HomeMy WebLinkAboutDFW West Logistics_Fire Protection Engineer_Letter of Engineering Compliance_12.11.24 TEXAS SPRINKLER 609 Industrial Blvd. Grapevine Texas 76051 (817) 416-0160 • FAX (817) 416-0862 TEXAS STATE CERTIFICATION REGISTRATION NO. 0785 December 11, 2024 Grapevine Fire Department 1007 Ira E Woods Avenue Grapevine, Texas 76051 Re: Project Swanson Permit Number GRA-2024-0000216 3642 Euless Grapevine Road Grapevine, Texas 76051 Texas Sprinkler completed the original ESFR shell system work at the above referenced project. All work is in compliance with NFPA 13, and the city of Grapevine. The systems are designed utilizing K22 ESFR’s flowing 12 heads at 40 psi. For buildings not exceeding 45 ft. top of steel, this ESFR design criteria will protect palletized, solid- piled, and open frame rack storage of Class I through IV encapsulated or unencapsulated products & cartoned unexpanded plastic products stored up to 40 ft. in up to a 45 ft. building. Open top containers & solid shelving is not permitted. All transverse and longitudinal flue spaces must be maintained per NFPA. A 36” minimum clearance from top of storage to sprinkler deflector must be maintained. These criteria will not protect exposed unexpanded plastics, or any expanded plastics. Respectfully submitted, Ricky Wright, CET RME-G 1743604 Texas Sprinkler Fire Protection Engineering Technology Water-Based Systems – Level III NICET #69212