PRELIMINARY REPORT OF
STRUCTURAL STEEL INSPECTION
Client: GTIS Acquisitions, LLC Date: 10/18/2024
PM: R YEOMAN
Project: 121 Commerce Center Addition (Lot 1) Project No: F241078
WO 1481756
Page No: 1 of 2
Service: Perform Structural Steel Inspection as detailed below:
Drawings Utilized: Structural
Locations and Items Inspected:
A representative of UES arrived on site to perform a Visual Structural Steel Inspection /Reinspection for
the above referenced project. Results of the inspection are as follows:
*Discrepancies, if any, are noted in BOLD
1) Welder Qualifications were reviewed for compliance AWS D1.1
2) Joist Girder to Column Welded Connections, Joist Girder to Panel Welded Connections and Joist to
Joist Girder Welded Connections - lines A to F & 19 to 13 – sheets S2.02 & S2.01
A) Re-inspected item 1(B) from report 1477185 referencing the joist to joist girder welded
connections. Reference details 211/S5.01 and 209/S5.01. Bolts were not installed in slotted holes in the
joist seats. Per the ERECTOR NOTE on joist drawing sheet J1.0, bolts are required in joist seats with
slotted holes. When bolts cannot be installed, or are removed, additional weld must be placed in slotted
holes. At reinspected locations - additional welds have been added at the joist seats as required. This
clears item 1(B) from report 1477185.
B) Joist girder to column welded connections in the lines 14 to 18 & B to E were inspected per
detail 209/S5.01. At inspected locations , the joist girder to column connections appeared to be per detail
and visually acceptable.
C) Joist girder to panel connections in lines 19 & B to E were inspected per detail 207/S5.01.
Inspected joist girder to panel embed appeared to be completed per detail and visually acceptable.
NOTE(1): The ¾”x6”x6” joist girder stabilizer plates – lines 19 & B to E were not installed at time
of inspection. See detail 207/S5.01
NOTE(2): The welding of the deck support angles in lines 19 & A to F, lines 19 to 13 & F and lines
A & 13 to 19 was incomplete at time of inspection. Work was in progress. See details 202/S5.01,
203/S5.01, 205/S5.01, 213/S5.01 and 214/S5.01.
CONTINUATION STRUCTURAL STEEL INSPECTION
Inspector’s Signature:
Client/Contractor Copied
Our test results and reports are for the exclusive use of the client (and their designated recipients on file in our office) and shall not be reproduced and/or distributed except with
express approval of ALPHA. The use of our name and test results must receive our written approval. Test results and reports apply only to the samples tested and/or
observed, and are not indicative of the qualities of apparently identical or similar specimens.
NOTE(3): The bridging terminations along line 19 were incomplete at time of inspection.
Reference New Millennium sheet J2.3 and detail 202/S5.01.
3) Precast Panel to Foundation Welded Connections – lines F to A & 1, lines A & 1 to 19, lines 19 & A
to F and lines F & 1 to 19 - sheets S1.01 & S1.02
*A) Connections were inspected /reinspected per details 103/S4.01 and 101/S4.01. Panel
P101 was missing a connection plate on one side . The pier embed is misaligned and this
connection will require an RFI. Panel 92 – lines 1&A – is missing (1) of (2) connections plates . It
was noted on 10/14/24 that the connections plates for panels P24, P23, P25 and P51 have been
spliced. The spliced connection plates at panel P23 have been addressed. The spliced
connections plates for panels P24, P25 and P51 still requir e corrective action. The non-compliant
welds for the connections plate at panel P3 have been repaired. The missing connections plates
for panel P11 and P12 (noted on report 1477185) have been added . See item 2(A) on report
1477185.
4) HSS(10”x10) Colum to Column Sleeve Welded Connections – lines 8 to 18 & A to F – sheets S1.01
and S1.02
A) Inspected connections in the referenced lines have been completed per the contract drawing
and details. Reference details 102/S4.01, 10/S0.04 and detail “A” on sheet AR102.
5) Joist To Precast Panel Welded Connections - lines A to F & 19 to 13 – sheets S2.02 & S2.01 – item
1(A) – item 1(A) – Report 1477185
A Along lines F & 18 to 13 – the joist to joist seat connections were inspected per detail 205/S5.01.
Reference erection detail 2/E3002. The inspected joists were not fully bearing on the joist seats at the
precast panel along line F. Gaps were visible. Pe r RFI #33 – “The reaction point of the joist is at the
vertical peg. If the required end anchorage welds can be achieved in that area of the seat, the gap
acceptable. Otherwise, a shim plate can be used if necessary.” RFI response is attached to this report.
*It was noted that bolts were not installed in slotted holes of the joist seats. Per the ERECTOR
NOTE on the joist drawing, bolts are required in joist seats with slotted holes. When bolts cannot
be installed, or are removed, additional weld must be placed in slotted holes. See attached detail.
6) Joist To Precast Panel Welded Connections – Panel P34 & P34 – sheets S2.02 & S2.01 – item1(C)
– item 1(C) – Report 1477185
*A) The joist seat to precast panel at panel joist connection at panels P35 & P34 – was
incomplete at time of inspection. The seat was not welded, and anchor bolts were not installed.
Slotted holes in the joist seat hit at the panel joint. See detail 206/S5.01.
CONTINUATION STRUCTURAL STEEL INSPECTION
Inspector’s Signature:
Client/Contractor Copied
Our test results and reports are for the exclusive use of the client (and their designated recipients on file in our office) and shall not be reproduced and/or distributed except with
express approval of ALPHA. The use of our name and test results must receive our written approval. Test results and reports apply only to the samples tested and/or
observed, and are not indicative of the qualities of apparently identical or similar specimens.
CONTINUATION STRUCTURAL STEEL INSPECTION