Project
No.
Approved
Checked
Drawn
REVISIONS
DateNo. Item
KEY PLAN
SCHEDULE
13012
08.21.2024
Code Information Summary
Square Footages:
Lease Space = 1965 SF
Jurisdictions:
City of Grapevine building department
Applicable information:
Codes: 2021 IBC
2021 IPC
2021 IMC
2020 NEC
2021 IECC
Regulations- TDLR- Texas Accessibility ST.
Building Occupancy B
Construction Type II- B
Interior wall & ceiling finish requirement
Class C
Flame Spread 76-200
Smoke developed: 0-450
Occupant load calculation:
1. Waiting space & Office: 1393 SF( 1393/150= 9 O.C.C.)
2. Fixed Seating & Bed: 15 O.C.C.
Total Actual Occupant Load = 24 O.C.C.
Number of restroom required= 1
Number of restroom provide= 1 Unisex ADA restroom, 1 staff restroom
Building egress-
Number of exists required: 1
Number of exists provided: 2
Egress width required: 36"
Egress width provided: 36"
Max. travel distance= 62'
GENERAL NOTES:
1. The general contractor shall verify all conditions and dimensions on the job
site and report any discrepancies and/or unusual conditions to the architect
prior to finalizing contract and commencement of construction.
2. Contractor shall provide public protection as necessary and required by the
local city requirements.
3. While the drawings have been segmented into standard divisions generally
reflecting the scope of work of different trades, work required of any trade may
be shown anywhere in the drawings.
Contractors is therefore cautioned to base contract on the entire integrated
construction documents. No claim for an extra will be considered for failure to
do so.
4. In the event of discrepancies between various drawings, report conditions to
architect in timely manner to allow review and response.
5. Unless otherwise indicated on these drawings as being N.I.C or existing, all
items, material etc. and installation of same are a part of the contract defined by
these drawings.
6. Colors shall be provided by architect, unless otherwise noted, upon
completion of approved color selection board.
7. Unless otherwise noted, exterior and interior exposed metal trim, treillage,
railings, moldings, frames, casting, W.I. work etc. shall be painted.
8. General contractor to keep site clean at all times.
9. Gaps between different materials or at corners shall be sealed.
10. Roof penetrations for new mechanical equipment shall conform w/existing
roofing manufacturers, warranty details, so as to maintain warranty coverage.
VICINITY MAP
G-001
Room NO. AREA
WO
O
D
VINYL
EP
O
X
Y
CO
N
C
R
E
T
E
QU
A
R
R
Y
TI
L
E
VI
N
Y
L
ST
A
I
N
L
E
S
S
ST
E
E
L
CO
V
E
ST
R
I
P
CE
R
A
M
I
C
CO
V
E
TI
L
E
QU
A
R
R
Y
CO
V
E
D
TI
L
E
EX
I
S
T
I
N
G
VI
N
Y
L
BA
S
E
GY
P
.
BO
A
R
D
CE
R
A
M
I
C
TI
L
E
(
5
'
AF
F
)
WI
T
H
PA
I
N
T
AB
O
V
E
FR
P
UP
TO
CE
I
L
I
N
G
ST
A
I
N
L
E
S
S
ST
E
L
L
SH
E
E
T
@ VE
N
T
HO
O
D
ON
L
Y
FR
P
UN
D
E
R
CO
U
N
T
E
R
CE
R
A
M
I
C
TI
L
E
TO
CE
I
L
I
N
G
FR
P
(4
'
AF
F
)
@ BE
H
I
N
D
BE
V
E
R
A
G
E
CO
O
L
E
R
S
CE
R
A
M
I
C
TI
L
E
AB
O
V
E
CO
U
N
T
E
R
TO
CE
I
L
I
N
G
AC
T
(
2
'
x
2
'
)
‐
VI
N
Y
L
FA
C
E
AC
T
(
2
'
x
2
'
)
GY
P
BO
A
R
D
CE
I
L
I
N
G
WI
T
H
OI
L
BA
S
E
D
EN
A
M
E
L
PA
I
N
T
AC
T
(
2
'
x
4
'
)
‐
VI
N
Y
L
FA
C
E
AC
T
(
2
'
x
4
'
)
OP
E
N
TO
ST
R
U
C
T
U
R
E
.
PT
D
O
CEILINGSBASE WALLSFLOOR
CE
R
A
M
I
C
CO
V
E
TI
L
E
Room Finish General Note:
1.
2. Provide schluter transition edge to floor for restroom per city of Grapevine requirement.
3. Provide vinyl clad hard gypsum ceiling product specified by USG, Gold Bond and Vinyl Rock.
4. All the epoxy paint wall are white color.
Amoi Group, LLC
8750 N Central Expressway, STE 800
Dallas, Texas 75213 972. 908. 9558
ISSUE FOR
PERMIT
Restroom ceramic tile finish are 24"*24" white color on floor.
UNRED
3
O
TANG MASSAGE SPA
3105 Ira E. Wds Ave Suite 134, Grapevine, TX 76051
101 LOBBY
X
X
X
X X
X
X
X
X
X
X
X
X
X
X
X
Room Schedule
1. ANY AND ALL PAINTED SURFACES MUST BE ABOSULATELY, TOTALLY SMOOTH, WITH ABSOLUTELY NO SURFACE TEXTURING.
THIS APPLIES TO ANY PAINTED GYPSUM BOARD CEILINGS IN THE RESTROOMS, AS WELL AS ANY PAINTED GYPSUM BOARD WAL
IN ANY FOOD HANDLING, FOOD STORAGE, OR WARE WASHING AREAS.
2. RESTROOM FINISH SHALL COMPLY WITH IBC 2021.
102 110 MASSAGE ROOM
111 STAFF ROOM
112 113 RESTROOM
TA
N
G
M
A
S
S
A
G
E
S
P
A
31
0
5
I
r
a
E
.
W
d
s
A
v
e
S
u
i
t
e
1
3
4
,
G
r
a
p
e
v
i
n
e
,
T
X
7
6
0
5
1
㈰㈴⼱㈯㈷
㈰㈴⼱㈯㈷
Sheet Number Sheet Name
G-001 KEY PLAN SCHEDULE
I-100 INTERIOR LAYOUT PLAN
I-200 RCP PLAN
I-300 INTERIOR DETAILS
I-400 ADA DETAILS
M-100 HAVC FLOOR PLAN
P-100 PLUMBING FLOOR PLAN
E-100 ELECTRICAL POWER PLAN
E-200 LIGHTING PLAN
E-300 ELECTRICAL ONE LINE
01/14/2025
Last Revision
Date
Project
No.
Approved
Checked
Drawn
REVISIONS
DateNo. Item
Amoi Group, LLC
INTERIOR
LAYOUT PLAN
13012
08.21.2024
8750 N Central Expressway, STE 800
Dallas, Texas 75213 972. 908. 9558
I-100
1'
ISSUE FOR
PERMIT
UNRED
380
2024/09/18
INTERIOR LAYOUT CONTROL PLAN 1 1/4"= 1'
LEGEND
NEW WALL
TYPE PARTITION GA. HGT GYM. BOARD TYPE INSULATION
A2 U 465 20 B.O. DECK 5/8" TYPE "X" GYP. BD. ON 4" MTL. STUDS @ 16" O.C. ON BOTH SIDES BATT INSULATION (R19)
A3 25 10' 5/8" WR GYP. BD. ON 6" MTL. STUDS @ 24" O.C. ON BOTH SIDES BATT INSULATION (R13) @TOILET
A4 EXISTING B.O. DECK 5/8" TYPE "X" GYP. BD. ON EXISTING WALL ON ONE SIDE BATT INSULATION (R13) @TOILET
A5 25 10' 5/8" WR GYP. BD. ON 3 5/8" MTL. STUDS @ 24" O.C. ON ONE SIDE BATT INSULATION (R13) @TOILET
A6 25 4'(V.I.F.) 5/8" GYP. BD. ON 3 5/8" MTL. STUDS @ 24" O.C. ON BOTH SIDES NO BATT INSULATION
A7 25 10' 5/8" TYPE "X" GYP. BD. ON 6" MTL. STUDS @ 24" O.C. ON BOTH SIDES BATT INSULATION (R13) @TOILET
A8 18 B.O. DECK 5/8" TYPE "X" GYP. BD. ON 3 5/8 MTL. STUDS @ 24" O.C. ON BOTH SIDES NO BATT INSULATION
A9 25 FURR DOWN 5/8" TYPE "X" GYP. BD. ON 3 5/8 MTL. STUDS @ 24" O.C. ON ONE SIDE NO BATT INSULATION
A10 25 FURR DOWN 5/8" TYPE "X" GYP. BD. ON 3 5/8 MTL. STUDS @ 24" O.C. ON BOTH SIDES NO BATT INSULATION
1
2
3
1 2 3
1. All the hardware to be schlage lever handle hardware with 626 finish, provide silencers, hinges and latch
sets for each door as required.
2. Provide closures( LCNA69- or approved Alum. equal)on toilet doors & exit doors.
Note:
1. Provide membrane penetration fire stopping design number and details for both demising walls
2. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface,
to a height of not less than 4 feet above the floor.
Door Hardware Schedule
㌮⁁汬湴敲楯爠睡汬猠獨慷攠瑹灥⁁㈠㘢祰獵洠扯慲搠睡汬
W
113
53.11 sf
SLIDE
3 3
䵁卓
剏位
76.
MASSAGE ROOMRESTROOMLOBBYㄳ
A2
䍏
13
'
-
9
"
8'
-
0
"
8'
-
0
"
13
'
-
3
"
10'-6"
0'-6"
9'-0"
10
'
-
0
"
6'-6"
10'-6"
19
'
-
0
"
14
'
-
0
"
22
'
-
3
"
22
'
-
9
"
10'-6"
7'
-
6
"
40
'
-
0
"
14
'
-
0
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
0'
-
6
"
14
'
-
0
"
4'-0"
26'-0"
4'
-
0
"
䙒低吠䑅卋䙏佔
73
'
-
0
"
10
'
-
0
"
坁午䕒
0'-3"
1'
-
0
"
䙒低吠䑏佒
80.75 sf 57 sf
196.3 sf
351.54 sf
144.55 sf
84.01 sf
84.01 sf
139.12 sf
78.76 sf
78.76 sf
78.76 sf
78.76 sf
78.76 sf
61
.
3
1
f
t
60
.
2
7
f
t
51
.
9
5
f
t
51
.
1
8
f
t
1
3 3
3
3
3
3
3
3
3
3
3
3
1 Hour Fire Rating
Demising Wall Existing
NEW COLUMNS
FOR DECORATION
3
2
1 Hour Fire Rating
Demising Wall Existing
䄲
䄲
䄲
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
䄸
TA
N
G
M
A
S
S
A
G
E
S
P
A
31
0
5
I
r
a
E
.
W
d
s
A
v
e
S
u
i
t
e
1
3
4
,
G
r
a
p
e
v
i
n
e
,
T
X
7
6
0
5
1
㈰㈴⼱㈯㈷
12/27/2024
㈰㈴⼱㈯㈷
A2
A2
A2
A2
A2
240.18 sf
01/14/2025
Last Revision
Date
Project
No.
Approved
Checked
Drawn
REVISIONS
DateNo. Item
Amoi Group, LLC
RCP
PLAN
13012
08.21.2024
8750 N Central Expressway, STE 800
Dallas, Texas 75213 972. 908. 9558
I-200
1'
Provide 36” min in depth, and 30” min wide in front of the
electrical equipment. The work space shall be clear and shall
extend from the floor or platform to a height of 6’-6” or the height of
the equipment, whichever is greater.
NOTES:
1.
ISSUE FOR
PERMIT
RCP PLAN 1 1/4"= 1'
UNRED
380
2024/09/18
LEGEND- MECHANICAL
SUPPLY AIR GRILL
EXHAUST FAN
RETURN AIR GRILL
LEGEND- LIGHTING
Reflected Ceiling Legend
2' x 2 ' SUSPENDED CEILING
2' x 4' SUSPENDED CEILING
qty: 6
qty: 20
qty: 19
qty: 1
5w 120V
20w 120V 2'x2' LED FLAT LIGHT
10w 120V WALL SCONCE
60w 120V CHANDERLIER
13
'
-
9
"
8'
-
0
"
8'
-
0
"
13
'
-
3
"
10'-6"
0'-6"
9'-0"
10
'
-
0
"
6'-6"
10'-6"
19
'
-
0
"
14
'
-
0
"
22
'
-
3
"
22
'
-
9
"
10'-6"
7'
-
6
"
40
'
-
0
"
14
'
-
0
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
0'
-
6
"
14
'
-
0
"
4'-0"
26'-0"
4'
-
0
"
䙒低吠䑅卋䙏佔
73
'
-
0
"
10
'
-
0
"
坁午䕒
0'-3"
1'
-
0
"
TA
N
G
M
A
S
S
A
G
E
S
P
A
31
0
5
I
r
a
E
.
W
d
s
A
v
e
S
u
i
t
e
1
3
4
,
G
r
a
p
e
v
i
n
e
,
T
X
7
6
0
5
1
㈰㈴⼱㈯㈷
12/27/2024
㈰㈴⼱㈯㈷
2x2
SUSPENDED CEILING
10'-0" AFF
2x2 SUSPENDED CEILING
10'-0" AFF
2x2
SUSPENDED CEILING
10'-0" AFF 2x2
SUSPENDED CEILING
10'-0" AFF
2x2
SUSPENDED CEILING
10'-0" AFF
2x2 SUSPENDED CEILING
10'-0" AFF
2x2 SUSPENDED CEILING10'-0" AFF
2x2 SUSPENDED CEILING10'-0" AFF
2x4 SUSPENDED CEILING
10'-0" AFF
2x2 SUSPENDED CEILING
10'-0" AFF
2x4
SUSPENDED CEILING
10'-0" AFF
2x2
SUSPENDED CEILING9'-0" AFF
2x4
SUSPENDED CEILING
10'-0" AFF
2x2 SUSPENDED CEILING
10'-0" AFF
ROUND LIGHT20w 120V qty: 3
01/14/2025
Last Revision
Date
Project
No.
Approved
Checked
Drawn
REVISIONS
DateNo. Item
Amoi Group, LLC
Interior Details
13012
04.20.2024
8750 N Central Expressway, STE 800
Dallas, Texas 75213 972. 908. 9558
I-300
ISSUE FOR
PERMIT
NRED M
380
2024/09/18
TA
N
G
M
A
S
S
A
G
E
S
P
A
31
0
5
I
r
a
E
.
W
d
s
A
v
e
S
u
i
t
e
1
3
4
,
G
r
a
p
e
v
i
n
e
,
T
X
7
6
0
5
1
㈰㈴⼱㈯㈷
12/27/2024
㈰㈴⼱㈯㈷
01/14/2025
Last Revision
Date
Project
No.
Approved
Checked
Drawn
REVISIONS
DateNo. Item
Amoi Group, LLC
13012
04.20.2024
8750 N Central Expressway, STE 800
Dallas, Texas 75213 972. 908. 9558
I-400
ADA details
ISSUE FOR
PERMIT
UNRED M
380
2024/09/18
MAX
MIN 16"
MIN 7" MAX 9"
TA
N
G
M
A
S
S
A
G
E
S
P
A
31
0
5
I
r
a
E
.
W
d
s
A
v
e
S
u
i
t
e
1
3
4
,
G
r
a
p
e
v
i
n
e
,
T
X
7
6
0
5
1
㈰㈴⼱㈯㈷
12/27/2024
㈰㈴⼱㈯㈷
01/14/2025
Last Revision
Date
Project
No.
Approved
Checked
Drawn
REVISIONS
DateNo. Item
Amoi Group, LLC
13012
09.19.2024
8750 N Central Expressway, STE 800
Dallas, Texas 75213 972. 908. 9558
2x2 LAY IN SUPPLY DIFFUSER
GENERAL NOTES IN MECHANICAL:
1. ALL WORK SHALL CONFORM WITH THE MOST CURRENT EDITION
OF MECHANICAL CODE AND LOCAL CODE.
2. ALL THE DUCTWORK SHALL BE CONFORM TO S.M.A.C.N.A
STANDARDS.
3. SUPPLY AND RETURN AIR DUCTWORK TO BE OF RIGID SHEET
METAL CONSTRUCTION WRAPPED WITH 1 1/2" THICK INSULATION
EXCEPT FINAL CONNECTION INSULATED FLEXIBLE DUCT AT 5" MAX TO END.
4. FINAL CONNECTIONS TO ALL GRILLES,. REFISTERS AND DIFFUSERS
TO BE A MAXIMUM 6" INSULATED CEILING PLAN AND LIGHTING PLAN.
5. THE LOCATION OF ALL CEILING DIFFUSERS, GRILLES AND
REGISTERS SHALL BE COORDINATED WITH THE REFLECTED CIELING
PLAN AND LIGHTING PLAN.
6. THERMOSTAT SHALL HAVE 5 DEG. F DEADBAND, SETBACK TO 55
DEG. F(HEAT) AND 85 DEG. (COOL): 7 DAYS CLOCK, 2 HOUR
OCCUPANT OVERRIDE, I/O BACK UP.
7. PROVIDE MINIMUM R-8 INSULATION FOR SUPPLY AND RETURN AIR
DUCTS.
8. ALL JOINTS, LONGITUDINAL AND TRANSVERSER SEAMS, AND
CONNECTIONSIN DUCTWORK MUST BE SECURELY SEALED.
9.MECHANCIAL FASTENERS AND SEALS, MASTICS, OR GASKETS MUST
BE USED WHEN CONNECTING DUCTS TO FANS AND OTHER AIR
DISTRIBUTION EQUIPMENT.
10. CONTRACTOR SHALL PROVIDE THE OWNER A COPY OF
OPERATION AND MAINTENANCE MANUAL ON ALL MECHANICAL
EQUIPMENT.
11. EACH SUPPLY AIR DIFFUSER & RETURN GRILLES SHALL HAVE
ADJUSTABLE DAMPER FOR ITS OWN AIR BALANCE. MECHANCIAL
CONTRACTOR SHALL PROVIDE AIR BALANCE REPORT FOR EACH A/C
SYSTEM.
12. PROVIDE SUPPORTS FOR EACH EXHAUST FAN WITH VIBRATION
ISOLATORS TO STRUCTURE.
13. PROVIDE SMOKE DETECTORS IN SUPPLY & RETURN DUCTS OF
EACH ROOF TOP A/C UNIT.
14. BALANCING DAMPERS TO BE INSTALLED IN ALL BRANCH TAKE
OFFS. ALL DAMPERS TO HAVE LOCKING QUARANTS.
MECHANICAL FLOOR PLAN 1
M-100
HVAC Floor PlanRAGR RETURN GRILL
EXAUST FAN
ISSUE FOR
PERMIT
1/4"= 1'
UNRED
38
2024/09/18
13
'
-
9
"
8'
-
0
"
8'
-
0
"
13
'
-
3
"
10'-6"
0'-6"
9'-0"
10
'
-
0
"
6'-6"
10'-6"
19
'
-
0
"
14
'
-
0
"
22
'
-
3
"
22
'
-
9
"
10'-6"
7'
-
6
"
40
'
-
0
"
14
'
-
0
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
0'
-
6
"
14
'
-
0
"
4'-0"
26'-0"
4'
-
0
"
䙒低吠䑅卋䙏佔
73
'
-
0
"
10
'
-
0
"
坁午䕒
0'-3"
1'
-
0
"
GENERAL NOTES:
ㄮ⁐剏噉䑅⁁⁄啃吠卍佋䔠䑅呅䍔佒⁉丠呈䔠剅呕剎⁆佒⁕义呓⁏噅删㈰〰⁃䙍
KEY NOTES:
NOTES:
PROVIDE FIRE DAMPER WHEN AC IS MORE THAN 2000 CFM PER CODE. PROVIDE EXHAUST SYSTEM CAPABLE OF EXHAUSTING 70
CUBIC FEET OF AIR PER MINUTES FOR EACH WATER CLOSET INSTALLED IN THE RESTROOM. THIS SYSTEM SHALL BE CONNECTED
DIRECTLY TO THE OUTSIDE.
1.ALL AIR CONDITIONING FLEX DUCTWORK SHALL REQUIRE 6 INCHES SOLID METAL SADDLES AND 1INCH SOLID METAL
STRAPS TO SECURE DUCTWORK TO FRAMING. (COA POLICY)
2.FLEXIBLE AIR DUCT MATERIAL SHALL BE A MAXIMUM OF 10 FEET IN LENGTH. (IMC AMENDMENT SECTION 603.6.1.1)
01
200 cfm
EXISTING
10 tons
RTU
㠢
200 cfm
200 cfm
200 cfm
200 cfm
225 cfm
225 cfm
375 cfm
375 cfm
300 cfm
300 cfm
300 cfm
150 cfm
150 cfm
100 cfm
250 cfm
250 cfm
10"
12"
10"10"
㠢
㠢
14"
20"
20"
18"
14"
18"
14"
T
䕘䡁啓吠䙁丠千䡅䑕䱅
啎䥔⁎伮 䕆ⴱⰲ
EXISTING
EF-2
375 cfm
225 cfm
225 cfm
375 cfm
400 cfm 200 cfm
200 cfm
200 cfm
200 cfm
200 cfm
900 cfm
500 cfm
50 cfm
EXISTING
EF-1
50 cfm
PRIMARY A/C CONDENSATE LINES MUST ROUTE TO THE SANITARY SEWER SYSTEM. CONDENSATE DRAINS SHALL NOT
DISCHARGE INTO A PLUMBING FIXTURE OTHER THAN A FLOOR SINK, FLOOR DRAIN, TRENCH DRAIN, MOP SINK, HUB DRAIN,
STANDPIPE, UTILITY SINK OR LAUNDRY SINK. (IMC SECTION 314.1.1). SECONDARY CONDENSATE LINES MUST ROUTE TO A
CONSPICUOUS POINT OF DISPOSAL DISCHARGING TO A PLACE APPROVED BY AHJ, OR SYSTEMS ALLOWED BY IMC SECTION
307.2.3 (COD POLICY)
TO MOP SINK
TO MOP SINK
LEGEND- MECHANICAL
SUPPLY AIR GRILL
EXHAUST FAN
RETURN AIR GRILL
NO WORK IN
EXISTING
TOILET
REUSE EXISTING RTU AND EF,
REWORK ON DUCT WORK.
CONTRACTOR SHALL SITE VERIFY ALL
THE DUCTWORK FOR REUSE AND
INTERCEPTION WITH NEW DUCTWORK.
TA
N
G
M
A
S
S
A
G
E
S
P
A
31
0
5
I
r
a
E
.
W
d
s
A
v
e
S
u
i
t
e
1
3
4
,
G
r
a
p
e
v
i
n
e
,
T
X
7
6
0
5
1
㈰㈴⼱㈯㈷
12/27/2024
㈰㈴⼱㈯㈷
24"
gLast Revision
Date
Project
No.
Approved
Checked
Drawn
REVISIONS
DateNo. Item
Amoi Group, LLC
Plumbing Floor Plan
13012
09.19.2024
8750 N Central Expressway, STE 800
Dallas, Texas 75213 972. 908. 9558
KEY NOTES IN PLUMBING:
PROVIDE WATER SUPPLY LINE FROM BUILDING METER FIEILD VERIFY.
PROVIDE BACKFLOW PREVENTOR PER IPC.
GENERAL NOTES IN PLUMBING:
1. ALL THE PLUMBING WORKS AND MATERIALS ARE TO
CONFORM WITH PLUMBING CODE , LOCAL AND STATE CODES.
2. PLUMBING CONTRACTOR SHALL VERIFY AVAILABILITY WITH
LOCATIONS, SIZES OF SEWER, WATER AND GAS.
3. PLUMBING CONTRACTOR SHALL MAKE ARRANGEMENT WITH
THE UTILITY COMPANY FOR SERVICE AND CONNECTIONS, PAY
FOR THE ALL PERMITS, CONNECTION FEES, INSPECTION FEES
AND METER CHARGES.
4. SOIL AND WASTE PIPING SHALL SLOPE @ 2% MINIMUM.
5. ALL VENTS AND FLUES SHALL CLEAR OUTSIDE AIR INTAKES
OR OPENING BY MINIMUM OF 10'.
6. PLUMBING CONTRACTOR SHALL MAKE AND COMPLETE
ROUGH IN ALL FINAL CONNECTION TO EQUIPMENT PROVIDED
BY OTHERS REQUIRING PLUMBING CONNECTIONS.
7. PLUMBING CONTRACTOR SHALL PROVIDE FIXTURES,
FAUCETS, TRAPS, STOPS, GATE VALVES, GLOBE VALVES, GAS
COCKS, WATER HAMMER ARRESTERS, CLEANOUTS, INDIRECT
WASTE PIPING AND ALL NECESSARY TRIMS FOR A COMPLETE
PLUMBING SYSTEM.
8.INSULATE ALL HOT AND COLDE WATER LINES ABOVE GRADE
WITH 1" FIBERGLASS PIPE INSULATION WITH VAPOR BARRIER.
9. PROVIDE GAS SUPPLY LINE FROM GAS METER.
10. VERIFYALL FINAL CONNECTIONS TO EQUIPMENT WITH
EQUIPMENT SUPPLIER. VERIFY ROUGH-IN REQUIREMENTS
WITH SAME.
11. MATERIAL SHALL BE AS FOLLOW:
A: WATER PIPING TO BE PEX OR "K" COPPER BELOW GRADE,
TYPE "L" COPPER ABOVE GRADE.
B: WASTE PIPING TO BE CAST IRON OR PVC IF ACCEPTED BY
CITY.
C: VENTS TO BE CAST IRON OR PVC IF ACCEPTED BY CITY.
D:GAS PIPING TO BE SCHEDULE 40, BLACK STEEL PIPE.
PROVIDE GAS SHUT OFF VALVE TO EACH EQUIPMENT.
E: CONDENSATE DRAIN PIPING TO BE COPPER,
PROVIDE INSULATION FOR PIPING INSIDE BUILDING.
12. ALL INDIRECT WASTES EXCEEDING 24" IN LENGTH SHALL
BE TRAPPED.
13. PROVIDE CLEANOUTS REQUIRED, AND AT THE BASE OF ALL
STACKS.
14. ROUTE DRAIN LINES FROM HOT WATER HEATERS TO
NEARBY FLOOR SINK.
15. HANDICAP PLUMBING FIXTURES SHALL BE INSULATED IN
ACCORDANCE WITH THE ADA REQUIREMENTS & LOCAL STATE
BARRIER FREE REQUIREMENT.
16. PROVIDE 1" WATER SUPPLY LINE FROM BUILDING WATER.
PROVIDEWATER BACKFLOW PREVENTER PER CITY.
17. ALL CONDENSER LINES AND GAS LINES SHALL BE PROPERLY
SUPPORTED ON ROOF TOPS BY APPROVED SUPPORTS (WOOD
BLOCKS FOR SUPPORTS ARE NOT ALLOWED.) (COA POLICY)
P-100
PLUMBING 1
ISSUE FOR
PERMIT
SEWER PLAN 1 1
1/4"= 1'
UNRED
2024/09/
13
'
-
9
"
8'
-
0
"
8'
-
0
"
13
'
-
3
"
10'-6"
0'-6"
9'-0"
10
'
-
0
"
6'-6"
10'-6"
19
'
-
0
"
14
'
-
0
"
22
'
-
3
"
22
'
-
9
"
10'-6"
7'
-
6
"
40
'
-
0
"
14
'
-
0
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
0'
-
6
"
14
'
-
0
"
4'-0"
26'-0"
4'
-
0
"
䙒低吠䑅卋䙏佔
73
'
-
0
"
10
'
-
0
"
坁午䕒
0'-3"
1'
-
0
"
13
'
-
9
"
8'
-
0
"
8'
-
0
"
13
'
-
3
"
10'-6"
0'-6"
9'-0"
10
'
-
0
"
6'-6"
10'-6"
19
'
-
0
"
14
'
-
0
"
22
'
-
3
"
22
'
-
9
"
10'-6"
7'
-
6
"
40
'
-
0
"
14
'
-
0
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
0'
-
6
"
14
'
-
0
"
4'-0"
26'-0"
4'
-
0
"
䙒低吠䑅卋䙏佔
73
'
-
0
"
10
'
-
0
"
坁午䕒
0'-3"
1'
-
0
"
ALL THE FLOOR DRAIN REQUIRE TRAP PRIMERS
GENERAL NOTES:
CONTRACTOR SHALL SITE VERIFY EXISTING PLUMBING CONNECTIONS.
CW CW CW CW CW CW CW CW CW CW CW CW
ㄯ㈢
HW HW HW HW HW HW HW HW HW HW HW HW
EXTEND ALL THE ROOF VENT
ABOVE THE PARAPET WALL
PER HOA RE4UIREMENT
PLUMBING RISER DIAGRAM
PLUMBING PLAN 1 1/4"= 1'
圮䠮
CW
CW
CW
CW
CW
CW
HW
HW
HW
HW
HW
HWCW CW
TIE TO EXISTING
WATER SUPPL<
EXISTING WATER
SUPPL< PIPE HW
HW
HW
HW
HW
HW
CW
CW
CW
CW
CW
CW
NEW WATER
SUPPL< PIPE
1/2"
3/4"3/4"
1/2"
1/2"
久圠䍏䵍䕒䍉䅌⁇剁䑅
EXISTING
SHOWER
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS SS SS SS SS SS SS SS SS SS SS SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
EXISTING
SANITER< PIPE
SSSSSSSSSSSSSS
3"
3"
2"
3"VT VT VT
VTVT
EXISTING 4" S.S.
HW
HW
HW
HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW HW
呩攠瑯硩獴楮朠㈢
2" CW
2" VENT
2"
呯楬整猠砲
2" VENT
3"
䙬潯爠䑲慩渠砳
2"
WCO
噥湴⁴漠副潦
1/2"
HW
HW
HW HW HW
1/2"
1/2"
3" VENT
ShoZer
2" VENT
2"
Washer
2" VENT
2"
䵯戠卩湫
2" VENT
2"
1/2"
HW
HW
HW HW HW
1/2"
3/4"
HW
HW
HW HW HW
3/4"
1/2"
HW
HW
HW HW HW
1/2"
NU. FIXTURE (F.U.) FACTOR # SUB TOTAL REMARK
1 Lavatory 1.5 2 3
2 Mop Sinks 3 1 3
3 Toilets 1 2 2
4 Shower 1 1 1
5 Washer 1 1 1
NU. FIXTURE (F.U.) FACTOR # SUB TOTAL REMARK
1 Lavortory 1.5 2 3
2 Mop Sinks 3 1 3
3 Shower 1.5 1 1.5
4 Washer 2 1 2
NU. FIXTURE (F.U.) FACTOR # SUB TOTAL REMARK
1 Lavortory 1.5 2 3
2 Floor Drain 2 3 6
3 Toilets 3 2 6
4 Shower 2 1 2
5 Washer 2 1 2
6 Mob Sink 2 1 2
GC SHALL VERIFY EXISTING 1.5"
HW PROVIDED
TOTAL GPM 20
COLD WATER FIXTURE UNIT (F.U.)
10
12
TOTAL F.U.
GPM
GC SHALL VERIFY EXISTING 2"
CW PROVIDED
TOTAL F.U. 15
DRAINAGE FIXTURE UNIT (F.U.)
WATER HEATER CALCULATION
TOTAL F.U. 9.5
WATER HEATER GPM 11.5
GC SHALL VERIFY EXISTING 4"
SEWER LINE PROVIDED
䕘䥓呉乇
午佗䕒
SS
NO WORK IN
EXISTING
TOILET
Contractor shall site verify the existing water
heater for reuse, replace with new commercial
grade water heater if the existing one is in a
bad condition or not commercial grade.
GASGASGASGASGAS
GA
S
GC SHALL SITE VERIFY EXISTING
GAS PIPE SIZE, LOCATION AND
CONDITION FOR REUSE,
TIE TO EXISTING MAIN GAS PIPE
TA
N
G
M
A
S
S
A
G
E
S
P
A
31
0
5
I
r
a
E
.
W
d
s
A
v
e
S
u
i
t
e
1
3
4
,
G
r
a
p
e
v
i
n
e
,
T
X
7
6
0
5
1
㈰㈴⼱㈯㈷
12/27/2024
㈰㈴⼱㈯㈷
Last Revision
Date
Project
No.
Approved
Checked
Drawn
REVISIONS
DateNo. Item
Amoi Group, LLC
13012
04.20.2024
8750 N Central Expressway, STE 800
Dallas, Texas 75213 972. 908. 9558
OCCUPANT SENSOR CONTROL SHALL BE INSTALLED TO TURN OFF RECEPTACLES
WITHIN 20 MINUTES OF ALL OCCUPANTS LEAVING A SPACE PER 2021 IECC SECTION
C405.11.1.- 2.2
GENERAL NOTES IN POWER:
ALL OUTLETS AT KITCHEN, RESTROOM AND ANY WET AREA SHALL BE GFCI. THERE
MUST BE ABSOLUTELY NO EXPOSED ELECTRICAL CONDUIT ANYWHERE WITHIN THE
ESTABLISHMENT. ALL ELECTRICAL CONDUIT AND SERVICE MUST BE INSTALLED TO
BE CONCEALED WITHIN THE FINISH WALLS, AND PENTRATE ONLY AT THE POINT OF
CONNECTION TO THE EQUIPMENT THAT IT SERVES. ALL THE ABOVE CONDITIONS
APPLY TO ADN INCLUDE ALL POS LINES, FIRE ALARM, AND FIRE EXTINGUSHIER
CONDUIT INSTALLTION.
GENERAL NOTES IN LIGHTING:
FLEXIBLE CORDS FOR THE CONNECTION OF APPLIANCES SHOULD COMPLY WITH
LOCAL CODES. RECESSED LIGHTING AND HANGING PENDANT LIGHTING OVER THE
FRONT FOOD SERVICE AREA MUST BE ORDERED WITH FULL COVERAGE LENSES
INTEGRAL TO EACH FIXTURE.
PROVIDE LIGHTING CONTROL OCCUPANCY SENSOR INCORPORATE A MANUAL
CONTROL TO ALLOW OCCUPANTS TO TURN LIGHTS OFF 50% POWER BY BI-LEVEL
SWITCHES AND THE OTHER 50% MANUALLY BY OCCUPANTS AUTOMATIC ON TO
100% IS ONLY PERMITTED FOR CORRIDOR, LOBBIES AND OTHER EGRESS
FEATURES
AUTOMATICALLY TURN OFF ALL LIGHTS WITHIN 30 MINS OF ALL OCCUPANTS
LEAVING THE SPACE.
E-100
LEGEND- POWER
GROUND FAULT CIRCUIT INTERRUPTER
DUPLEX RECEPTACLE, SINGLE PHASE 110V
QUDRAPLEX RECEPTACLE, SINGLE PHASE 110V
RECEPTACLE, SINGLE PHASE 240V
SINGLE POLE TOGGLE SWITCH
JUNCTION BOX
DISCONNECT SWITCH
ELECTRICAL BOARD
FLOOR DRAINAGE
FLOOR SINK
DATA/ TELEPHONE OUTLET
ELECTRICAL
POWER PLAN
INTERIOR POWER FLOOR PLAN ROOF POWER FLOOR PLAN 1 2
ISSUE FOR
PERMIT
1/4"= 1' 1/4"= 1'
UNRED M
380
2024/09/18
19
'
-
0
"
14
'
-
0
"
22
'
-
3
"
22
'
-
9
"
40
'
-
0
"
14
'
-
0
"
14
'
-
0
"
26'-0"
4'
-
0
"
73
'
-
0
"
13
'
-
9
"
8'
-
0
"
8'
-
0
"
13
'
-
3
"
10'-6"
0'-6"
9'-0"
10
'
-
0
"
6'-6"
10'-6"
19
'
-
0
"
14
'
-
0
"
22
'
-
3
"
22
'
-
9
"
10'-6"
7'
-
6
"
40
'
-
0
"
14
'
-
0
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
0'
-
6
"
14
'
-
0
"
4'-0"
26'-0"
4'
-
0
"
䙒低吠䑅卋䙏佔
73
'
-
0
"
10
'
-
0
"
坁午䕒
0'-3"
1'
-
0
"
GENERAL NOTES:
Exam rooms, X-ray rooms, Treatment rooms, Operating rooms, Therapy areas, and Patient Care
spaces will require Redundant Grounding Methods for wiring Per NEC Article 517.13(A) (B).
NO WORK
ON ROOF
EXISTING
PANEL "A"
TO REUSE
GFCI
GF
C
I
GF
C
I
FOR MASSAGE SOFA
FOR MASSAGE SOFA
FOR MASSAGE SOFA
FOR MASSAGE SOFA
FOR WASHER
FOR DRYEREXISTING
PANEL "B"
TO REUSE
ROUND LIGHT
LEGEND- LIGHTING
20w 120V
5w 120V
20w 120V 2'x4' LED FLAT LIGHT
FOR LOGO
䄭〱
䄭〱
䄭〱
䄭〳
䄭〳
䄭〵
䄭〵
䄭〵
䄭〸
䄭〸
䄭
䄭
䄭ㄲ
䄭ㄴ
䄭ㄴ
䄭ㄶ 䄭ㄶ
䄭ㄶ
䄭ㄸ
䄭ㄸ
䄭ㄸ
䄭㈰
䄭㈴
䄭㈵
䄭〲
䄭〲
䄭〲䄭〴
䄭〴
䄭〶
䄭〵
䄭〷
䄭〹
䄭ㄱ
NO WORK IN
EXISTING
TOILET
䄭ㄲ
䄭ㄴ
䄭ㄲ
䄭
䄭
䄭〸
䄭ㄲ
䄭〸
䄭〸
䄭ㄸ
䄭ㄶ
䄭㈰ 䄭㈰
䄭㈲ 䄭㈲
䄭㈰
䄭㈲
䄭㈴ 䄭㈴
䄭㈲
䄭〳䄭〳
䄭㈴
䄭ㄴ 䄭ㄴ
䄭〵
GFCI
䄭〳
TA
N
G
M
A
S
S
A
G
E
S
P
A
31
0
5
I
r
a
E
.
W
d
s
A
v
e
S
u
i
t
e
1
3
4
,
G
r
a
p
e
v
i
n
e
,
T
X
7
6
0
5
1
㈰㈴⼱㈯㈷
12/27/2024
㈰㈴⼱㈯㈷
䄭〲
䄭〲
䄭〵
Last Revision
Date
Project
No.
Approved
Checked
Drawn
REVISIONS
DateNo. Item
Amoi Group, LLC
13012
04.20.2024
8750 N Central Expressway, STE 800
Dallas, Texas 75213
972. 908. 9558
E-200
ISSUE FOR
PERMIT
LI
LIGHTING PLAN 1 1
CLIGHTING PLAN
1/4"= 1'
UNRED
380
2024/09/18
LEGEND- LIGHTING
qty: 6
qty: 20
qty: 19
qty: 1
5w 120V
20w 120V 2'x2' LED FLAT LIGHT
10w 120V WALL SCONCE
60w 120V CHANDERLIER
ROUND LIGHT20w 120V
13
'
-
9
"
8'
-
0
"
8'
-
0
"
13
'
-
3
"
10'-6"
0'-6"
9'-0"
10
'
-
0
"
6'-6"
10'-6"
19
'
-
0
"
14
'
-
0
"
22
'
-
3
"
22
'
-
9
"
10'-6"
7'
-
6
"
40
'
-
0
"
14
'
-
0
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
7'
-
6
"
0'
-
6
"
14
'
-
0
"
4'-0"
26'-0"
4'
-
0
"
䙒低吠䑅卋䙏佔
73
'
-
0
"
10
'
-
0
"
坁午䕒
0'-3"
1'
-
0
"
䄭㈷
NO WORK IN
EXISTING
TOILET
ㄮ⁃低呒䅃呏删午䅌䰠卉呅⁖䕒䥆夠呈䔠䕘䥓呉乇⁌䥇䡔匠䱏䍁呉低⁁乄⁃低䑉呉低⁆佒
GENERAL NOTES:
䄭㌱
䄭㈹
䄭㌱
䄭㈹
䄭㌱
䄭㌱
䄭㈹
䄭㈹
䄭㌱
䄭㌱
䄭㌵
䄭㌵
䄭㌷
TA
N
G
M
A
S
S
A
G
E
S
P
A
31
0
5
I
r
a
E
.
W
d
s
A
v
e
S
u
i
t
e
1
3
4
,
G
r
a
p
e
v
i
n
e
,
T
X
7
6
0
5
1
㈰㈴⼱㈯㈷
12/27/2024
㈰㈴⼱㈯㈷
䄭㈷
䄭㈷
qty: 3
Last Revision
Date
Project
No.
Approved
Checked
Drawn
REVISIONS
DateNo. Item
Amoi Group, LLC
13012
09.19.2024
8750 N Central Expressway, STE 800
Dallas, Texas 75213 972. 908. 9558
E-300
Electrical
ELECTRICAL PANEL BOARD
ISSUE FOR
PERMIT
3#600KCMIL &
1#500KCMIL-G
(10) -4"(10) -4"4#600KCMIL &
1#500KCMIL-G 4000A
3#500KCMIL &
1#500KCMIL-G
(8) -4"(8) -4"4#500KCMIL &
1#600KCMIL-G 3200A
3#600KCMIL &
1#4/0G (4) -4"(4) -4"4#600KCMIL &
1#4/0G 1600A
3#600KCMIL &
1#3/0G (3) -4"(3) -4"4#600KCMIL &
1#3/0G 1200A
2000A4#600KCMIL &
1#250KCMIL-G (5) -4"(5) -4"3#600KCMIL &
1#250KCMIL-G
2500A4#600KCMIL &
1#350KCMIL-G (6) -4"(6) -4"
3000A4#500KCMIL &
1#500KCMIL-G (8) -4"(8) -4"
3#600KCMIL &
1#350KCMIL-G
3#500KCMIL &
1#2/0G (3) -4"(3) -4"4#500KCMIL &
1#2/0G 1000A
3#350KCMIL &
1#2/0G (3) -3"(3) -3"4#350KCMIL &
1#2/0G 900A
3#600KCMIL &
1#1/0G (2) -4"(2) -4"4#600KCMIL &
1#1/0G 800A
600A4#350KCMIL &
1#1G (2) -3"(2) -3"3#350KCMIL &
1#1G
700A4#500KCMIL &
1#1/0G (2) -4"(2) -4"3#500KCMIL &
1#1/0G
3#500KCMIL &
1#3G 4"4"4#500KCMIL &
1#3G 350A
3#350KCMIL &
1#4G 3"3"4#350KCMIL &
1#4G 300A
3#250KCMIL &
1#4G 3"3"4#250KCMIL &
1#4G 250A
400A4#600KCMIL &
1#3G 4"4"3#600KCMIL &
1#3G
450A4#4/0 & 1#2G (2) -3"(2) -3"3#4/0 & 1#2G
500A4#250KCMIL &
1#2G (2) -3"(2) -3"3#250KCMIL &
1#2G
3#4/0 & 1#4G 3"3"
4#4/0 & 1#4G
225A
3#3/0 & 1#6G 2"2"4#3/0 & 1#6G 200A
3#2/0 & 1#6G 2"2"4#2/0 & 1#6G 175A
3#4 & 1#10G 1"1 1/4"4#4 & 1#10G 60A
70A4#4 & 1#8G 1 1/4"1"3#4 & 1#8G
80A4#3 & 1#8G 1 1/4"1 1/4"3#3 & 1#8G
90A4#2 & 1#8G 1 1/2"1 1/4"3#2 & 1#8G
100A4#1 & 1#8G 2"2"3#1 & 1#8G
110A4#1 & 1#6G 2"2"3#1 & 1#6G
125A4#1 & 1#6G 2"2"3#1 & 1#6G
150A4#1/0 & 1#6G 2"2"3#1/0 & 1#6G
3#6 & 1#10G 1"1"4#6 & 1#10G 50A
3#6 & 1#10G 1"1"4#6 & 1#10G 45A
3#8 & 1#10G 3/4"3/4"4#8 & 1#10G 40A
3#8 & 1#10G 3/4"3/4"4#8 & 1#10G 35A
3#10 & 1#10G 3/4"4#10 & 1#10G 30A
3#10 & 1#10G 3/4"4#10 & 1#10G 25A
3#12 & 1#12G 4#12 & 1#12G 20A
15A
THREE PHASE OVERHEAD CIRCUIT SCHEDULE (COPPER)
3/4"
3/4"
3/4"
3/4"
3/4"
3#600KCMIL &
1#500KCMIL-G
4#600KCMIL &
2#350KCMIL-G 5000A
1
2
2/5
3
3/5
4
4/5
5
6
7
8
9
10
11
12
15
17
20
22
25
30
35
40
45
50
60
70
80
90
100
120
160
200
250
300
320
400
500
CONDUCTORS IN
EACH CONDUIT
3-PHASE, 4-WIRE
& GROUND
CONDUIT
SIZE
CIRCUIT OR
OVERCURRENT
RATING 3-POLE
CONDUIT
SIZE
CONDUCTORS IN
EACH CONDUIT
3-PHASE, 3-WIRE
& GROUND
CIRCUIT
SYMBOL
3#12 & 1#12G 4#12 & 1#12G3/4"
(12) -4"3#600KCMIL &
2#350KCMIL-G (12) -4"
UNRED M
380
2024/09/18
T HOMERUN T
T WIRING. WIR
EQUIRED
F
LOOR
OTHERWISE
One line
BRANCH CIRCUIT
BRANCH CIRCUIT
CONDUITS AS RE
WEATHERPROOF
ABOVE FINISH FL
COPPER
ALUMINUM
UNLESS NOTED NO
NOTE: CONTRACTOR SHALL CONFIRM CIRCUIT BREAKER SIZE & PHASE OF ALL THE EQUIPMENT WITH MANUFACTURER'S SPEC PRIOR TO INSTALLATION.
AUTHORITY HAVING JURISDIC
LIGHTED EXIT SIGN
EMERGENCY LIGHTING
FIRE EXTINGUISHER
NO CHANGE ON UPSTREAM
ELECTRICAL DISTRIBUTION 200A, 3 PH
㈰㠯ㄲざ
BRANCH CIRCUIT
BRANCH CIRCUIT
CONDUITS AS RE
WEATHERPROOF
ABOVE FINISH FL
COPPER
ALUMINUM
UNLESS NOTED UNO
M
200A, 3 PH
㈰㠯ㄲざ
LTS REC MECH MISC AMP POL AMP POL
LTS REC MECH MISC
1 250 20 1 A 20 1 540 EXISTING HOOD SYSTEM 2
3 540 20 1 B 20 1 540 EXISTING ICE CREAM DIPPER 4
5 540 20 1 C 20 1 540 EXISTING HOSTESS 6
7 360 20 1 A 20 1 540 EXISTING RECP 8
9 540 20 1 B 20 1 540 EXISTING SANDWICH PREP RECP 10
11 540 20 1 C 20 1 540 EXISTING SANDWICH PREP RECP 12
13 280 20 1 A 20 1 540 EXISTING SHAKE BLENDER 14
15 540 20 1 B 20 1 540 EXISTING SHAKE BLENDER 16
17 540 20 1 C 20 1 540 EXISTING BEER DISPENSER 18
19 280 20 1 A 20 1 540 EXISTING COOLER VAULT 20
21 540 20 1 B 20 1 540 EXISTING COOLER VAULT CU 22
23 400 20 1 C 20 1 200 NEW LIGHTS IN LOBBY 24
25 540 20 1 A 20 1 180 NEW FLOOR RECP.26
27 400 20 1 B 20 1 540 EXISTING BEER DISPENSER 28
29 300 20 1 C 20 1 540 EXISTING BACK BAR COOLER 30
31 500 20 1 A 20 1 540 EXISTING GLASS WASHER 32
33 380 20 1 B 20 1 540 EXISTING BEER DISPENSER 34
35 780 20 1 C 20 1 540 EXISTING PIZZA PREP REFRIG 36
37 95 20 1 A 20 1 540 EXISTING ICE CREAM DIPPER 38
39 95 20 1 B 20 1 540 EXISTING HOT WELL 40
41 800 20 1 C 20 1 200 NEW UTILITIES AROUND RESTROOM 42
0.0 8.4 0.0 0.0 0.0 10.1 0.0 0.2 SUBTOTAL CONNECTED KVA TOTAL
0.0 18.5 0.0 0.2 18.7
LTS REC MECH MISC SUBTOT SPARE
0.0 18.5 0.0 0.2 18.7
NEW RECP
NEW RECP
EXISTING RECP
NEW RECP FOR FRIDGE
EXISTING RECP
EXISTING RECP
NEW RECP FOR FRIDGE
NEW RECP FOR REACH IN FRIDGE
EXISTING RECP
NEW RECP FOR WATER BOILER
TOTAL PHASE C LOAD 3.9 5
TOTAL PHASE A LOAD 2.3 3
TOTAL PHASE B LOAD 3.0 4
TOTAL CONNECTED LOAD TOTAL CONNECTED
AMPACITY17.8 49
SUBTOTAL CONNECTED KVA
LOAD SUMMARY & FEEDER CALCULATION
EXISTING RECP
NEW RECP FOR REACH IN FRIDGE
EXISTING FOR WALK IN FREEZER
NEW RECP FOR RICE WAMER
NEW RECP FOR RICE WAMER
NEW RECP FOR FOOD PREP TABLE
REUSE RECP FOR REACH-IN REFRIG.
NEW RECO FOR GLASS FRIDGE
CKT
NO.
DESCRIPTION LOAD
(VA)
CIRCUIT
BREAKER
FOR IRON WOK RANGE
EXISTING RECP
EXISTING RECP
POLES: 42 WIRE: 4
LOAD
(VA)
INTERRUPTING RATING: 22 K
LOCATION: FILL IN LOCATION GROUND BUS: YES
DESCRIPTION CKT
NO
CIRCUIT
BREAKER
MOUNTING: SURFACE PHASE: 3 MAIN: MCB
PANELBOARD NO: B
ENGINEER:
SECTION: 1 OF 1 VOLTAGE: 208/120 BUS: 200A
LTS REC MECH MISC AMP POL AMP POL
LTS REC MECH MISC
1 720 20 1 A 20 1 900 FRONT DESK RECP 2
3 720 20 1 B 20 1 540 FOOT MASSAGE CONV. RECP 4
5 300 20 1 C 20 1 60 LOGO 6
7 300 20 1 A 20 1 900 MASSAGE ROOM RECP-1 8
9 300 20 1 B 20 1 720 MASSAGE ROOM RECP-2 10
11 300 20 1 C 20 1 720 MASSAGE ROOM RECP-3 12
13 800 A 20 1 900 MASSAGE ROOM RECP-4 14
15 800 B 20 1 720 MASSAGE ROOM RECP-5 16
17 800 C 20 1 720 MASSAGE ROOM RECP-6 18
19 1000 20 1 A 20 1 720 MASSAGE ROOM RECP-7 20
21 1300 20 1 B 20 1 720 MASSAGE ROOM RECP-8 22
23 1300 20 1 C 20 1 720 MASSAGE ROOM RECP-9 24
25 2000 20 1 A 20 1 720 HALL WAY RECP 26
27 140 20 1 B SPACE 28
29 300 20 1 C SPACE 30
31 340 20 1 A SPACE 32
33 50 20 1 B 20 1 100 EF-1 (V.I.F.)34
35 240 20 1 C 20 1 100 EF-2 (V.I.F.)36
37 40 20 1 A 3100 38
39 B 3100 40
41 C 3100 42
0.0 11.8 0.0 0.0 0.0 9.1 9.5 0.0 SUBTOTAL CONNECTED KVA TOTAL
0.0 20.8 9.5 0.0 30.3
LTS REC MECH MISC SUBTOT SPARE
0.0 20.8 9.5 0.0 30.3
TOTAL PHASE C LOAD 3.2 4
OFFICE RECP
OFFICE RECP
MASSAGE SOFA
MASSAGE SOFA
MASSAGE SOFA
TOTAL PHASE A LOAD 5.2 6
TOTAL PHASE B LOAD 3.3 4
MAIN: MCB
PANELBOARD NO: A
ENGINEER:
SECTION: 1 OF 1 VOLTAGE: 208/120 BUS: 200A
MOUNTING: SURFACE PHASE: 3
INTERRUPTING RATING: 22 K
LOCATION: FILL IN LOCATION GROUND BUS: YES
CKT
NO
CIRCUIT
BREAKER
LOAD
(VA)
DESCRIPTION
POLES: 42 WIRE: 4
EXISTING RTU (V.I.F.)40 3
CKT
NO.
DESCRIPTION LOAD
(VA)
CIRCUIT
BREAKER
WASHER
WATER HEATER
DRYER
CHANDERLIER
SPACE
SPACE
LOBBY LIGHT
MASSAGE ROOM LIGHT
LOAD SUMMARY & FEEDER CALCULATION
TOTAL CONNECTED LOAD TOTAL CONNECTED
AMPACITY
SUBTOTAL CONNECTED KVA
MASSAGE SOFA
EXISTING AIR COMPRESSOR(V.I.F.)20 3
28.8 80
STAFF & MASSAGE ROOM LIGHT
EXISTING TOILET LIGHT
HALL WAY LIGHT
TA
N
G
M
A
S
S
A
G
E
S
P
A
31
0
5
I
r
a
E
.
W
d
s
A
v
e
S
u
i
t
e
1
3
4
,
G
r
a
p
e
v
i
n
e
,
T
X
7
6
0
5
1
㈰㈴⼱㈯㈷
12/27/2024
㈰㈴⼱㈯㈷
COMcheck Software Version COMcheckWeb
Interior Lighting Compliance Certificate
Project Title:
2021 IECC
Project Type:Alteration
Construction Site:Owner/Agent:Designer/Contractor:
Project Information
Energy Code:
Project Title:
Data filename:
01/02/25Report date:
61 ofPage
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed
Watts
1-Massage Room (Healthcare Facility:Physical Therapy)846 0.91 770
2-Common Space Types:Office - Enclosed 196 0.74 145
3-Common Space Types:Lobby - General 352 0.84 296
4-Common Space Types:Corridor/Transition <8 ft wide 240 0.71 170
5-Common Space Types:Restrooms 138 0.63 87
1468Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixture
Massage Room (Healthcare Facility: Physical Therapy, 846 sq.ft.)
LED: 2x2 LED FLAT LIGHT: LED Panel 19W:1 9 20 180
LED: WALL SCONCE: LED A Lamp 11W:1 9 10 90
Common Space Types: Office - Enclosed (196 sq.ft.)
LED: 2x2 LED FLAT LIGHT: LED Panel 19W:2 1 20 20
Common Space Types: Lobby - General (352 sq.ft.)
LED: CHANDERLIER: Other:1 1 60 60
LED: 2x2 LED FLAT LIGHT: LED Panel 19W:2 1 20 20
LED: WALL SCONCE: LED A Lamp 11W:3 1 10 10
LED: ROUND DOWN LIGHT: LED A Lamp 25W:3 1 20 20
Common Space Types: Corridor/Transition <8 ft wide (240 sq.ft.)
LED: 2x2 LED FLAT LIGHT: LED Panel 19W:4 1 20 20
LED: WALL SCONCE: LED A Lamp 11W:7 1 10 10
Common Space Types: Restrooms (138 sq.ft.)
LED: 2x2 LED FLAT LIGHT: LED Panel 19W:1 2 20 40
470Total Proposed Watts =
Chris Jia
Amoi group
8750 N Central Expressway STE
800
ALLEN, Texas 75013
9729089558
chengjia@utexas.edu
3105 Ira E. Wds Ave Suite
134
Grapevine, TX 76051
Jiandong Lin
Tang Tai Health LLC
1229 Free stone ct
Fort Worth, TX 76179
linjiandong29@gmail.com
3
9
Interior Lighting Compliance
Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting
systems have been designed to meet the 2021 IECC requirements in COMcheck Version COMcheckWeb and to comply with any
applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES
Project Title:
Data filename:
01/02/25Report date:
62 ofPage
Chris Jia P.E 12/27/2024