HomeMy WebLinkAboutCONCRETE PAVING - F241078-1455815,1455815 -10-30-2024Concrete Compression Test Report 5058 Brush Creek Rd Fort Worth, TX 76119 817-496-5600 UES Professional Solutions 44, LLC TBPELS #813 / TBPG #50341 FIELD DATA Placement Location:PAVING: AREA 5 ON WEST SIDE OF JOB SITE Project Desc:121 COMMERCE CENTER ADDITION (LOT 1) OFF GENESIS WAY AND ENCHANTED WAY Our Report #:F241078-1455815-S1 GTIS ACQUISITIONS, LLC 787 SEVENTH AVENUE, 50TH FLOOR NEW YORK, NY 10019 KYLE ROBERSONATTN: Date Placed:9/11/2024 Time Placed:8:45 AM 6 5 72 90 Date Received:N/A Concrete Supplier:HOLCIM Submitted By:Mendoza, Andrew Plant Number:955a Delivery Ticket No.:91491267 145.6 Batch Time:7:08:00 AM Tested For: Lab No.: Cure Type: Date Tested: Age (Days): Max Load: Area: Sq. In.PSI: Cap Spec: CYLINDER COMPRESSION TEST RESULTS (ASTM C-231) Avg. Length Avg. Width Avg Depth/ Diameter Cast By:UES Cured Specification:ASTM C-31 Mix ID:5409 Break Type: Sample Location:30'N 10'W OF NW CORNER BLDG 4 PM:RONNIE YEOMAN Date Issued:10/09/2024 Specified Strength:4000 Results Specification 3-5 2-6 N/A N/A N/A Air Content: Ambient Temp (F): Concrete Temp (F): Unit Weight: Slump (ASTM C-143): Weather: Wind: Drizzle Initial Curing Method:Protected Area, Covered with Lid Final Curing Method:Moist Room Truck Number:N/A 709 9/18/2024 7 3925012.56 3120LABC-1231 8.00 N/A 4.003 710 10/9/2024 28 5479012.56 4360LABC-1231 8.00 N/A 4.002 711 10/9/2024 28 5562012.56 4430LABC-1231 8.00 N/A 4.002 712 10/9/2024 28 5482012.56 4360LABC-1231 8.00 N/A 4.003 713 HOLD HOLD 012.56 0LABC-1231 8.00 N/A 4.00 Average 28-day Compressive Strength is compliant with project specifications CC: 4380 Respectfully Submitted By:__________________________________________________________ of UES Geotechnical Engineering * Construction Materials Testing * Environmental Engineering * Consulting 594234 Break Types: 1: Cone 2: Cone and Split 3: Columnar 4: Diagonal 5: Single Sided Fracture 6: Double Sided Fracture * = Specification out of spec Test Method: Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231, C173, C1064, C31, C1231 and C138. Compression strength tests per ASTM C39. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. This report shall not be reproduced except in full, without the prior written approval of UES. Page 1 of 2 Concrete Compression Test Report 5058 Brush Creek Rd Fort Worth, TX 76119 817-496-5600 UES Professional Solutions 44, LLC TBPELS #813 / TBPG #50341 FIELD DATA Placement Location:PAVING: AREA 5 ON WEST SIDE OF JOB SITE Project Desc:121 COMMERCE CENTER ADDITION (LOT 1) OFF GENESIS WAY AND ENCHANTED WAY Our Report #:F241078-1455815-S2 GTIS ACQUISITIONS, LLC 787 SEVENTH AVENUE, 50TH FLOOR NEW YORK, NY 10019 KYLE ROBERSONATTN: Date Placed:9/11/2024 Time Placed:10:15 AM 5.5 5 71 88 Date Received:N/A Concrete Supplier:HOLCIM Submitted By:Mendoza, Andrew Plant Number:955A Delivery Ticket No.:91651366 145.2 Batch Time:9:31:00 AM Tested For: Lab No.: Cure Type: Date Tested: Age (Days): Max Load: Area: Sq. In.PSI: Cap Spec: CYLINDER COMPRESSION TEST RESULTS (ASTM C-231) Avg. Length Avg. Width Avg Depth/ Diameter Cast By:UES Cured Specification:ASTM C-31 Mix ID:5409 Break Type: Sample Location:50'N 30'W OF NW CORNER OF BLDG 4 PM:RONNIE YEOMAN Date Issued:10/09/2024 Specified Strength:4000 Results Specification 3-5 2-6 N/A N/A N/A Air Content: Ambient Temp (F): Concrete Temp (F): Unit Weight: Slump (ASTM C-143): Weather: Wind: Drizzle Initial Curing Method:Protected Area, Covered with Lid Final Curing Method:Moist Room Truck Number:N/A 714 9/18/2024 7 4762012.56 3790LABC-1231 8.00 N/A 4.003 715 10/9/2024 28 5410012.56 4310LABC-1231 8.00 N/A 4.002 716 10/9/2024 28 5552012.56 4420LABC-1231 8.00 N/A 4.002 717 10/9/2024 28 5737012.56 4570LABC-1231 8.00 N/A 4.002 718 HOLD HOLD 012.56 0LABC-1231 8.00 N/A 4.00 Average 28-day Compressive Strength is compliant with project specifications CC: 4430 Respectfully Submitted By:__________________________________________________________ of UES Geotechnical Engineering * Construction Materials Testing * Environmental Engineering * Consulting 594241 Break Types: 1: Cone 2: Cone and Split 3: Columnar 4: Diagonal 5: Single Sided Fracture 6: Double Sided Fracture * = Specification out of spec Test Method: Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231, C173, C1064, C31, C1231 and C138. Compression strength tests per ASTM C39. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. This report shall not be reproduced except in full, without the prior written approval of UES. Page 2 of 2