTAL AREA of of ALTERATION AREA (Detached one and TOTAL AREA ADDITION two family UNDER ROOF dwellings, townhomes not more than 3-stores in height with a separate means of egress) R2 RESIDENTIAL $ .30 / Square $ 1.00 / Square Foot $ 1.00 / Square Foot DWELLINGS Foot TOTAL AREA of of ALTERATION AREA TOTAL AREA ADDITION UNDER ROOF Ordinance No. 2023-081 5 (Apartments, condominiums, three and four family dwellings, etc) SIMPLE ALTERATION PERMITS Projects in which FLAT FEE $150.00 square footage does not apply as determined by the Building Official. (Window replacement, foundation repair, siding replacement, etc) UNENCLOSED OTHER INSPECTIONS AND FEES: 1. Certificate of Occupancy................................................................................................... $ 50.00 2. Inspections outside of normal business hours .................. $50-00 per hour* (minimum charge- two hours) 3. Reinspection fees assessed under provisions of Section 108.5 ................................................. $50-00 4. Inspections for which no fee is specifically indicated .... $50.00 per hour* (minimum charge- one-half hour) 5. Additional plan review required by changes, additions or revisions to plans .................... $50.00 per hour* 6. For use of outside consultants for plan checking and inspections, or both ..........................actual costs' 7. Foundation only permits or any partial permit ................ 10% of building permit fee in addition to building permit fee 8. Plan review fee (not applicable to Group R-3 private residences) ................ 65% of building permit fee in addition to building permit fee 9. Building permit fees for the Grapevine- Colleyville Independent School District ............... 25% of the fees established in Table No. 1 -A- Building Permit Fees 10. Project valuation to be determined by the regional construction valuation table, adopted by the city, or the contract valuation whichever is greater. Permit valuations shall include all work required for a completed project, including profit, but need not include the value or cost of the land. Other methods for determining Ordinance No. 2023-081 6 the project valuations for unique or unusual projects may be approved by the Building Official. 11. Public Works Antenna or Equipment Installation Charge on City Owned Water Towers Only ......... $350.00 *Or the total hourly cost of the jurisdiction, whichever is the greatest. This cost shall include supervision, overhead, equipment, hourly wages and fringe benefits of the employees involved. ** Actual costs include administrative and overhead costs. LOT DRAINAGE FEES Single Family & Duplex Swimming Pools All remaining classifications Full Acre Cost Portion Other than Full Acre $150.00 $150.00 $350.00 Per Acre $350.00 x Percentage of Full Ordinance No. 2023-081 7 EXHIBIT "B" BUILDING VALUATION DATA The following table, based on the table published in Building Valuation Data ICCSAFE.org, shall be used to determine construction costs per square foot. Adjustments may be determined to be necessary by the Building Official for unusual projects. The unit costs are intended to comply with the description of "valuation" in Section 109.3 of the 2021 International Building Code and thus include architectural, structural, electrical, plumbing and mechanical work. The unit costs also include the contractor's profit, which should not be omitted. If there are differences between the value of the project calculated using this table, and the contract valuation, the greater number shall be used. This table shall also be used to calculate plan review fees. Exhibit "B" BUILDING VALUATION TABLE (cost per square foot) Group (2021 International Building Code) Type of Construction I 1 II II IIIA IIIB 1 VA VB A B A B V A-1 Assembly, theaters, with 250.3 241.9 235.6 226.1 212.3 206.1 218.8 197. 190.3 stage 9 1 3 0 2 8 3 45 3 assembly, theaters, 229.4 220.9 214.6 205.1 191.3 185.2 197.8 176. 169.3 without stage 2 4 6 2 5 1 6 48 5 A-2 Assembly, nightclubs 196.1 190.2 185.6 178.0 167.8 163.2 171.7 151. 146.7 3 9 2 2 2 0 0 89 1 A-2 Assembly, restaurants, 195.1 189.2 183.6 177.0 165.8 162.2 170.7 149. 145.7 bars, banquet halls 3 9 2 2 2 0 0 89 1 A-3 Assembly, churches 232.0 223.5 217.2 207.7 194.3 189.1 200.4 179. 172.3 4 7 9 5 4 9 9 48 5 --A-ssefflbly, A-3 general, community halls, 194.1 185.6 178.4 169.8 155.0 149.9 162.6 140. 134.1 libraries, museums 7 9 1 7 9 6 1 23 0 A-4 Assembly, arenas 228.4 219.9 212.6 204.1 189.3 184.2 196.8 174. 168.3 2 4 6 2 5 1 6 48 5 B Business 202.3 194.9 188.4 179.1 163.5157.4 172.1 143. 137.4 0 2 4 8 5 2 3 89 6 E Educational 212.0 �204.7 198.8 190.2 177.2168.2 183.7 155. 150.2 3 0 2 5 7 9 0 00 6 F-1 Factory and industrial, 119.5 113.9 1-2 107.3 103.4 92.64 88.38 99.02 76.3 71.7 moderate hazard 3 1 8 5 3 Ordinance No. 2023-081 8 Factory and industrial, lo hazard INEWEREENE III Hazard, explosives1• 11 • • .• :• :1 • • •• ® I li 1• 11 • • •• :• :1 • • •• •� 1 10 Institutional 1-1, supervised environment • ME MENEM • • • 1 homes • ; ®facilities Institutional 1-4, day care Mercantile lip%11t' �� • NMI • :•: moderate hazard 1 1 •. • •� •i .� • . •i • • . . 1 11111W111111 Storage, low hazard WOMEN Utility, miscellaneous III EEEE�Emmm. Add 0.5 percent to total cost for each story over three and deduct 20 percent for shell only buildings. This table is based on the August 2020 Building Valuation Data published by the International Code Council. Ordinance No. 2023-081 9 Section 109; add Section 109.7 to read as follows: 109.7 Re -inspection Fee. A fee as established by city council resolution may be charged when: 1. The inspection called for is not ready when the inspector arrives; 2. No building address or permit card is clearly posted; 3. City approved plans are not on the job site available to the inspector; 4. The building is locked or work otherwise not available for inspection when called; 5. The job site is red -tagged twice for the same item; 6. The original red tag has been removed from the job site. 7. Failure to maintain erosion control, trash control or tree protection. Any re -inspection fees assessed shall be paid before any more inspections are made on that job site. SECTION 202; amend definition of AMBULATORY CARE FACILITIES as follows: AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing or similar care on a less than 24-hour basis to persons who are rendered incapable of self-preservation by the services provided. This group may include but not be limited to the following: - Dialysis centers - Sedation dentistry - Surgery centers - Colonic centers - Psychiatric centers Section 202; add definition of ASSISTED LIVING FACILITIES to read as follows: ASSISTED LIVING FACILITIES. A building or part thereof housing persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment which provides personal care services where the occupants are capable of responding to an emergency situation without physical assistance from staff. Section 202; amend definition of REPAIR GARAGE as follows: REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor vehicles. This occupancy shall also include garages involved in minor repair, modification and servicing of motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor part replacement and other such minor repairs. Ordinance No. 2023-081 10 Section 202; amend definition of SPECIAL INSPECTOR to read as follows: SPECIAL INSPECTOR. A qualified person employed or retained by an approved agency who shall prove to the satisfaction of the registered design professional in responsible charge and the Building Official as having the competence necessary to inspect a particular type of construction requiring special inspection. Section 202; amend definition of HIGH-RISE BUILDING to read as follows: Option B Section 202; amend definition to read as follows: HIGH-RISE BUILDING. A building with an occupied floor located more than 55 feet (16, 764 mm) above the lowest level of fire department vehicle access. Section 304.1; add the following to the list of occupancies: Fire stations Police stations with detention facilities for 5 or less Section 307.1.1; add the following sentence to item 4: 4. Cleaning establishments... {Text unchanged} ...with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 711 or both. See also IFC Chapter 21, Dry Cleaning Plant provisions. Section 403.1, Exception 3; change to read as follows: 3. The open-air portion of a building [remainder unchanged] Section 403.3, Automatic Sprinkler System. Delete exception; Section 403.3.2; change to read as follows: [F] 403.3.2 Water supply to required fire pumps. In buildings that are more than 120 feet in building height, required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. Exception: {No change to exception.} Ordinance No. 2023-081 11 Section 404.10; change to read as follows: Section 404.10 Exit Stairways in an atrium. Where an atrium contains an interior exit access stairway all the following shall be met: [Remainder Unchanged] Section 406.2.7.1; section added as follows: 406.2.7.1 Prohibited locations. Electric vehicle charging stations are expressly prohibited indoors and within or on any public or private parking garage. Exceptions: 1. Group R-3 buildings and their accessory structures on the same lot. 2. Where approved by the Building Official and fire code official. Section 406.3.3.1 Carport separation; add sentence to read as follows: A fire separation is not required between a Group R-2 and U carport provided that the carport is entirely open on all sides and that the distance between the two is at least 10 feet (3048 mm). Section 423.5.1; change to read as follows: 423.5.1 Required occupant capacity. The required occupant capacity of the storm shelter shall include all of the buildings on the site and shall be the total occupant load of the classrooms, vocational rooms and offices in the Group E occupancy. Exceptions: 1. Where a new building is being added on an existing Group E site, and where the new building is not of sufficient size to accommodate the required occupant capacity of the storm shelter for all of the buildings on the site, the storm shelter shall at a minimum accommodate the required occupant capacity for the new building. 2. Where approved by the Building Official, the required occupant capacity of the shelter shall be permitted to be reduced by the occupant capacity of any existing storm shelters on the site. 3. Where approved by the Building Official, the actual number of occupants for whom each occupied space, floor or building is designed, although less than those determined by occupant load calculation, shall be permitted to be used in the determination of the required design occupant capacity for the storm shelter. Ordinance No. 2023-081 12 Section 503.1.; add sentence to read as follows: 503.1. General. [Existing Text to remain], add the following text: Where a building contains more than one distinct type of construction, the building shall comply with the most restrictive area, height, and stories, for the lesser type of construction or be separated by fire walls, except as allowed in Section 510. Table 506.2; delete footnote (i) from table: {Delete.} Section 506.3.1; add sentence to read as follows: 506.3.1 Minimum percentage of perimeter. [Existing Text remains], add the following text: In order to be considered as accessible, if not in direct contact with a street or fire lane, a minimum 10-foot-wide pathway meeting fire department access from the street or approved fire lane shall be provided. Section 708.4.2; change sentence to read as follows: 708.4.2 Fireblocks and draftstops in combustible construction. [Body of text unchanged] Exceptions: 1. Buildings equipped with an automatic sprinkler system installed throughout in accordance with Section 903.3.1.1, or in accordance with Section 903.3.1.2 provided that sprinkler protection is provided in the space between the top of the fire partition and the underside of the floor or roof sheathing, deck or slab above as required for systems complying with Section 903.3.1.1. Portions of buildings containing concealed spaces filled with noncombustible insulation as permitted for sprinkler omission shall not apply to this exception for draftstopping. 2. [Unchanged] Section 718.3; change sentence to read as follows: 718.3 Draftstopping in floors. [Body of text unchanged] Exception: Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. and provided that in combustible construction, sprinkler protection is provided in the concealed floor space. Ordinance No. 2023-081 13 Section 718.4; change sentence to read as follows: 718.4 Draftstopping in attics. [Body of text unchanged] Exception: Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and provided that in combustible construction, sprinkler protection is provided in the attic space. Section 901.6.1; add Section 901.6.1.1 to read as follows: 901.6.1.1 Standpipe Testing. Building owners/managers must maintain and test standpipe systems as per NFPA 25 requirements. The following additional requirements shall be applied to the testing that is required every 5 years: 1. The piping between the Fire Department Connection (FDC) and the standpipe shall be backflushed or inspected by approved camera when foreign material is present or when caps are missing, and also hydrostatically tested for all FDC's on any type of standpipe system. Hydrostatic testing shall also be conducted in accordance with NFPA 25 requirements for the different types of standpipe systems. 2. For any manual (dry or wet) standpipe system not having an automatic water supply capable of flowing water through the standpipe, the tester shall connect hose from a fire hydrant or portable pumping system (as approved by the fire code official) to each FDC, and flow water through the standpipe system to the roof outlet to verify that each inlet connection functions properly. Confirm that there are no open hose valves prior to introducing water into a dry standpipe. There is no required pressure criteria at the outlet. Verify that check valves function properly and that there are no closed control valves on the system. 3. Any pressure relief, reducing, or control valves shall be tested in accordance with the requirements of NFPA 25. All hose valves shall be exercised. 4. If the FDC is not already provided with approved caps, the contractor shall install such caps for all FDC's as required by the fire code official. 5. Upon successful completion of standpipe test, place a blue tag (as per Texas Administrative Code, Fire Sprinkler Rules for Inspection, Test and Maintenance Service (ITM) Tag) at the bottom of each standpipe riser in the building. The tag shall be check -marked as "Fifth Year" for Type of ITM, and the note on the back of the tag shall read "5 Year Standpipe Test" at a minimum. 6. The procedures required by Texas Administrative Code Fire Sprinkler Rules with regard to Yellow Tags and Red Tags or any deficiencies noted during the testing, including the required notification of the local Authority Having Jurisdiction (fire code official) shall be followed. Ordinance No. 2023-081 14 7. Additionally, records of the testing shall be maintained by the owner and contractor, if applicable, as required by the State Rules mentioned above and NFPA 25. 8. Standpipe system tests where water will be flowed external to the building shall not be conducted during freezing conditions or during the day prior to expected nighttime freezing conditions. 9. Contact the fire code official for requests to remove existing fire hose from Class II and III standpipe systems where employees are not trained in the utilization of this firefighting equipment. All standpipe hose valves must remain in place and be provided with an approved cap and chain when approval is given to remove hose by the fire code official. Section 903.1.1; change to read as follows: 903.1.1 Alternative Protection. Alternative automatic fire -extinguishing systems complying with Section 904 shall be permitted in addition to automatic sprinkler protection where recognized by the applicable standard, or as approved by the fire code official. Section 903.2; add paragraph to read as follows and delete the exception for telecommunications buildings: Automatic Sprinklers shall not be installed in elevator machine rooms, elevator machine spaces, and elevator hoistways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances. Storage shall not be allowed within the elevator machine room. Signage shall be provided at the entry doors to the elevator machine room indicating "ELEVATOR MACHINERY — NO STORAGE ALLOWED." Sections 903.2.1.1, 903.2.1.3, and 903.2.1.4; change to read as follows: 903.2.1.1 Group A-1. {text unchanged}.....where one of the following conditions exists: 1. The building area exceeds 6,000 square feet. 2. {text unchanged} 3. {text unchanged} 4. {text unchanged} 903.2.1.3 Group A-3. {text unchanged}.....where one of the following conditions exists: 1. The building area exceeds 6,000 square feet. 2. The building area has an occupant load of 300 or more. Ordinance No. 2023-081 15 3. {text unchanged} 903.2.1.4 Group A-4. {text unchanged}.....where one of the following conditions exists: 1. The building area exceeds 6,000 square feet. 2. {text unchanged} 3. {text unchanged} Section 903.2.3; change to read as follows: 903.2.3 Group E. {text unchanged}.....where one of the following conditions exists: 1. The building area exceeds 6,000 square feet. 2. {text unchanged} 3. {text unchanged} Section 903.2.4; change to read as follows: 903.2.4 Group F-1. {text unchanged}.....where one of the following conditions exists: 1. The building area exceeds 6,000 square feet. 2. {text unchanged} 3. {deleted} Section 903.2.4.2; change to read as follows: 903.2.4.2 Group F-1 distilled spirits. An automatic sprinkler system shall be provided throughout a Group F-1 building used for the manufacture of distilled spirits involving more than 120 gallons of distilled spirits (>16% alcohol) in the fire area at any one time. Section 903.2.7; change to read as follows: 903.2.7 Group M. {text unchanged}.....where one of the following conditions exists: 1. The building area exceeds 6,000 square feet. 2. {text unchanged} 3. {deleted} Section 903.2.8; change to read as follows: 903.2.8. Group R. {text unchanged} .... With a Group R fire area. Ordinance No. 2023-081 16 Exception: Group R-3 buildings less than 6,000 square feet in area. For the purpose of this provision, fire walls shall not define separate buildings. Section 903.2.9.1; change to read as follows: Section 903.2.9.1 Group S-1 repair garages. {text unchanged) ... as shown: 1. Buildings 6,000 square feet or greater in area containing a repair garage. 2. {deleted} 3. {text unchanged} 4. {text unchanged} Section 903.2.9.3; change to read as follows: 903.2.9.3 Group S-1 distilled spirits or wine. An automatic sprinkler system shall be provided throughout a Group S-1 building used for the bulk storage of distilled spirits or wine involving more than 120 gallons of distilled spirits or wine (>16% alcohol) in the fire area at any one time. Section 903.2.9.4; change to read as follows: Section 903.2.9.4 Group S-1 upholstered furniture and mattresses. An automatic sprinkler system shall be provided throughout a Group S-1 building where the area used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet. Section 903.2.9.5; section added as follows: 903.2.9.5 Self -Service Storage Facility. An automatic sprinkler system shall be installed throughout all self-service storage facilities. Section 903.2.10; change to read as follows: Section 903.2.10 Group S-2 parking garages. {text unchanged} ... where any of the following conditions exists: rt 1. Where the building area containing an enclosed parking garage in accordance with Section 406.6 is 6,000 square feet or greater. 2. Where the enclosed parking garage in accordance with Section 406.6 is located beneath other groups. Exception: Enclosed parking garages located beneath R-3 occupancies 3. Where the building area of an open parking garage in accordance with Section 406.5 is 6,000 square feet or greater and does not meet the requirements of Section 903.2.11.9. Ordinance No. 2023-081 17 Section 903.2.11; change 903.2.11.3 and add 903.2.11.7, 903.2.11.8, and 903.2.11.9 as follows: 903.2.11.3 Buildings 35 feet or more in height. An automatic sprinkler system shall be installed throughout buildings that have one or more stories, other than penthouses in compliance with Section 1510 of the International Building Code, located 35 feet or more above the lowest level of fire department vehicle access, measured to the finished floor. 903.2.11.7 High -Piled Combustible Storage. For any building with a clear height exceeding 12 feet (4572 mm), see Chapter 32 of the International Fire Code to determine if those provisions apply. 903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be protected by an approved automatic fire -extinguishing system. 903.2.11.9 Buildings over 6,000 sq. ft. An automatic sprinkler system shall be installed throughout all buildings with a building area 6,000 sq. ft. or greater and in all existing buildings that are enlarged to be 6,000 sq. ft. or greater. For the purpose of this provision, fire walls shall not define separate buildings. Exception: Open parking garages in compliance with section 406.5 where all of the following conditions apply: a. The structure is freestanding. b. The structure does not contain any mixed uses, accessory uses, storage rooms, electrical rooms, elevators or spaces used or occupied for anything other than motor vehicle parking. c. The structure does not exceed three stories. d. An approved fire apparatus access road is provided around the entire structure. Section 903.3.1.1.1; change to read as follows: 903.3.1.1.1 Exempt Locations. When approved by the fire code official, automatic sprinklers shall not be required in the following rooms or areas where such .{text unchanged}... because it is damp, of fire -resistance -rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the fire code official. 3. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling Ordinance No. 2023-081 18 or roof/ceiling assemblies having a fire -resistance rating of not less than 2 hours. 4. {Delete.} 5. Elevator machine rooms, machinery spaces, and hoistways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances. 6. {Delete.} Section 903.3.1.2; change to read as follows: 903.3.1.2 NFPA 13R sprinkler systems. Automatic sprinkler systems in Group R occupancies shall be permitted to be installed throughout in accordance with NFPA 13R where the Group R occupancy meets all of the following conditions: 1. Four stories or less above grade plane. 2. The floor level of the highest story is 35 feet (9144 10668 mm) or less above the lowest level of fire department vehicle access. 3. The floor level of the lowest story is 35 feet (9144 10668 mm) or less below the lowest level of fire department vehicle access. {No change to remainder of section.} Section 903.3.1.2.2; change to read as follows: 903.3.1.2.2 Corridors and balconies in the means of egress. Sprinkler protection shall be provided in all corridors and for all balconies. {Delete the rest of this section.} Section 903.3.1.2.3; delete section and replace as follows: Section 903.3.1.2.3 Attached Garages and Attics. Sprinkler protection is required in attached garages, and in the following attic spaces: 1. Attics that are used or intended for living purposes or storage shall be protected by an automatic sprinkler system. 2. Where fuel -fired equipment is installed in a non-sprinklered attic, not fewer than one quick -response intermediate temperature sprinkler shall be installed above the equipment. 3. Attic spaces of buildings that are two or more stories in height above grade plane or above the lowest level of fire department vehicle access. 4. Group R-4, Condition 2 occupancy attics not required by Item 1 or 3 to have sprinklers shall comply with one of the following: 4.1. Provide automatic sprinkler system protection. 4.2. Provide a heat detection system throughout the attic that is arranged to activate the building fire alarm system. 4.3. Construct the attic using noncombustible materials. Ordinance No. 2023-081 19 4.4. Construct the attic using fire -retardant -treated wood complying with Section 2303.2 of the International Building Code. 4.5. Fill the attic with noncombustible insulation. Section 903.3.1.3; change to read as follows: 903.3.1.3 NFPA 13D Sprinkler Systems. Automatic sprinkler systems installed in one- and two-family dwellings; Group R-3; Group R-4, Condition 1; and townhouses shall be permitted to be installed throughout in accordance with NFPA 13D or in accordance with state law. Section 903.3.1.4; add to read as follows: [F] 903.3.1.4 Freeze protection. Freeze protection systems for automatic fire sprinkler systems shall be in accordance with the requirements of the applicable referenced NFPA standard and this section. 903.3.1.4.1 Attics. Only dry pipe, pre -action, or listed antifreeze automatic fire sprinkler systems shall be allowed to protect attic spaces. Exception: Wet -pipe fire sprinkler systems shall be allowed to protect non - ventilated attic spaces where: 1. The attic sprinklers are supplied by a separate floor control valve assembly to allow ease of draining the attic system without impairing sprinklers throughout the rest of the building, and 2. Adequate heat shall be provided for freeze protection as per the applicable referenced NFPA standard, and 3. The attic space is a part of the building's thermal, or heat, envelope, such that insulation is provided at the roof deck, rather than at the ceiling level. 903.3.1.4.2 Heat trace/insulation. Heat trace/insulation shall only be allowed where approved by the fire code official for small sections of large diameter water -filled pipe. Section 903.3.5; add a second paragraph to read as follows: Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every water - based fire protection system shall be designed with a 10-psi safety factor. Reference Section 507.4 for additional design requirements. Ordinance No. 2023-081 20 Section 903.4; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water -flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. Section 903.4.2; add second paragraph to read as follows: The alarm device required on the exterior of the building shall be a weatherproof horn/strobe notification appliance with a minimum 75-candela strobe rating, installed as close as practicable to the fire department connection. Section 905.2; change to read as follows: 905.2 Installation Standard. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high/low alarm. Section 905.3; add Section 905.3.9 and exception to read as follows: 905.3.9 Buildings Exceeding 10,000 sq. ft. In buildings exceeding 10,000 square feet in area per story and where any portion of the building's interior area is more than 200 feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire department vehicle access, Class I automatic wet or manual wet standpipes shall be provided. Exceptions: 1. Automatic dry, semi -automatic dry, and manual dry standpipes are allowed as provided for in NFPA 14 where approved by the fire code official. 2. R-2 occupancies of four stories or less in height having no interior corridors. Section 905.4; change Items 1, 3, and 5, and add Item 7 to read as follows: 1. In every required exit stairway, a hose connection shall be provided for each story above and below grade plane. Hose connections shall be located at an intermediate landing between stories, unless otherwise approved by the fire code official. Exception: {No change.} 2. {No change.} Ordinance No. 2023-081 21 3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. Exception: Where floor areas adjacent to an exit passageway are reachable from an interior exit stairway hose connection by a {remainder of text unchanged) 4. {No change.} 5. Where the roof has a slope less than 4 units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with a two-way hose connection located to serve the roof or at the highest landing of an exit stairway with stair access to the roof provided in accordance with Section 1011.12. 6. {No change.) 7. When required by this Chapter, standpipe connections shall be placed adjacent to all required exits to the structure and at two hundred feet (200') intervals along major corridors thereafter, or as otherwise approved by the fire code official. Section 905.8; change to read as follows: 905.8 Dry standpipes. Dry standpipes shall not be installed. Exception: Where subject to freezing and in accordance with NFPA 14. Additionally, manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high/low Supervisory alarm. Section 905.9; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water -flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. Section 906.1(1); delete Exception #3: Section 907.1; add Section 907.1.4 to read as follows: 907.1.4 Design Standards. Where a new fire alarm system is installed, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke detectors shall have analog initiating devices. Section 907.2.1; change to read as follows: 907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group A Ordinance No. 2023-081 22 occupancies having an occupant load of 300 or more persons, or where the occupant load is more than 100 persons above or below the lowest level of exit discharge. Group A occupancies not separated from one another in accordance with Section 707.3.10 of the International Building Code shall be considered as a single occupancy for the purposes of applying this section. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy. Exception: {No change.} Activation of fire alarm notification appliances shall: 1. Cause illumination of the means of egress with light of not less than 1 foot-candle (11 lux) at the walking surface level, and 2. Stop any conflicting or confusing sounds and visual distractions. Section 907.2.3; change to read as follows: 907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings, whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems. Exceptions: 1. {No change.) 1.1. Residential In -Home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. (For care of more than five children 2 1/2 or less years of age, see Section 907.2.6.) {No change to remainder of exceptions.} Section 907.2.10; change to read as follows: 907.2.10 Group S. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group S public- and self -storage occupancies for interior corridors and interior common areas. Visible notification appliances are not required within storage units. Exception: {No change.} Ordinance No. 2023-081 23 Section 907.2.13, Exception 3; change to read as follows: 3. Open air portions of buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code; however, this exception does not apply to accessory uses including but not limited to sky boxes, restaurants, and similarly enclosed areas. Section 907.2.23, add exception as follows: Exception: Buildings containing an R-3 occupancy shall comply with applicable provisions of the IRC and are exempt from this section. Section 907.4.2; add Section 907.4.2.7 to read as follows: 907.4.2.7 Type. Manual alarm initiating devices shall be an approved double action type. Section 907.6.1; add Section 907.6.1.1 to read as follows: 907.6.1.1 Wiring Installation. All fire alarm systems shall be installed in such a manner that a failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All signaling line circuits (SLC) shall be installed in such a way that a single open will not interfere with the operation of any addressable devices (Class A). Outgoing and return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits and shall have a minimum of four feet separation horizontal and one foot vertical between supply and return circuit conductors. The initiating device circuit (IDC) from a signaling line circuit interface device may be wired Class B, provided the distance from the interface device to the initiating device is ten feet or less. Section 907.6.3; delete all four Exceptions. Section 907.6.6; add sentence at end of paragraph to read as follows: 907.6.6 Monitoring. {bulk of text unchanged).... in accordance with NFPA 72. See 907.6.3 for the required information transmitted to the supervising station. Section 910.2; change Exception 2 and 3 to read as follows: 910.2 Where required. Smoke and heat vents or a mechanical smoke removal system shall be installed as required by Sections 910.2.1, 910.2.2, and 910.2.3. 2. Only manual smoke and heat removal shall not be required in areas of buildings equipped with early suppression fast -response (ESFR) sprinklers. Automatic smoke and heat removal is prohibited. Ordinance No. 2023-081 24 3. Only manual smoke and heat removal shall not be required in areas of buildings equipped with control mode special application sprinklers with a response time index of 50(m*S)1/2 or less that are listed to control a fire in stored commodities with 12 or fewer sprinklers. Automatic smoke and heat removal is prohibited. Section 910.2.3; add subsection to read as follows: 910.2.3 Group H. Smoke and heat vents installed in accordance with Section 910.3 or a mechanical smoke removal system installed in accordance with Section 910.4 shall be installed in buildings and portions thereof used as a Group H occupancy as follows: In occupancies classified as Group H-2 or H-3, any of which are more than 15,000 square feet (1394 m2) in single floor area. Exception: Buildings of noncombustible construction containing only noncombustible materials. 2. In areas of buildings in Group H used for storing Class 2, 3, and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or Class 2 or 3 water -reactive materials as required for a high -hazard commodity classification. Exception: Buildings of noncombustible construction containing only noncombustible materials. Section 910.4.3.1; change to read as follows: 910.4.3.1 Makeup Air. Makeup air openings shall be provided within 6 feet (1829 mm) of the floor level. Operation of makeup air openings shall be manual or automatic. The minimum gross area of makeup air inlets shall be 8 square feet per 1,000 cubic feet per minute (0.74 m2 per 0.4719 m3/s) of smoke exhaust. Section 913.2.1; add Section 913.2.1.1 and exception to read as follows: 913.2.1.1 Fire Pump Room Access. When located on the ground level at an exterior wall, the fire pump room shall be provided with an exterior fire department access door that is not less than 3 ft. in width and 6 ft. — 8 in. in height, regardless of any interior doors that are provided. A key box shall be provided at this door, as required by IFC Section 506.1. Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior wall, the corridor leading to the fire pump room access from the exterior of the building shall be provided with equivalent fire resistance as that Ordinance No. 2023-081 25 required for the pump room, or as approved by the fire code official. Access keys shall be provided in the key box as required by IFC Section 506.1. Section 1809.5.1 Frost Protection at required exits: Section deleted Section 2702.5; added to read as follows: Section 2702.5 Designated Critical Operations Areas (DCOA): In areas within a facility or site requiring continuous operation for the purpose of public safety, emergency management, national security or business continuity, the power systems shall comply with NFPA 70 Article 708. Section 2901.1; add a sentence to read as follows: [P] 2901.1 Scope. {existing text to remain} The provisions of this Chapter are meant to work in coordination with the provisions of Chapter 4 of the International Plumbing Code. Should any conflicts arise between the two chapters, the Building Official shall determine which provision applies. Section 2902.1; add a second paragraph to read as follows: 2902.1 Minimum number of fixtures. {bulk of text unchanged}.... shall be determined by this code. In other than E Occupancies, the minimum number of fixtures in Table 2902.1 may be lowered, if requested in writing, by the applicant stating reasons for a reduced number and approved by the Building Official. Table 2902.1; add footnote g to read as follows: g. Drinking fountains are not required in Group M occupancies with an occupant load of 50 or less, Group B occupancies with an occupant load of 25 or less, and for dining and/or drinking establishments. Add Section 2902.1.4 to read as follows: 2902.1.4 Additional fixtures for food preparation facilities. In addition to the fixtures required in this Chapter, all food service facilities shall be provided with additional fixtures set out in this section. 2902.1.4.1 Hand washing lavatory. At least one hand washing lavatory shall be provided for use by employees that is accessible from food preparation, food dispensing and ware washing areas. Additional hand washing lavatories may be required based on convenience of use by employees. 2902.1.4.2 Service sink. In new or remodeled food service establishments, at least one service sink or one floor sink shall be provided so that it is conveniently located for the cleaning of mops or similar wet floor cleaning tool and for the disposal of Ordinance No. 2023-081 26 mop water and similar liquid waste. The location of the service sink(s) and/or mop sink(s) shall be approved by the Tarrant County Health Department. Section 3002.1 Hoistway Enclosure Protection required. Add exceptions as follows: Exceptions: 1. Elevators completely located within atriums shall not require hoistway enclosure protection. 2. Elevators in open or enclosed parking garages that serve only the parking garage, shall not require hoistway enclosure protection. Section 3005.4 Machine rooms, control rooms, machinery spaces and control spaces; Delete exceptions and add two new exceptions to as follows: Exceptions: 1. Elevator machine rooms, control rooms, machinery spaces, and control spaces completely located within atriums shall not require enclosure protection. 2. Elevator machine rooms, control rooms, machinery spaces, and control spaces in open or enclosed parking garages that serve only the parking garage, shall not require enclosure protection. Section 3005.5: Add a new subsection to Section 3005.5.1 as follows: 3005.5.1 Fire Protection in Machine rooms, control rooms, machinery spaces, and control spaces. 3005.5.1.1 Automatic sprinkler system. The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, except as otherwise permitted by Section 903.3.1.1.1 and as prohibited by Section 3005.5.1.1.1. 3005.5.1.1.1 Prohibited locations. Automatic sprinklers shall not be installed in machine rooms, elevator machinery spaces, control rooms, control spaces and elevator hoistways. 3005.5.1.1.2 Sprinkler system monitoring. The sprinkler system shall have a sprinkler control valve supervisory switch and water -flow initiating device provided for each floor that is monitored by the building's fire alarm system. 3005.5.1.2 Water protection. An approved method to prevent water from infiltrating into the hoistway enclosure from the operation of the automatic sprinkler system outside the elevator lobby shall be provided. Ordinance No. 2023-081 27 3005.5.1.3 Omission of Shunt trip. Means for elevator shutdown in accordance with Section 3005.5 shall not be installed. Section 3005.7; add Section 3005.7 as follows: 3005.7 Storage. Storage shall not be allowed within the elevator machine room, control room, machinery spaces and or control spaces. Provide approved signage at each entry to the above listed locations stating: "ELEVATOR MACHINERY - NO STORAGE ALLOWED". Section 3006.2, Hoistway opening protection required; Revise text as follows: 5. The building is a high rise and the elevator hoistway is more than 55 feet (16 764 mm) in height. The height of the hoistway shall be measured from the lowest floor at or above grade to the highest floors served by the hoistway." Section 3007.3 and Section 3008.3: Revise text by deleting "enclosed" as follows: 3007.3 Water Protection. Water from the operation of an automatic sprinkler system outside the lobby shall be prevented from infiltrating into the hoistway enclosure in accordance with an approved method. 3008.3 Water Protection. Water from the operation of an automatic sprinkler system outside the lobby shall be prevented from infiltrating into the hoistway enclosure in accordance with an approved method. ARTICLE III. - ELECTRICAL CODE DIVISION 4. -INSTALLATION, EQUIPMENT AND MATERIALS STANDARDS Sec 7-91. National Electric Code adopted; penalty. (a) There is hereby adopted by the city, for the purpose of prescribing regulations, governing conditions hazardous to life and property, that a certain 2020 Edition of the National Electric Code, {remainder of section unchanged} Ordinance No. 2023-081 28 Sec. 7-97. Amendments to the National Electric Code. [The following are amendments to the 2020 Edition of the National Electric Code] Article 100; add the following to definitions: Engineering Supervision. Supervision by a Qualified State of Texas Licensed Professional Engineer engaged primarily in the design or maintenance of electrical installations. Article 110.2; change the following to read as follows: 110.2 Approval. The conductors and equipment required or permitted by this Code shall be acceptable only if approved. Approval of equipment may be evident by listing and labeling of equipment by a Nationally Recognized Testing Lab (NRTL) with a certification mark of that laboratory or a qualified third party inspection agency or a field evaluation by a Field Evaluation Body accredited by either the International Code Council, International Accreditation Service AC354, or ANSI National Accreditation Board programs and approved by the AHJ. Exception: Unlisted equipment that is relocated to another location within a jurisdiction or is field modified is subject to the approval by the AHJ. This approval may be by a field evaluation by a NRTL, a qualified third -party inspection agency, or a field evaluation by a Field Evaluation Body accredited by either the ICC IAS AC354 or ANAB programs and approved by the AHJ. Informational Note No. 1: See 90.7, Examination of Equipment for Safety, and 110.3, Examination, Identification, Installation, and Use of Equipment. See definitions of Approved, Identified, Labeled, and Listed. Informational Note No. 2: Manufacturer's self -certification of equipment may not necessarily comply with U.S. product safety standards as certified by an NRTL. Informational Note No. 3: National Fire Protection Association (NFPA) 790 and 791 provide an example of an approved method for qualifying a third -party inspection agency. Article 410.118; Change the following to read as follows: 410.118 Access to other boxes. Luminaires recessed in the ceilings, floors, or walls shall not be used to access outlet, pull, or junction boxes or conduit bodies, unless the box or conduit body is an integral part of the listed luminaire. Exception: removable luminaires with a minimum measurement of 22 in. X 22 in. shall be permitted to be used as access to outlet, pull, junction boxes or conduit bodies. Ordinance No. 2023-081 29 Article 500.8 (A) (3); change to read as follows: 500.8 Equipment. Articles 500 through 504 require equipment construction and installation that ensure safe performance under conditions of proper use and maintenance. Informational Note No. 1: It is important that inspection authorities and users exercise more than ordinary care with regard to installation and maintenance. Informational Note No. 2: Since there is no consistent relationship between explosion properties and ignition temperature, the two are independent requirements. Informational Note No. 3: Low ambient conditions require special consideration. Explosion proof or dust -ignition proof equipment may not be suitable for use at temperatures lower than -25°C (-13°F) unless they are identified for low - temperature service. However, at low ambient temperatures, flammable concentrations of vapors may not exist in a location classified as Class 1, Division 1 at normal ambient temperature. (A) Suitability. Suitability of identified equipment shall be determined by one of the following: (1) Equipment listing or labeling; (2) Evidence of equipment evaluation from a qualified testing laboratory or inspection agency concerned with product evaluation; or, (3) Evidence acceptable to the authority having jurisdiction such as a manufacturer's self -evaluation or an engineering judgment signed and sealed by a qualified licensed Professional Engineer in the State of Texas. Informational Note: Additional documentation for equipment may include certificates demonstrating compliance with applicable equipment standards, indicating special conditions of use, and other pertinent information. Article 505.7 (A); changed to read as follows: 505.7 Special Precaution. Article 505 requires equipment construction and installation that ensures safe performance under conditions of proper use and maintenance. Informational Note No. 1: It is important that inspection authorities and users exercise more than ordinary care with regard to the installation and maintenance of electrical equipment in hazardous (classified) locations. Ordinance No. 2023-081 30 Informational Note No. 2: Low ambient conditions require special consideration. Electrical equipment depending on the protection techniques described by 505.8(A) may not be suitable for use at temperatures lower than -200C (-4°F) unless they are identified for use at lower temperatures. However, at low ambient temperatures, flammable concentrations of vapors may not exist in a location classified Class I, Zones 0, 1, or 2 at normal ambient temperature. (A) Implementation of Zone Classification System. Classification of areas, engineering and design, selection of equipment and wiring methods, installation, and inspection shall be performed by a qualified Registered licensed Professional Engineer in the State of Texas. Article 625.40.1; Add to read as follows: 625.40.1 Knox Remote Power Box Required. All electric vehicle charging system locations shall have a Knox Remote Power Box (KRPB) to allow the Fire Department to remotely operate a shunt trip breaker to safely disconnect power to the charging station(s) compliant with all of the following: (1) The KRPB shall be located within 50 feet of, but not less than 30 feet from Charging station(s). (2) The location of the KRPB shall be at a point that allows the operator to be in -line -of -sight to the incident. (3) The KRPB shall be protected from physical damage including but not limited to motor vehicle impact. (4) The height of the KRPB shall be no less than 42" but not more than 48" measured vertically from grade. (5) A sign shall be placed adjacent to or on the structure supporting the KRPB stating "FIRE DEPARTMENT USE ONLY" with minimum 2" lettering. Exception: Group R-3 buildings and their accessory structures on the same lot. 695.6 (A) Supply Conductors. (1) Services and On -Site Power Production Facilities. Service conductors and conductors supplied by on -site power production facilities shall be physically routed outside a buildinq(s) and shall be installed as service - entrance conductors in accordance with 230.6, 230.9, and Parts III and IV of Article 230. Where supply conductors cannot be physically routed outside of buildinqs, the conductors shall be permitted to be routed throuq_ h the building_ (s) where installed in accordance with 230.60) or (2). Ordinance No. 2023-081 31 Article 710.15 A; Change the following to read as follows: 710.15 General 710.15(A) Supply Output. Power supply to premises wiring systems fed by stand-alone or isolated microgrid power sources shall have adequate capacity to meet the calculated load in accordance with Article 220. ARTICLE V. - RESIDENTIAL CODE Sec. 7-140 — Adoption. There is hereby adopted for the purpose of establishing rules and regulations for the construction, alteration, removal, demolition, equipment, use and occupancy, location and maintenance of buildings and structures, that a certain code known as the International Residential Code, particularly the 2021 Edition thereof, {remainder of section unchanged} Sec. 7-142. - Amendments Section R101.1; [NAME OF JURISDICTION] changed to "City of Grapevine, TX" Section R102.4; change to read as follows: R102.4 Referenced codes and standards. The codes, when specifically adopted, and standards referenced in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections R102.4.1 and R102.4.2. When amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference made to NFPA 70 or the Electrical Code shall mean the Electrical Code as adopted. Where the enforcement of a provision of this code would violate the conditions of the listing of appliances or equipment, the conditions of the listing and the manufacturer's installation instructions shall apply. Section R103 and R103.1 amend to insert the Department Name: Ordinance No. 2023-081 32 R103.1 Creation of enforcement agency. The Building Services Department is hereby created and the official in charge thereof shall be known as the Building Official. Section R104.10.1 Flood Hazard areas; delete this section. Section R105.2 Work exempt from permit; under sub -title entitled "Building" add text to items 1,5, and 8 and delete item 2 as follows: Building: 1. One-story detached accessory structures used as tool and storage sheds, playhouses and similar uses, provided the floor area does not exceed 120 square feet (11 m2) require permits but are exempt from fees. Such structures must comply with all provisions of the Zoning Ordinance. 2. {Deleted) 3.4. {Remain Unchanged) 5. Sidewalks and driveways; however, all applicable provisions of the Zoning Ordinance must be met relative to required materials, maximum coverage, and required landscape areas. 7. {Remain Unchanged) 8. Swings and other playground equipment accessory to detached one - and two-family dwellings; however, such structures must comply with all applicable provisions of the Zoning Ordinance. 9.-10. {Remain Unchanged) [Remainder of section unchanged] Section R105.3.1.1 & R106.1.4; delete these sections. Section R108 Fees, is hereby deleted and replaced with the following: Section R108 Schedule of Permit Fees. On buildings, structures, electrical, gas, mechanical and plumbing systems or alterations requiring a permit, a fee for each permit shall be paid as required, in accordance with Table 1A, Building Permit Fees attached hereto as Exhibit "A" and Table 108A Mechanical, Electrical and Plumbing Permit Fees attached hereto as Exhibit "C" and incorporated herein by reference. Ordinance No. 2023-081 33 TABLE NO. 1-A BUILDING PERMIT FEES PERMIT FFFS OR ALL BUILDING PERMITS EXCEPT FOR RESIDENTIAL DWELLNGS TOTAL VALUATION FEE $1.00 to $500.00 $50.00 $501.00 to $2,000.00 $50.00 for the first $500.00 plus $4.00 for each additional $100.00, or fraction thereof, to and including $2,000.00 $2,001.00 to $75.00 for the first $2,000.00 plus $16.00 for each additional $1,000.00, $25.000.00 or fraction thereof, to and including $25,000.00 $25,001.00 to $500.00 for the first $25,000.00 plus $13.50 for each additional $50,000.00 $1,000.00, or fraction thereof, to and including $50,000.00 $50,001.00 to $750.00 for the first $50,000.00 plus $8.25 for each additional $100,000.00 $1,000.00, or fraction thereof, to and including $100,000.00 $100,001.00 to $1,250.00 for the first $100,000.00 plus $6.25 for each additional $500,000.00 $1,000.00, or fraction thereof, to and including $500,000.00 $500,001.00 to $4,000.00 for the first $500,000.00 plus $5.50 for each additional $1,000,000.00 $1,000.00, or fraction thereof, to and including $1,000,000.00 $1,000,001.00 and $7,500.00 for the first $1,000,000.00 plus $5.00 for each additional u $1,000.00, or fraction thereof BUILDING PERMIT FEES FOR RESIDENTIAL DWELLINGS NEW ADDITIONS ALTERATIONS CONSTRUCTION R3 RESIDENTIAL DWELLINGS $ .55 / Square $ 1.00 / Square Foot $ 1.00 / Square Foot Foot TOTAL AREA of of ALTERATION AREA (Detached one and TOTAL AREA ADDITION two family UNDER ROOF dwellings, townhomes not more than 3-stores in height with a separate means of egress) R2 RESIDENTIAL $ .30 / Square $ 1.00 / Square Foot $ 1.00 / Square Foot DWELLINGS Foot TOTAL AREA of of ALTERATION AREA TOTAL AREA ADDITION UNDER ROOF Ordinance No. 2023-081 34 (Apartments, condominiums, three and four family dwellings, etc) SIMPLE ALTERATION PERMITS Projects in which FLAT FEE $150.00 square footage does not apply as determined by the Building Official. (Window replacement, foundation repair, siding replacement, etc) UNENCLOSED OTHER INSPECTIONS AND FEES: 1. Certificate of Occupancy................................................................................................... $ 50.00 2. Inspections outside of normal business hours .................. $50.00 per hour* (minimum charge- two hours) 3. Reinspection fees assessed under provisions of Section 108.5 ................................................. $50.00 4. Inspections for which no fee is specifically indicated .... $50.00 per hour* (minimum charge- one-half hour) 5. Additional plan review required by changes, additions or revisions to plans .................... $50.00 per hour* 6. For use of outside consultants for plan checking and inspections, or both ..........................actual costs' 7. Foundation only permits or any partial permit ................ 10% of building permit fee in addition to building permit fee 8. Plan review fee (not applicable to Group R-3 private residences) ................ 65% of building permit fee in addition to building permit fee 9. Building permit fees for the Grapevine- Colleyville Independent School District ............... 25% of the fees established in Table No. 1 -A- Building Permit Fees 10. Project valuation to be determined by the regional construction valuation table, adopted by the city, or the contract valuation whichever is greater. Permit valuations shall include all work required for a completed project, including profit, but need not include the value or cost of the land. Other methods for determining Ordinance No. 2023-081 35 the project valuations for unique or unusual projects may be approved by the Building Official. 11. Public Works Antenna or Equipment Installation Charge on City Owned Water Towers Only ......... $350.00 *Or the total hourly cost of the jurisdiction, whichever is the greatest. This cost shall include supervision, overhead, equipment, hourly wages and fringe benefits of the employees involved. ** Actual costs include administrative and overhead costs. LOT DRAINAGE FEES Single Family & Duplex Swimming Pools All remaining classifications Full Acre Cost Portion Other than Full Acre $150.00 $150.00 $350.00 Per Acre $350.00 x Percentage of Full Ordinance No. 2023-081 36 EXHIBIT "C" CITY OF GRAPEVINE MECHANICAL, ELECTRICAL, PLUMBING AND FUEL GAS PERMIT FEES TYPE OF OCCUPANCY BUILDING AREA PERMIT FEES AMOUNT DUE (SO FT) EACH TRADE 1. R-3 1- 749 $ 33.25 SINGLE FAMILY, DUPLEX 750- 1,199 $ 49.88 TOWNHOUSE, NEW CONSTRUCTION & 1,200- 1,500 1,501 - 1,750 $ 63.18 $ 76.48 ADDITIONS (PER UNIT) 1,751 - 2,000 2,001 - 2,250 $ 83.13 $ 89.78 TOTAL SQ.FOOT UNDER ROOF 2,251 - 3,000 3,001 - 3,500 3,501 - 4,000 $ 96.43 $ 103.08 $ 109.73 $ 4, 001 + $ 120.37 EACH TRADE 11. A, E, I, R-1 1 - 500 $ 37.00 HOTELS, APARTMENTS, 501-100,000 $ 17.50+.035 PER 1 DRINKING/DINING, 100,001-500,000 $ 3,500.00+.03 SQUARE EDUCATIONAL, ASSEMBLY, 500,001 + $15,000.00+.02 FOOT $ INSTITUTIONAL EACH TRADE Ill. B, F, H, M, S, U 1- 500 $ 37.00 OFFICE, RETAIL, WHOLESALE, 501 - 50,000 $ 32.00+.01 PER GARAGES, FACTORIES, 50,001- 100,000 $ 182.00+.007 SQUARE WORKSHOPS, SERVICE 100,001+ $ 582.00+.003 FOOT $ STATIONS WAREHOUSE CONTRACT EACH TRADE IV. ANY OCCUPANCY GROUP, VALUATION OF WORK ALTERATIONS, FINISH -OUTS, SHELL COMPLETIONS 0- 500 $ 37.00 501- 1,500 $ 45.00 CONTRACT VALUATION OF WORK: 1,501- 3,000 $ 57.00 3,001- 5,000 $ 72.00 5,001- 50,000 $ 27.O+.009 50,001. 100,000 $ 127.00+.007 PER $ 100,001- 500,000 500,000+ $ 327.00+ .005 DOLLAR $1,327.00+.003 TVALUATION $ V. MISCELLANEOUS EACH TRADE IRRIGATION SYSTEMS $ 37.00 MOBILE HOME SERVICE $ 37.00 TEMPORARY POLE SERVICE $ 37.00 SWIMMING POOLS $ 37.00 SIGN ELECTRIC $ 37.00 $ OTHER INSPECTIONS AND FEES • INSPECTIONS OUTSIDE NORMAL BUSINESS HOURS (2HR MINIMUM) ............................ ................... $42.00/HOUR' • REINSPECTION FEES.................................................................................................................. $42.00 • PERMITS FOR WHICH NO FEE IS SPECIFICALLY INDICATED........................................................... $37.00 • INSPECTIONS FOR WHICH NO FEE IS SPECIFICALLY INDICATED (1/2 HOUR MINIMUM)......................$42.00/HOUR • ADDITIONAL PLAN REVIEW REQUIRED BY CHANGES, ADDITIONS, OR REVISIONS TO APPROVEDPLANS ................. ......................... ............................................................... .............. $42.00/HOUR • BUILDING PERMIT FEES FOR THE GRAPEVINE-COLLEYVILLE INDEPENDENT SCHOOL DISTRICT SHALL BE 25% OF THE FEES ESTABLISHED IN THIS TABLE • FOR USE OF OUTSIDE CONSULTANTS FOR PLAN CHECKING AND INSPECTIONS, OR BOTH......... ACTUAL COSTS" 'OR THE TOTAL HOURLY COST TO THE JURISDICTION WHICHEVER IS GREATER. -ACTUAL COSTS INCLUDE ADMINISTRATIVE AND OVERHEAD COSTS. Ordinance No. 2023-081 37 Except for residential dwellings, all other building permits shall be determined by the building valuation data table attached hereto as Exhibit "B", Building Valuation Data or the contract valuation wherever is greater. Section R110 (R110.1 through R110.5); delete the section. Section R202; change definition of "Townhouse Unit" to read as follows: TOWNHOUSE UNIT. A single-family dwelling unit separated by property lines in a townhouse that extends from foundation to roof and that has a yard or public way on not less than two sides. Section R202; add definition of "Conditioned space" and "Appliance, Unvented" to read as follows: CONDITIONED SPACE. Conditioned Space. An area, room, or space that is enclosed within the building thermal envelope and is directly or indirectly heated or cooled. Spaces are indirectly heated or cooled where they communicate through openings with conditioned spaces, where they are separated from condition spaces by uninsulated walls, floor or ceilings, or where they contain insulated ducts, piping or other sources of heating or cooling. Additionally, the attic space shall be provided with active or passive heating systems capable of maintaining an indoor temperature of not less than 55 degrees F at a point 3 feet above the floor. APPLIANCE, UNVENTED. An appliance designed or installed in such a manner that the products of combustion are not conveyed by a vent or chimney directly to the outside atmosphere. Such appliances are hereby prohibited by this code. Table R301.2; replace table as follows as follows: Delete remainder of table Manual J Design Criteria and footnotes "n" and {Loll W c7 a SEISMI z A� GROUND DESIGN SUBJECT TO W W a SNOW WIND DESIGN CATEG DAMAGE FROM LOAD ORY' U W A SPE Topogr aphic Spec ial Windb orne A 5Ib/ft EDd Effects` Win Debris 0? (MP d Zone' H) Regi w E. one 22' N Loc 1 64. F o al 5 91 115 Co 0 Fde (3 No No No Mode 6" Ver sec- rate y gust) Hea / 76 vY faste st mile Section R302.1; Delete exceptions 3 and 4 Exceptions 1, 2, and 5 remain unchanged Section R302.3; add text as follows: Two-family dwelling units that are also divided by a property line through the structure shall be separated as required for townhouses. Section R302.2.6; delete exception #6: Exceptions 1-5 remain unchanged. Section R302.5.1; change to read as follows: R302.5.1 Opening protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors not less than 13/8 Ordinance No. 2023-081 39 inches (35 mm) in thickness, solid or honeycomb core steel doors not less than 13/8 inches (35 mm) thick, or 20-minute fire -rated doors. Section R302.7; change to read as follows: R302.7 Under -stair protection. Enclosed space under stairs that is accessed by a door or access panel shall have walls, under -stair surface and any soffits protected on the enclosed side with 5/8" Type X gypsum board. Section R313 Automatic Fire Sprinkler Systems is deleted and replaced with the following: R313 Automatic Fire Sprinkler Systems R313.1 Automatic Fire Sprinkler Systems. Automatic fire sprinkler systems shall be regulated by the Fire Code as adopted by the city. Section R322 Flood Resistant Construction; deleted section. Section 327.1 is amended as follows: Section 327.1 General. The design and construction of pools and spas shall comply with the International Swimming Pool and Spa Code as adopted and amended by the State of Texas. Section 329 is amended as follows: 329.1 General. Stationary generators shall be listed and labeled in accordance with UL 2200 and shall comply with this section and the Electric Code and ordinance adopted by the city. The connection to the premise wiring system shall be by an approved method using listed materials. Generators installed for continuous use in non -emergency conditions are prohibited. Section R401.2; amended by adding a new sentence following the existing paragraph to read as follows: Section R401.2. Requirements. {existing text unchanged) .... with accepted engineering practice. For all dwelling units, any foundation or any size addition to an existing foundation regulated by this code shall be designed, signed and sealed by a Professional Engineer registered in the State of Texas. Exception: Buildings accessory to an R-3 occupancy not used as dwellings. Ordinance No. 2023-081 40 Section R602.6.1; amend the following: R602.6.1 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load -bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 Ga) and 5 inches (127 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) having a minimum length of 1 '/2 inches (38 mm) at each side or equivalent. Fasteners will be offset to prevent splitting of the top plate material. The metal tie must extend a minimum of 6 inches past the opening. See figure R602.6.1. {remainder unchanged} (Amendment to 2015 IRC carried forward to 2018 IRC.) Figure R602.6.1; delete the figure and insert the following figure: 1 AND S RL WIDE WED ACROSS AHD r EACH SIDE OF THE NNAALS EACH SI" TOP (Amendment to 2018 IRC carried forward to 2021 IRC also provides additional assurance of maintaining the integrity of the framing by spreading the nailing pattern.) Add section R703.8.4.1.2 Veneer Ties for Wall Studs; to read as follows: R703.8.4.1.2 Veneer Ties for Wall Studs. In stud framed exterior walls, all ties may be anchored to studs as follows: When studs are 16 in (407 mm) o.c., stud ties shall be spaced no further apart than 24 in (737 mm) vertically starting approximately 12 in (381 mm) from the foundation; or 2. When studs are 24 in (610 mm) o.c., stud ties shall be spaced no further apart than 16 in (483 mm) vertically starting approximately 8 in (254 mm) from the foundation. Ordinance No. 2023-081 41 Section R902.1; amend and add exception No. 5 to read as follows: R902.1 Roofing covering materials. Roofs shall be covered with materials as set forth in Sections R904 and R905. Class A, B, or C roofing shall be installed. {remainder unchanged} Exceptions: 1. {text unchanged} 2. {text unchanged} 3. {text unchanged} 4. {text unchanged} 5. Non -classified roof coverings shall be permitted on one-story detached accessory structures used as tool and storage sheds, playhouses, and similar uses, provided the floor area does not exceed 120 square feet. Chapter 11 [RE] — Energy Efficiency is deleted in its entirety; Reference the IECC for energy code provisions as adopted by the State of Texas. Section M1305.1.2; change to read as follows: M1305.1.2 Appliances in attics. Attics containing appliances shall be provided . . {bulk of paragraph unchanged}. . side of the appliance. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. As a minimum, for access to the attic space, provide one of the following: 1. A permanent stair. 2. A pull -down stair with a minimum 300 lb. (136 kg) capacity. 3. An access door from an upper floor level. Exceptions: [remaining text unchanged] Section M2005.2; change to read as follows: M2005.2 Prohibited locations. Fuel -fired water heaters shall not be installed in a room used as a storage closet. Water heaters located in a bedroom or bathroom shall be installed in a sealed enclosure so that combustion air will not be taken from the living space. Access to such enclosure may be from the bedroom or bathroom when through a solid door, weather-stripped in accordance with the exterior door air leakage requirements of the International Energy Conservation Code and equipped with an approved self -closing device. Installation of direct - vent water heaters within an enclosure is not required. Water heaters shall not be installed in unconditioned attic spaces unless listed for installation outdoors. Ordinance No. 2023-081 42 Section G2415.2 CSST; add a second paragraph to read as follows: Both ends of each section of medium pressure gas piping shall identify its operating gas pressure with an approved tag. The tags are to be composed of aluminum or stainless steel and the following wording shall be stamped into the tag: "WARNING: 1/2 to 5 psi gas pressure - Do Not Remove" Section G2415.12 and G2415.12.1; change to read as follows: G2415.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 18 inches (457 mm) below grade. G2415.12.1 Individual Outdoor Appliances; Deleted in its entirety. Section G2417.1; change to read as follows: G2417.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication, and installation practices comply with the requirements of this code. The permit holder shall make the applicable tests prescribed in Sections 2417.1.1 through 2417.1.5 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the building official when the piping system is ready for testing. The equipment, material, power and labor necessary for the inspections and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests. Section G2417.4; change to read as follows: G2417.4 Test pressure measurement. Test pressure shall be measured with a monometer or with a pressure -measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Section G2417.4.1; change to read as follows: G2417.4.1 Test pressure. The test pressure to be used shall be no less than 3 psig (20 kPa gauge), or at the discretion of the code official, the piping and valves may be tested at a pressure of at least six (6) inches (152 mm) of mercury, measured with a manometer or slope gauge. For tests requiring a pressure of 3 psig, diaphragm gauges shall utilize a dial with a minimum diameter of three and Ordinance No. 2023-081 43 one half inches (3'/2"), a set hand, 1/10 pound incrementation and pressure range not to exceed 6 psi for tests requiring a pressure of 3 psig. For tests requiring a pressure of 10 psig, diaphragm gauges shall utilize a dial with a minimum diameter of three and one-half inches (3 '/2"), a set hand, a minimum of 2/10 pound incrementation and a pressure range not to exceed 20 psi. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa) (1/2 psi) and less than 200 inches of water column pressure (52.2 kPa) (7.5 psi), the test pressure shall not be less than ten (10) pounds per square inch (69.6 kPa). For piping carrying gas at a pressure that exceeds 200 inches of water column (52.2 kPa) (7.5 psi), the test pressure shall be not less than one and one-half times the proposed maximum working pressure. Diaphragm gauges used for testing must display a current calibration and be in good working condition. The appropriate test must be applied to the diaphragm gauge used for testing. Section G2417.4.2; change to read as follows: G2417.4.2 Test duration. The test duration shall be held for a length of time satisfactory to the Building Official, but in no case for less than fifteen (15) minutes. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa), the test duration shall be held for a length of time satisfactory to the Building Official, but in no case for less than thirty (30) minutes. Section G2420.1; add Section G2420.1.4 to read as follows: G2420.1.4 Valves in CSST installations. Shutoff valves installed with corrugated stainless steel (CSST) piping systems shall be supported with an approved termination fitting, or equivalent support, suitable for the size of the valves, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration but in no case greater than 12-inches from the center of the valve. Supports shall be installed so as not to interfere with the free expansion and contraction of the system's piping, fittings, and valves between anchors. All valves and supports shall be designed and installed so they will not be disengaged by movement of the supporting piping. Section G2420.5.1; change to read as follows: G2420.5.1 Located within the same room. The shutoff valve ... {bulk of paragraph unchanged)... in accordance with the appliance manufacturer's instructions. A secondary shutoff valve must be installed within 3 feet (914 mm) of the firebox if appliance shutoff is located in the firebox. Ordinance No. 2023-081 44 Section G2421.1; add text and Exception to read as follows: G2421.1 Pressure regulators. A line pressure regulator shall be ... {bulk of paragraph unchanged)... approved for outdoor installation. Access to regulators shall comply with the requirements for access to appliances as specified in Section M 1305. Exception: A passageway or level service space is not required when the regulator is capable of being serviced and removed through the required attic opening. Section G2422.1.2.3 Prohibited locations and penetrations; delete Exception 1 and Exception 4: Section G2445 Unvented Room Heaters is deleted and replaced with the following: G2445 Unvented Room Heaters. G2445.1 General. Unvented room heaters, and any other unvented heating appliance or fireplace are strictly prohibited by this code where installed indoors regardless of manufacturers listing. Section G2448.1.1; change to read as follows: G2448.1.1 Installation requirements. The requirements for water heaters relative to access, sizing, relief valves, drain pans and scald protection shall be in accordance with this code. Water heaters shall not be installed in unconditioned attic spaces unless listed for installation outdoors. Section P2603; add to read as follows: P2603.3 Protection against corrosion. Metallic piping, except for cast iron, ductile iron and galvanized steel, shall not be placed in direct contact with steel framing members, concrete or cinder walls and floors or other masonry. Metallic piping shall not be placed in direct contact with corrosive soil. Where sheathing is used to prevent direct contact, the sheathing shall have a thickness of not less than 0.008 inch (8 mil) (0.203 mm) and the sheathing shall be made of approved material plastic. Where sheathing protects piping that penetrates concrete or masonry walls or floors, the sheathing shall be installed in a manner that allows movement of the piping within the sheathing. Section P2603.5.1 Sewer Depth; change to read as follows: P2603.5.1 Sewer depth. Building sewers that connect to private sewage disposal systems shall be a minimum of 12 inches (mm) below finished grade at the point Ordinance No. 2023-081 45 of septic tank connection. Building sewers shall be a minimum of 12 inches (304 mm) below grade. Section P2604; add to read as follows: P2604.2.1 Plastic sewer and DWV piping installation. Plastic sewer and DWV piping installed underground shall be installed in accordance with the manufacturer's installation instructions. Trench width shall be controlled to not exceed the outside the pipe diameter plus 16 inches or in a trench which has a controlled width equal to the nominal diameter of the piping multiplied by 1.25 plus 12 inches. The piping shall be bedded in 4 inches of granular fill and then backfilled compacting the side fill in 6-inch layers on each side of the piping. The compaction shall be to minimum of 85 percent standard proctor density and extend to a minimum of 6 inches above the top of the pipe. Section P2804.6.1; change to read as follows: P2804.6.1 Requirements for discharge piping. The discharge piping serving a pressure relief valve, temperature relief valve or combination thereof shall: {unchanged} 2. {unchanged} 3. Not be smaller than the diameter of the outlet of the valve served and shall discharge full size to the air gap. Flexible connectors are prohibited. 4. {unchanged} 5. Discharge to an approved location or to the outdoors. {remainder unchanged} Section P2902.5.3; change to read as follows: P2902.5.3 Lawn irrigation systems. The potable water supply to lawn irrigation systems shall be protected against backflow by an atmospheric -type vacuum breaker, a pressure -type vacuum breaker, a double-check assembly or a reduced pressure principle backflow preventer. A valve shall not be installed downstream from an atmospheric vacuum breaker. Where chemicals are introduced into the system, the potable water supply shall be protected against backflow by a reduced pressure principle backflow preventer. Section P2904; delete in entirety and replace with the following: Ordinance No. 2023-081 46 Section P2904 Dwelling Unit Fire Sprinkler Systems P2904.1 General. The design and installation of residential automatic fire sprinklers shall conform to the fire code adopted by the city and be approved by the fire code official. Section P2906.22; add Section as follows: P2096.22 Prohibited joints and connections. The following types of joints and connections shall be prohibited: Cement or concrete joints. 2. Joints made with fittings not approved for the specific installation. 3. Solvent -cement joints between different types of plastic pipe. 4. {unchanged} 5. Joints in copper or copper -alloy pipe or tubing where underground beneath buildings shall only be made using wrought copper or copper -alloy fittings with brazed joints. Section P3003.9; change to read as follows: P3003.9.2 Solvent cementing. Joint surfaces shall be clean and free from moisture. A purple primer that conforms to ASTM F 656 shall be applied. Solvent cement not purple in color and conforming to ASTM D 2564, CSA B137.3, CSA 13181.2 or CSA 13182.1 shall be applied to all joint surfaces. The joint shall be made while the cement is wet and shall be in accordance with ASTM D 2855. Solvent cement joints shall be permitted above or below ground. Section P3111 Combination waste and vent systems; delete this section in its entirety. Section P3112.2 Vent Connection; delete and replace with the following: P3112.2 Installation. Traps for island sinks and similar equipment shall be roughed in above the floor and may be vented by extending the vent as high as possible, but not less than the drainboard height and then returning it downward and connecting it to the horizontal sink drain immediately downstream from the vertical fixture drain. The return vent shall be connected to the horizontal drain through a wye-branch fitting and shall, in addition, be provided with a foot vent taken off the vertical fixture vent by means of a wye-branch immediately below the floor and extending to the nearest partition and then through the roof to the open air or may be connected to other vents at a point not less than six (6) inches (152 mm) above the flood level rim of the fixtures served. Drainage fittings shall be used on all parts Ordinance No. 2023-081 47 of the vent below the floor level and a minimum slope of one -quarter (1/4) inch per foot (20.9 mm/m) back to the drain shall be maintained. The return bend used under the drain -board shall be a one (1) piece fitting or an assembly of a forty-five (45) degree (0.79 radius), a ninety (90) degree (1.6 radius) and a forty-five (45) degree (0.79 radius) elbow in the order named. Pipe sizing shall be as elsewhere required in this Code. The island sink drain, upstream of the return vent, shall serve no other fixtures. An accessible cleanout shall be installed in the vertical portion of the foot vent. Chapters 34-43 are deleted in their entirety and replaced with the following: Chapter 34 Electrical Requirements Section 3401 General Section 3401.1 Electrical installations shall comply with all applicable provisions of the Electric Code and ordinance adopted by the city. EXHIBITS A-L {these exhibits are hereby deleted in their entirety} ARTICLE VI. - MECHANICAL CODE Sec. 7-150. Code Adopted. There is hereby adopted by the City of Grapevine, Texas, for the purpose of providing minimum standards to safeguard life, limb, health, property and public welfare by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance of heating, ventilation, cooling, refrigeration systems, incinerators, and other miscellaneous heat -producing appliances, the 2021 International Mechanical Code [remainder of section unchanged) Section 7-151. — Amendments. Section 101.1 [Name of Jurisdiction] changed to "City of Grapevine, TX" Section 102.8; change to read as follows: 102.8 Referenced Codes and Standards. The codes and standards referenced herein shall be those that are listed in Chapter 15 and such codes, when specifically adopted, and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the adopted amendments. Any reference to NFPA 70 Ordinance No. 2023-081 48 shall mean the Electrical Code as adopted. Where the enforcement of a provision of this code would violate the conditions of the listing of appliances or equipment, the conditions of the listing and the manufacturer's installation instructions shall apply. Section 202; add definition of "Conditioned space" and "Appliance, Unvented" to read as follows: CONDITIONED SPACE. An area, room, or space that is enclosed within the building thermal envelope and is directly or indirectly heated or cooled. Spaces are indirectly heated or cooled where they communicate through openings with conditioned spaces, where they are separated from condition spaces by uninsulated walls, floor or ceilings, or where they contain insulated ducts, piping or other sources of heating or cooling. Additionally, the attic space shall be provided with active or passive heating systems capable of maintaining an indoor temperature of not less than 55 degrees F at a point 3 feet above the floor. APPLIANCE, UNVENTED. An appliance designed or installed in such a manner that the products of combustion are not conveyed by a vent or chimney directly to the outside atmosphere. Such appliances are hereby prohibited by this code. Section 306.3; change to read as follows: 306.3 Appliances in attics. Attics containing appliances shall be provided {bulk of paragraph unchanged} side of the appliance. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. As a minimum, for access to the attic space, provide one of the following: 1. A permanent stair. 2. A pull -down stair with a minimum 300 lb. (136 kg) capacity. 3. An access door from an upper floor level. Exceptions: [remaining text unchanged] Section 306.5; change to read as follows: 306.5 Equipment and Appliances on Roofs or Elevated Structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet (4877 mm) above grade to access, an interior or exterior means of access shall be provided. Exterior ladders providing roof access need not extend closer than 12 feet (2438 mm) to the finish grade or floor level below and shall extend to the Ordinance No. 2023-081 49 equipment and appliances' level service space. Such access shall ... {bulk of section to read the same} ... on roofs having a slope greater than four units vertical in 12 units horizontal (33-percent slope).... {remainder of text unchanged}. Section 306.5.1; change to read as follows: 306.5.1 Sloped Roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25-percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a catwalk at least 16 inches in width with substantial cleats spaced not more than 16 inches apart shall be provided from the roof access to a level platform at the appliance. The level platform shall be provided on each side of the appliance to which access is required for service, repair or maintenance. The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1067 mm) above the platform, shall be constructed so as to prevent the passage of a 21-inch-diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the International Building Code ... {remainder of text unchanged}. Section 501.3; add an exception to read as follows: 501.3 Exhaust Discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a public nuisance and not less than the distances specified in Section 501.3.1. The air shall be discharged to a location from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted into an attic, crawl space, or be directed onto walkways. Exceptions: 1. Whole -house ventilation -type attic fans shall be permitted to discharge into the attic space of dwelling units having private attics. 2. Commercial cooking recirculating systems. 3. Where installed in accordance with the manufacturer's instructions and where mechanical or natural ventilation is otherwise provided in accordance with Chapter 4, listed and labeled domestic ductless range hoods shall not be required to discharge to the outdoors. Ordinance No. 2023-081 50 4. Toilet room exhaust ducts may terminate in a warehouse or shop area when infiltration of outside air is present. ARTICLE Vill. PLUMBING CODE Sec. 7-171. Plumbing code adopted (a) There is hereby adopted by the City of Grapevine, Texas, the 2021 International Plumbing Code {remainder of section unchanged} Sec. 7-177. Amendements. [The plumbing code adopted herein is amended as follows:] Section 101.1[Name of Jurisdiction] changed to "City of Grapevine, TX" Section 102.8; change to read as follows: 102.8 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 15 and such codes, when specifically adopted, and standards shall be considered as part of the requirements of this code to the prescribed extent of each such reference. Where the differences occur between provisions of this code and the referenced standards, the provisions of this code shall be the minimum requirements. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the adopted amendments. Any reference to NFPA 70 shall mean the Electrical Code as adopted. Where the enforcement of a provision of this code would violate the conditions of the listing of appliances or equipment, the conditions of the listing and the manufacturer's installation instructions shall apply. Section 202; add definition of "Conditioned space" to read as follows: Conditioned Space. An area, room, or space that is enclosed within the building thermal envelope and is directly or indirectly heated or cooled. Spaces are indirectly heated or cooled where they communicate through openings with conditioned spaces, where they are separated from condition spaces by uninsulated walls, floor or ceilings, or where they contain insulated ducts, piping or other sources of heating or cooling. Additionally, the attic space shall be provided with active or passive heating systems capable of maintaining an indoor temperature of not less than 55 degrees F at a point 3 feet above the floor. Section 301.6.1; add section to read as follows: Ordinance No. 2023-081 51 301.6.1 Access required. All mechanical, flare, compression, and push -fit joints shall be provided with access or installed in an approved location. Section 305.4.1; change to read as follows: 305.4.1 Sewer depth. Building sewers shall be installed not less than 12 inches (304 mm) below grade. Section 306.2.4; added to read as follows: 306.2.4 Plastic sewer and DWV piping installation. Plastic sewer and DWV piping installed underground shall be installed in accordance with the manufacturer's installation instructions. Trench width shall be controlled to not exceed the outside the pipe diameter plus 16 inches or in a trench which has a controlled width equal to the nominal diameter of the diameter of the piping multiplied by 1.25 plus 12 inches. The piping shall be bedded in 4 inches of granular fill and then backfilled compacting the side fill in 6-inch layers on each side of the piping. The compaction shall be to minimum of 85 percent standard proctor density and extend to a minimum of 6 inches above the top of the pipe. Table 403.1; add footnote "g" to read as follows: g. Drinking fountains are not required in Group M occupancies with an occupant load of 50 or less, Group B occupancies with an occupant load of 25 or less, and for dining and/or drinking establishments. Section 413.4; change to read as follows: 413.4 Required location for floor drains; Floor drains shall be installed in the following areas: 1. In public laundries and in the central washing facilities of multiple family dwellings, the rooms containing automatic clothes washers shall be provided with floor drains located to readily drain the entire floor area. Such drains shall have a minimum outlet of not less than 3 inches (76 mm) in diameter. 2. Commercial kitchens. In lieu of floor drains in commercial kitchens, the Code Official may accept floor sinks. 3. Public restrooms. Section 502.3; change to read as follows: 502.3 Water heaters installed in attics. [Bulk of section unchanged] ...... to allow removal of the water heater. Water heaters shall not be installed in unconditioned attic spaces unless listed for installation outdoors. Section 504.6.; change to read as follows: Ordinance No. 2023-081 52 504.6 Requirements for discharge piping. The discharge piping serving a pressure relief valve, temperature relief valve or combination thereof shall: 1. {unchanged} 2. {unchanged} 3. Not be smaller than the diameter of the outlet of the valve served and shall discharge full size to the air gap. Flexible connectors are prohibited. 4. {unchanged} 5. Discharge to an approved location or to the outdoors. {remainder unchanged} Section 605.9; add item 5. to read as follows: 605.9 Prohibited joints and connections connections shall be prohibited: 1. {unchanged} 2. {unchanged} 3. {unchanged} 4. {unchanged} The following types of joints and 5. Joints in copper or copper -alloy pipe or tubing where underground beneath buildings shall only be made using wrought copper or copper -alloy fittings with brazed joints. Section 608.17.5; change to read as follows: 608.17.5 Connections to lawn irrigation systems. The potable water supply to lawn irrigation systems shall be protected against backflow by an atmospheric -type vacuum breaker, a pressure -type vacuum breaker, a double-check assembly or a reduced pressure principal backflow preventer. A valve shall not be installed downstream from an atmospheric vacuum breaker. Where chemicals are introduced into the system, the potable water supply shall be protected against backflow by a reduced pressure principal backflow preventer. Section 703.6; Delete this section in its entirety. Ordinance No. 2023-081 53 Section 704.5; added to read as follows: 704.5 Single stack fittings. Single stack fittings with internal baffle, PVC schedule 40 or cast-iron single stack shall be designed by a registered engineer and comply to a national recognized standard. Section 712.4.3; add Section 712.4.3.1 to read as follows: 712.4.3.1 Dual Pump System. All sumps shall be automatically discharged and, when in any "public use" occupancy where the sump serves more than 10 fixture units, shall be provided with dual pumps or ejectors arranged to function independently in case of overload or mechanical failure. For storm drainage sumps and pumping systems, see Section 1113. Section 713, 713.1; change to read as follows: ENGINEERED DRAINAGE DESIGN 713.1 Design of drainage system. The sizing, design and layout of the drainage system shall be designed by a registered engineer using approved design methods. Section 903.1.1; change to read as follows: 903.1.1 Roof extension unprotected. Open vent pipes that extend through a roof shall terminate not less than six (6) inches (152 mm) above the roof. Section 1106.1; change to read as follows: 1106.1 General. The size of the vertical conductors and leaders, building storm drains, building storm sewers and any horizontal branches of such drains or sewers shall be based on a rainfall intensity of six (6) inches per hour. Section 1109; change to read as follows: 1109.1 General. Combined sanitary and storm water sewer systems are expressly prohibited by this code. Section 1301.1; Change to read as follows: Section 1301.1 General. The provisions of Chapter 13 shall govern the materials, design, construction and installation and installation of approved systems for the collection, storage, treatment and distribution of nonpotable water. For approved nonpotable rainwater systems, the provisions of CSA B805/ICC805 shall be an alternative for regulating the materials, design, construction and installation of Ordinance No. 2023-081 54 systems for rainwater collection, storage, treatment and distribution of nonpotable water. These systems shall only be installed where approved by the Building Official, in accordance with Texas Commission of Environmental Quality standards and in compliance with state laws, rules and ordinances applicable in the City of Grapevine. Section 1401.1; Change to read as follows: Section 1401.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation and installation of approved subsurface graywater soil absorption (SGSA) systems connected to nonpotable water from on -site water reuse systems. SGSA systems shall only be installed where approved by the county of record and the Building Official. Systems shall be designed in accordance with Texas Commission of Environmental Quality standards and in compliance with state law. ARTICLE IX. - INTERNATIONAL FUEL GAS CODE Sec. 7-181 Fuel Gas Code adopted (a) There is hereby adopted by the City of Grapevine, Texas, the 2021 International Fuel Gas Code {remainder of section unchanged} Sec. 7-185 Amendments. [The fuel gas code adopted herein is amended as follows:] Section 101.1[Name of Jurisdiction] changed to "City of Grapevine, TX" Section 102.8; change to read as follows: 102.8 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 8 and such codes, when specifically adopted, and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the National Electrical Code shall mean the Electrical Code as adopted. Where the enforcement of a provision of this code would violate the conditions of the listing Ordinance No. 2023-081 55 of appliances or equipment, the conditions of the listing and the manufacturer's installation instructions shall apply. Section 202; revise definition of "Appliance, Unvented" to read as follows: APPLIANCE, UNVENTED. An appliance designed or installed in such a manner that the products of combustion are not conveyed by a vent or chimney directly to the outside atmosphere. Such appliances are hereby prohibited by this code. Section 202; add definition of "Conditioned space" to read as follows: Conditioned Space. An area, room, or space that is enclosed within the building thermal envelope and is directly or indirectly heated or cooled. Spaces are indirectly heated or cooled where they communicate through openings with conditioned spaces, where they are separated from condition spaces by uninsulated walls, floor or ceilings, or where they contain insulated ducts, piping or other sources of heating or cooling. Additionally, the conditioned attic space within the building thermal envelope shall be provided with active or passive heating systems capable of maintaining an indoor temperature of not less than 55 degrees F at a point 3 feet above the floor. Section 306.5; change to read as follows: [M] 306.5 Equipment and Appliances on Roofs or Elevated Structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet (4877 mm) above grade to access, an interior or exterior means of access shall be provided. Exterior ladders providing roof access need not extend closer than 12 feet (2438 mm) to the finish grade or floor level below and shall extend to the equipment and appliances' level service space. Such access shall ... {bulk of section to read the same} ... on roofs having a slope greater than four units vertical in 12 units horizontal (33-percent slope).... {remainder of text unchanged} Section 306.5.1; change to read as follows: [M] 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of 3 units vertical in 12 units horizontal (25-percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a catwalk at least 16 inches in width with substantial cleats spaced not more than 16 inches apart shall be provided from the roof access to a level platform at the appliance. The level platform shall be provided on each side of the appliance to which access is required for service, repair or maintenance. The platform shall be not less than 30 Ordinance No. 2023-081 56 - inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1067 mm) above the platform, shall be constructed so as to prevent the passage of a 21-inch-diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the International Building Code. Section 401.5; add a second paragraph to read as follows: Both ends of each section of medium pressure gas piping shall identify its operating gas pressure with an approved tag. The tags are to be composed of aluminum or stainless steel and the following wording shall be stamped into the tag: "WARNING: 1/2 to 5 psi gas pressure - Do Not Remove" Section 404.12; change to read as follows: 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 18 inches below grade. 404.12.1 Delete in its entirety. Section 406.4; change to read as follows: 406.4 Test pressure measurement. Test pressure shall be measured with a monometer or with a pressure -measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than five times the test pressure. Spring type gauges do not meet the requirement of a calibrated gauge. Section 406.4.1; change to read as follows: 406.4.1 Test pressure. The test pressure to be used shall be no less than 3 psi (20 kPa gauge), or at the discretion of the Code Official, the piping and valves may be tested at a pressure of at least six (6) inches (152 mm) of mercury, measured with a manometer or slope gauge, For tests requiring a pressure of 3 psig, diaphragm gauges shall utilize a dial with a minimum diameter of three and one half inches (3 Y2"), a set hand, 1/10 pound incrementation and pressure range not to exceed 15 psi for tests requiring a pressure of 3 psig. For tests requiring a pressure of 10 psig, diaphragm gauges shall utilize a dial with a minimum diameter of three and one-half inches (3 Y2"), a set hand, a minimum of 2/10 pound incrementation and a pressure range not to exceed 50 psi. For welded piping, and Ordinance No. 2023-081 57 for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa) (1/2 psi) and less than 200 inches of water column pressure (52.2 kPa) (7.5 psi), the test pressure shall not be less than ten (10) pounds per square inch (69.6 kPa). For piping carrying gas at a pressure that exceeds 200 inches of water column (52.2 kPa) (7.5 psi), the test pressure shall be not less than one and one-half times the proposed maximum working pressure. Diaphragm gauges used for testing must display a current calibration and be in good working condition. The appropriate test must be applied to the diaphragm gauge used for testing. Section 409.1; add Section 409.1.4 to read as follows: 409.1.4 Valves in CSST installations. Shutoff valves installed with corrugated stainless steel (CSST) piping systems shall be supported with an approved termination fitting, or equivalent support, suitable for the size of the valves, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration but in no case greater than 12-inches from the center of the valve. Supports shall be installed so as not to interfere with the free expansion and contraction of the system's piping, fittings, and valves between anchors. All valves and supports shall be designed and installed so they will not be disengaged by movement of the supporting piping. Section 411.1.3.3: Prohibited locations and penetrations; delete Exception 1 and Exception 4: Section 621 Unvented Room Heaters: is deleted and replaced with the following: 621 Unvented Room Heaters. G2445.1 General. Unvented room heaters, and any other unvented heating appliance or fireplace are strictly prohibited by this code where installed indoors regardless of manufacturers listing. ARTICLE XI. - SWIMMING POOLS Sec 7-207. Definitions. For the purpose of this article, "swimming pool" shall mean all permanent structures or excavations which contain or may contain a body of water over 24 inches in depth, which is used for recreation bathing or swimming purposes. Ordinance No. 2023-081 58 Private Swimming Pool, Spa, or Hot Tub: A swimming pool, spa, or hot tub located on the premises of a single-family or duplex residence, under the control of the owner or tenant, the use of which is limited to members of the household and invited guests. Public Swimming Pool, Spa, or Hot Tub: Any swimming pool, spa, or hot tub not classified as a public swimming pool, spa, or hot tub. Sec 7-208. Adoption of State Regulations The City of Grapevine hereby adopts by reference the most current International Swimming Pool and Spa Code as adopted by the State of Texas. Sec 7-209. Public Swimming Pools; Regulation The regulation of public swimming pools, spas, and hot tubs shall be as defined in Chapter 12 of this code. Section 7-210. Permit Fees; Contractor Registration Permit fees for swimming pools shall be as required for building permits as described elsewhere in this code. Plumbing and electrical permit fees shall be required in addition to the building permit fee. Contractors shall be registered and regulated as general contractors as described elsewhere in this code. Section 7-211-7-220, Reserved. Section 9. Any person violating any of the provisions of this ordinance shall be deemed guilty of a misdemeanor and upon conviction thereof shall be fined in a sum not to exceed Two Thousand Dollars ($2,000.00) for each offense and a separate offense shall be deemed committed each day during or on which an offense occurs or continues. Section 10. All ordinances or any parts thereof in conflict with the terms of this ordinance shall be and hereby are deemed repealed and of no force or effect. Section 11. If any section, subsection, sentence, clause or phase of this ordinance shall for any reason be held to be invalid, such decision shall not affect the validity of the remaining portions of this ordinance. Section 12. That the effective date of this rate adjustment will be January 1, 2024. Ordinance No. 2023-081 59 PASSED AND APPROVED BY THE CITY COUNCIL OF THE CITY OF GRAPEVINE, TEXAS on this the 21 st day of November, 2023. William D. Tate Mayor ATTEST: GRAP,ple Tara Brooks City Secretary APPROVED AS TO FORM: Matthew t.6. Boyle City Attorney Ordinance No. 2023-081 60