HomeMy WebLinkAboutSFRA2024-003337 -INHOWN0201 I-VA1199
LOT.- BLOCK: SUBDIVISION:
BUILDING CONTRACTOR (company name):
CURRENT MAILING ADDRESS:
CITY/STATE/ZIP:
PROPERTY OWNER:
CURRENT MAILING ADDRESS:
CITY/STATE/ZIP:
PROJECT VALUE: $
DESCRIPTION OF WORK TO BE DONE:
USE OF BUILDING OR STRUCTURE:
["HONE NUMBER:
ELECTRIC PLUMBING
OK
Fax #
Total Square Footage under roof- Square Footage of alterationladdition-
I I hereby certify that plans have been reviewed and the building will be inspected by a certified energy code inspector in accordance with
State Law. Plan review and inspection documentation shall be made available to the Building Department (required for new buildings,
alterations and additions)
El I hereby certify that plans have been submitted to the Texas Department of Licensing and Regulation for Accessibility Review.
Control Number: - (Not required for I & 2 family dwellings)
Ll I hereby certify that an asbestos survey has been conducted for this structure in accordance with the regulatory requirements of the Texas
Department of Health.
(REQUIRED FOR DEMOLITIONS, ADDITIONS AND OR ALTERATION TO COMMERCIAL AND PUBLIC BUILDINGS)
I hereby certify that the foregoing is correct to the best of my knowledge and all work will be performed according to the documents approved by
the Building Department and in compliance with the City Of Grapevine Ordinance regulating construction. It is understood that the issuance of
this permit does not grant or authorize any violation of any code or ordinance of the City Of Grapevine. I FURTHERMORE UNDERSTAND
THAT PLANS AND SPECIFICATIONS ARE NOT REVIEWED FOR HANDICAPPED ACCESSIBILITY BY THE CITY, AND THAT THE
DESIGN PROFESSIONAL/OWNER IS RESPONSIBLE FOR OBTADffNG SUCH APPROV-% I FROM THE APPROPRIATE STATE AND
OR FEDERAL AGENCY(S).
PRINT NAME: SIGNATURE
PHONE
0 CHECK Box w PREFERRED TO BE CONTACTED BY E-MAIL
THE FOLLOWING IS TO BE COMPLETED BY THE BUILDING INSPECTION DEPARTMENT
Construction Tv )ebacks Approval to Issue
Occupanc% Group: Fire Sj)rinkler: Y'ES NO Front:
Electrical
Division.
-2oning:
:7
5
Ooad:
Plan Review Ayproval:
Site Plan oval:
Fire Department:
Public Works Department:
Health Department:
Approved for Permit:
Lot Drainage Submitted-':
Buildim., D Left: Plumbing
Buildim, it: Rear:
I Mechanical
Grease Tra 1 Ri!+t: I Hood
Date:
Permit Fee:
Building
Date: Plan Review Fee:
Date: Lot Drainasye Fee:
J
Date: Sewer Availability, Rate:
Date: Water Availability Rate:
Date: Total Fees:
Approved: ¢ Total Amount Due:
P.O. BOX 95104, GRAPEVINE, TX 76499 (817) 41G-3165 0:FORWDSPERMTTAPPLICATIONS
ADDRESS
1114 Valley Vista Dr.
Grapevine, TX 76051
LEGAL
Bellaire Addition Blk 2
Lot 12
*00152293*
PERMIT HOLDER
Ben Lord
Texas Foundation Expert
s
(817) 917-9381
COLLABORATORS
•Ben Lord
Texas Foundation
Experts
(817) 917-9381
OWNERS
•Russell, Richard
Anthony
INSPECTIONS 1
1. Building Final
INFORMATION FIELDS
**APPLICANT NAME (Individual)Katy Lindholm
**APPLICANT PHONE NUMBER 682-287-6611
VALUATION 6200
* CONSTRUCTION TYPE VB
* OCCUPANCY GROUP R-3
DOCUMENTS - MISC 01 Grapevine-BUILDING PERMIT
APPLICATION 1.pdf
DOCUMENTS - MISC 02 1114 Valley Vista TFE Cursory Review
1.pdf
* ZONING DISTRICT R-7.5
FEE TOTAL PAID DUE
Building Permit Fee, ($150.00
Flat Fee) Simple Alteration $ 150.00 $ 150.00 $ 150.00
TOTALS $ 150.00 $ 150.00 $ 0.00
READ AND SIGN
I HEREBY CERTIFY THAT THE FOREGOING IS CORRECT TO THE BEST OF
MY KNOWLEDGE AND ALL WORK WILL BE PERFORMED ACCORDING TO
THE DOCUMENTS APPROVED BY THE BUILDING DEPARTMENT AND IN
COMPLIANCE WITH THE CITY OF GRAPEVINE ORDINANCE REGULATING
CONSTRUCTION. IT IS UNDERSTOOD THAT THE ISSUANCE OF THIS PERMIT
DOES NOT GRANT OR AUTHORIZE ANY VIOLATION OF ANY CODE OR
ORDINANCE OF THE CITY OF GRAPEVINE.
I FURTHERMORE UNDERSTAND THAT PLANS AND SPECIFICATIONS ARE
NOT REVIEWED FOR HANDICAPPED ACCESSIBILITY BY THE CITY AND THAT
THE DESIGN PROFESSIONAL / OWNER IS RESPONSIBLE FOR OBTAINING
SUCH APPROVAL FROM THE APPROPRIATE STATE AND OR FEDERAL
AGENCY(S).
September 19, 2024
City of Grapevine
PO Box 95104
Grapevine, Texas 76099
817) 410-3166
Building - Residential
Alteration
Project # 24-003337
Project Description: Install (13) Concrete Piers on Exterior of
home.
Issued on: 09/19/2024 at 9:20 AM
MYGOV.US 24-003337, 09/19/2024 at 9:20 AM Issued by: Connie Cook
Page 1/2
Signature Date
City of Grapevine Building - Residential Alteration
Project # 24-003337
NOTICES
1) ALL work must be done in compliance with the 2021 INTERNATIONAL BUILDING CODE.
**ALL work ISSUED prior to January 1, 2024, must be done in compliance with the 2006 INTERNATIONAL
BUILDING CODE.
2) City Approved Stamped Plans must be on-site for ALL INSPECTIONS.
3) Project address must be clearly posted at the job site.
NOTES
> 24 HOUR INSPECTION NUMBER
METRO (817) 410-3010, CUT OFF TIME FOR A.M. INSPECTION IS 7:30 A.M. --- CUT OFF TIME FOR P.M.
INSPECTION IS 12:30 P.M.
> PERMIT ISSUED IN ACCORDANCE WITH APPLICATION ON FILE IN THIS OFFICE.
THIS PERMIT SHALL EXPIRE IF WORK IS NOT COMMENCED WITHIN (180 DAYS) OF ISSUANCE OR IF
WORK IS SUSPENDED OR ABANDONED FOR A PERIOD OF (180 DAYS). THE ISSUANCE OR
GRANTING OF THIS PERMIT AND / OR APPROVAL OF PLANS, SPECIFICATIONS AND
COMPUTATIONS SHALL NOT BE CONSTRUED TO BE A PERMIT FOR, OR AN APPROVAL OF, ANY
VIOLATION OF ANY OF THE PROVISIONS OF THE CODES AND ORDINANCES OF THE CITY OF
GRAPEVINE. THE ISSUANCE OF A PERMIT BASED ON PLANS, SPECIFICATIONS, AND OTHER DATA
SHALL NOT PREVENT THE BUILDING DEPARTMENT FROM THEREAFTER REQUIRING THE
CORRECTION OF ERRORS IN SAID PLANS, SPECIFICATIONS, AND OTHER OR REQUIRING
CORRECTIONS OF THE CONSTRUCTION ITSELF.
MYGOV.US 24-003337, 09/19/2024 at 9:20 AM Issued by: Connie Cook
Page 2/2
601 Corry A Edwards Drive
!n Kennedale, Texas 76060
f8M 576-1973
C, 0 N U L I A IT Texas Registered Engineering Firm F-15336
Date: September 11, 2024
Attention: Texas Foundation Experts
Subject: Cursory Foundation Repair Report
Slab Foundation
1114 Valley Vista Drive, Grapevine, TX 76051
To Whom It May Concern:
Thomas Engineering Consultants JEC) was retained to conduct a review of the limited foundation repair Plan
prepared by Texas Foundation Experts (the contractor) to determine, in our opinion, if the recommended
remediation plan is a reasonable plan of repair based on the relative elevation map provided.
The contractor provided a limited repair plan which included the pre -lift elevations and recommended piling
locations for the structure for our review. No other information was provided regarding any exploratory
measures such as soil testing concrete testing, prior engineering reports, prior recommendations for
foundation repairs, or any construction documents relative to this structure. If existing pilings are shown in
the limited repair plan, then their locations were provided by either the homeowner or contractor. Suchexisting
pilings are approximated and are not certified in any way by TEC. If the reader would like to determine if they
are present, they must contact the homeowner or contractor to obtain an engineering certificate certifying
them. TEC has not performed a visual inspection of the subject structure.
According to the contractor, the foundation system appears to have settled towards the areas where
foundation remediation is recommended which coincides to areas of cosmetic stress. Texas Foundation
Experts has included the following items in their recommended limited repair plan:
• Install 13 Concrete Piers
• Install/Replace Bearrits) per Texas Foundation Experts Limited Repair. Plan and Estimate Details
• Re -shim substructure per Texas Foundation Experts Limited Repair Plan and Estimate Details
The foundation repairs are intended to meet or exceed 2021 IRC. Based on the contractor's evaluation of the
property in conjunction with TEC's review of the elevation drawing, it is the opinion of TEC that the proposed
limited repair plan is a reasonable and limited repair. Modifications to this plan may become necessary based
on field conditions discovered during execution by the foundation crew.
This report provides our reasonable professional opinion of the condition of the foundation on the date of the
inspection by the contractor and is based on the data provided to us and does not take into consideration any
changes in the condition of the foundation or soils after that date, The contents of this report supersede any
verbal comments made regarding the structure before, during or after the inspection. Although document
review is an integral part of the foundation repair process, we recommend obtaining a visual inspection by a
licensed engineer. TEC can complete this visual inspection for an additional fee.
W.W F, Tf
't Tr fIT7
-fb ff -,T[fCeT
-?,nd is not intended to level the foundation. The contractor shall determine the amount of elevation correction
needed based on the reaction of the structure during the lift in order to minimize damages and additional
RECEIVED 9.1612024
24-003337
1114 VALLEY VISTA DRIVE
FOUNDATION REPAIR
fim• !
Because the structure has endured pre -repair foundation differential movement, residual differential elevation
and perceptible floor slope or other noticeable issues may remain following the foundation repairs. Damage
to the structure may arise during the foundation repair installation activities. We recommend pre -lift and post -
lift plumbing tests be performed on the sewer and potable plumbing lines. Any leak found shall be repaired
immediately.
Please see the attachments for additional information on the recommended repairs as well as the general
recommendations for maintaining foundations in North Texas. If you have any questions or if we can be of
lurther service, please give us a call. We appreciate the opportunity to serve you.
Very truly yours,
Attachments:
TEC - Disclosure & Disclaimer
TFE - Limited Repair Plan
TFE - Combination Piling
TFE - Concrete Piling
TFE - Steel Piling
TFE - Pier and Beam Interior Support
TEC - General Recommendations for a Foundation Maintenance Program
...............................................
Property Address: 1114 Valley Vista Drive, Grapevine, TX 76051
DISCLOSURE & DISCLAIMER:
It is known to knowledgeable professional engineers that the soils in this area are subject to movement due
to expansion, contraction or densification of the soils etc. This soil movement could possibly cause the
foundation to move after the remediation plan within the attached report has been implemented and may
impact the stability of the foundation and cause damage. NO WARRANTY IS EXPRESSED OR IMPLIED BY
THIS ENGINEER AS TO THE PERFORMANCE OF THIS FOUNDATION OR THE REPAIRS THERETO.
Diligent foundation maintenance to maintain consistent soil conditions along the perimeter should reduce
further problems after the recommendations within this report have been implemented. However, seasonal
moisture variations, water leaks, erosionlra.nd"oth—er factors maV-pffect the stability of the foundation and put it
in danger of further damage.
REPORT LIMITATIONS:
This report is written for informational purposes only and is not intended to be a detailed technical evaluation
of the property or an inventory of defects. The opinions expressed in this report are based on a visual
evaluation of current conditions observed at the time of the inspection. THERE IS NO WARRANTY,
EXPRESSED OR IMPLIED, CONCERNING THIS ENGINEERING REPORT.
The information in this report supersedes any verbal comments, expressed or implied, made by Thomas
Engineering Consultants or its principals, agents or employees. The client agrees that neither TEC nor its
employees or owners will be responsible for:
1 . Knowledge of the subsurface condons without extensive geotechnical data obtained from onsite
drng and testing of the recovered samples,
2. Knowledge of cracks, vertical differential displacement of floors without uncovering of the floor by the
client; and
3. Any other element such as joists or beams and other structural members that is boxed or otherwise
not readily available to TEC for viewing, and releases TEC from any liability attributable to such
knowledge or condons.
Any prescribed repair or maintenance plan detailed by this report is based on observations of apparent
performance of the structure at the time of this assessment. Compliance with any code or specification other
than as expressly noted is specifically excluded.
F, IeUlf-( rf n Fe7-11#,WtTi#7 f g-'cff W-Lf7d5�f5l7iff 17-d777T
now exist and DOES NOT IMPLY OR WA14RANT THAT OTHER PROBLEMS AND OR AREAS MAY NOT
MANIFEST IN THE FUTURE. This report was prepared expressly for the client and expressly for the purposes
indicated by the client. Permission for use by any other person for any purpose, or by the client for different
purpose is denied unless otherwise stated in writing by TEC.
MINNIEaN ,
6,1111 wi1"1 A.
1111, 0. 1."LM
lot
1:1200101:101112V z"Nsoall"IMIN211 W401111111150105 1*041 1114,
TEC expressly DISCLAIMS ANY WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE and the client
expressly disclaims that it has contracted for or received any warranty of fitness for a particular purpose with
respect to this report. THE REPORT UNDER THIS AGREEMENT IS THE OPINION OF TEC AND THERE
ARE NO WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS
AGREEMENT.
Thomas Engineering Consultants
Property Address: 1114 Valley Vista Drive, Grapevine, TX 76051
TFE — Limited Repair Plan
M4 Valley Vista, Grapevine TX
682-365-7929 marghail@env itioripr"rtgbugett,corn
0.9
02
"Ll (?OC
I
03
05
'd
0.6 04
r—xt. tea-,
This drawing is provided for preliminary permitting purposes only and is a limited plan of repair, Additional work may be
needed once the foundation work has begun based on the performance of this limited plan of repair, Thomas Engineerinq
fim=lil!
Consultants has provided review of this limited plan of repair and it is our opinion that it is reasonable and safe for the
structure, If interior piers are shown on this drawing the contractor will place them based on the locations of grade beams,
plumbing lines and post tension cables, therefore, the locations shown on this map are approximate. The contractor shall
provide the means -and -methods of this installation. Additional repairs may be required upon review of the structure by
Thomas Engineering Consultants. This is a proposed scope of work and has not been completed therefore we do not certify
any existing or proposed foundation repair work on this map at this time. If the reader would like to be certain that any
proposed or existing repairs have been completed they must request an engineering certificate for the subject foundation
work from the foundation repair company.
Thomas Engineering Consultants
Property Address: 1114 Valley Vista Drive, Grapevine, TX 76051
3a��=
I
Void after
Lifting Foundation
Steel Shims
Concrete Cylinders
Cap 13106n
12' LENGTH
Soil6'DIAMET
ER
PILE SECTION
75
err
Transition from
concrete to steel
Uri
_j Steel cap sheet
L 2-7/8 Clutter steel pipe
(D
2-3/8 Inner Steel pipe
Thomas Engineering Consultants
Property Address: 1114 Valley Vista Drive, Grapevine, TX 76051
SIDE VIEW
ME
N
FRONT VIEW
�'OJNDA'104
co'w'R' ---
CYLINIDERS,
x
CAP
PIROVV)�A) BY V/ 1 0
COLUNIN", Of ;t,l 04
94 SG,� i� D�'111 1 60
F,AQ 1:11'R
GKCA 7 N PLAC,'1%
L.A'TRAt
C,YJJNJ[)Lf�S12' 18'"
'A 24' SECT K)NS
MAY Bi- usD'
fim��
V LF1411; 1 -4
6' DIAME7F_R
4" , DIANIF ' R , SLIC I IONS
PIL'
THOWO,A 1.10NOP, jR
A k
ME=
Property Address: 1114 Valley Vista Drive, Grapevine, TX 7605""
--+0UNDATIOt',�
STEEL SHIM3
CO!'NCRETE CYLINDEF
CONCRETE OR STEEL
STEEL CAP SHEET
--2-71'8" OUTER STEEL
-2-3/8" INNER STEEL
...........
I
TWMA�,A
Thomas Engineering Consultants
Property Address: 1114 Valley Vista Drive, Grapevine, TX 76051
SONOTUBE DETAIL
(if applicable)
GIRDER IREAM
SCALE. N TS
METAL SHIMS
19'(WN) SONOTUBE ----- -
FILLED WITH 3,000 PSI (MIN) (4) #4 REBAR
f- nrlt Mir" 1 M /M
#3 STIRRUPS
NOTE MINIMUM PAD DEPTH 24 INCHES
PAD /BLOCK DETAIL
(if applicable)
GIRDER IBEAM
SCALE N TS
-METAL SHIMS
8" x 8" (MIN) CNIU BLOCK
FILLED WITH GROUT
GROUND LEVEL
#5 REBAR - 2 EA
18"x24"XG"ftvllN)COt,ICRETEPAD
3,000 PSI (MIN) w/(4) #4 REBAR 0 C E .W
NOTE: MINIMUM PAD DEPTH 24 INCHES
4:
5
07
.