HomeMy WebLinkAboutSFRA2025-0001547Foundation Report
Page 1 of 4
Adam A. Green, P.E. (TX), MBA
Austin | Dallas | Fort Worth | Houston |San Antonio | Waco (469) 751-7694
www.CrosstownEngineering.com
Date: April 24, 2025
Attention: Atlas Foundation Co., Inc. (via e-mail)
Subject: Structural Foundation Initial Inspection Report
3914 Meadow Dr., Grapevine, TX. 76051
To Whom It May Concern:
Crosstown Engineering (CE) was retained to conduct a review of the provided pier plan prepared by Atlas
Foundation Co., Inc. to determine if it is a reasonable limited plan of repair.
CE visited the subject site to interview the property owner, observe the structure and terrain, and to verify
the floor elevation data.
We observed brick cracks, drywall cracks, ceiling cracks, window separations, frieze board separations
and trim separations that indicated settlement was occurring on the right and front sides of the structure.
These observations are confirmed by floor elevation data.
Atlas Foundation Co., Inc. has proposed to perform the following in the approximate locations of the
structure as indicated on the limited repair plan to support the foundation:
x Obtained a ground penetrating radar scan to identify interior concrete beam within the slab.
x Install 25 total pilings (17 exterior, 8 breakouts).
The foundation repairs are to meet or exceed 2021 IRC. Based on our observations, it is our opinion that
the proposed plan of repair is reasonable. Because the structure has endured pre-repair foundation differ-
ential movement, residual differential elevation and perceptible floor slope may remain following the lim-
ited foundation repairs. This limited repair plan is intended to provide a reasonable repair to improve the
performance of the foundation and is not intended to level the foundation. The contractor shall determine
the amount of elevation correction needed based on the reaction of the structure during the lift in order to
minimize damages and additional stress.
Please see the Disclosure & Disclaimer, pier detail (if provided), and limited repair plan for more infor-
mation and do not hesitate to call us if you have any questions.
Sincerely,
Crosstown Land Development Services
Texas Engineering Firm (F-15944)
Adam Green, P.E. 4/24/25
Professional Engineer (TX #116597)
Foundation Report
Page 2 of 4
Adam A. Green, P.E. (TX), MBA
Austin | Dallas | Fort Worth | Houston |San Antonio | Waco (469) 751-7694
www.CrosstownEngineering.com
DISCLOSURE & DISCLAIMER
It is known to knowledgeable professional engineers that the soils in this area are subject to movement due to expan-
sion, contraction or densification of the soils etc. This soil movement could possibly cause the foundation to move
after the remediation plan within the attached report has been implemented and may impact the stability of the foun-
dation and cause damage.
NO WARRANTY IS EXPRESSED OR IMPLIED BY THIS ENGINEER AS TO THE PERFORMANCE OF THIS
FOUNDATION OR THE REPAIRS THERETO. Diligent foundation maintenance to maintain consistent soil con-
ditions along the perimeter should reduce further problems after the recommendations within this report have been
implemented. However, seasonal moisture variations, water leaks, erosion and other factors may affect the stability
of the foundation and put it in danger of further damage.
REPORT LIMITATIONS
This report is written for informational purposes only and is not intended to be a detailed technical evaluation of the
property or an inventory of defects. The opinions expressed in this report are based on a visual evaluation of current
conditions observed at the time of the inspection. THERE IS NO WARRANTY, EXPRESSED OR IMPLIED,
CONCERNING THIS ENGINEERING REPORT.
The information in this report supersedes any verbal comments, expressed or implied, made by Crosstown Land
Development Services or its principals, agents or employees. The client agrees that neither CLDS nor its employees
or owners will be responsible for:
1.Knowledge of the subsurface conditions without extensive geotechnical data obtained from onsite drilling and
testing of the recovered samples,
2.Knowledge of cracks, vertical differential displacement of floors without uncovering of the floor by the client;
and
3.Any other element such as joists or beams and other structural members that is boxed or otherwise not readily
available to CE for viewing, and releases CE from any liability attributable to such knowledge or conditions.
Any prescribed repair or maintenance plan detailed by this report is based on observations of apparent performance
of the facility at the time of this structural survey. Compliance with any code or specification other than as express-
ly noted is specifically excluded.
The provided Floor Elevation Map and resulting recommendations are based on conditions as they now exist and
DOES NOT IMPLY OR WARRANT THAT OTHER PROBLEMS AND OR AREAS MAY NOT MANIFEST IN
THE FUTURE.
This report was prepared expressly for the client and expressly for the purposes indicated by the client. Permission
for use by any other person for any purpose, or by the client for different purpose is denied unless otherwise stated
in writing by CE.
CE SHALL HAVE NO LIABILITY FOR ACTS OR OMISSIONS BY THE CONTRACTOR OR HIS SUBCON-
TRACTORS PERFORMING WORK ON THIS PROJECT, OR THE FAILURE OF THE CONTRACTOR TO
PERFORM THE WORK IN ACCORDANCE WITH THE REPAIR PLAN. CE IS NOT RESPONSIBLE FOR
THE CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCE OR PROCEDURES OR THE PRE-
CAUTIONS INCIDENTAL THERETO.
CE expressly DISCLAIMS ANY WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE and the client
expressly disclaims that it has contracted for or received any warranty of fitness for a particular purpose with respect
to this report. THE REPORT UNDER THIS AGREEMENT IS THE OPINION OF CE AND THERE ARE NO
WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS AGREEMENT.
VOID
AFTER
LIFT
FOUNDATION
STEEL SHIMS
CONCRETE CYLINDERS
CONCRETE OR STEEL CAP
W/ WELDED SLEEVE
STEEL CAP SHEET
2-7/8" OUTER STEEL PIPE
2-3/8" INNER STEEL PIPE
ST
E
E
L
P
I
P
E
S
H
A
L
L
B
E
P
R
E
S
S
E
D
T
O
R
E
F
U
S
A
L
SOIL
GROUT FILL
CYLINDERS PREFERRED
FRICTION PLATE
MI
N
I
M
U
M
3
0
0
0
P
S
I
CROSSTOWN ENGINEERING
FBPE FIRM F-15944 - WWW.CROSSTOWNENGINEERING.COM
(972)-533-9203 - DALLAS METROPLEX
STEEL PRESSED PILING DIAGRAM
FRONT VIEW SIDE VIEW
0($'2:'5*5$3(9,1(7;04/24/2025
LIKELY BEAM LOCATION,
COULD NOT CONFIRM WITH
SCAN
LEGEND
CONCRETE GRADE BEAM
WITHIN THE SLAB (TYP.)
GPR NOTES:
1)SLAB IS 5" THICK.
2)STEEL AT 36" APART.
3) BEAMS ARE 24"-28" WIDE AND 15"-18" THICK.
APPROXIMATE YEAR BUILT: 1986
FRONT
D/W
D/W
MONO-
LITHIC
FP
POOL
EQUIP-
MENT
POOL
NON-
MONOLITHIC
0.2
-0.1
-0.1
N/A
N/A
N/A
0.1
0.1
0.1
0.1
0.1
0.1 0.1
0.0 0.0
0.0
0.0
0.0
0.0
0.0
0.2
0.20.2 0.2
0.2
0.2
0.2
0.2
-0.3
-0.2
-1.1
-1.0
-0.5
-1.3
-1.7
-0.5
-0.5 -0.5
-0.1
-0.1 -0.1
-0.8 -2.0
-1.8
-2.8
-2.4
-1.6-1.0-1.4
-0.8-0.8
0.2
0.0
-0.2
-0.3
-0.4
28" WIDE
18" THICK
28" WIDE
18" THICK
24" WIDE
15" THICK
28" WIDE
15" THICK
CROSSTOWN ENGINEERING
TBPE FIRM F-15944 - WWW.CROSSTOWNENGINEERING.COM
(469)-751-7694 - DALLAS METROPLEX
3914 MEADOW DR., GRAPEVINE, TX. 76051
LIMITED REPAIR PLAN *NOT TO SCALE - ALL LOCATIONS APPROXIMATE*
PRE-LIFT ELEVATIONS BY CE (04.17.25) POST-LIFT ELEVATIONS BY CE (________)
LEGEND
ELEVATION BASEPOINT PROPOSED PAD/BLOCK EXISTING PIER
PROPOSED BEAM EXISTING PAD/BLOCK PROPOSED BREAKOUT PIER
EXISTING BEAM PROPOSED PIER EXISTING BREAKOUT PIER
0.0 (X.X)
x OBTAINED A GROUND PENETRATING RADAR SCAN TO IDENTIFY INTERIOR CONCRETE BEAM WITHIN THE
SLAB.
x INSTALL 25 TOTAL PILINGS (17 EXTERIOR, 8 BREAKOUTS).
CONSTRUCTION NOTE: IF INTERIOR
PILING LOCATIONS ARE SHOWN ON
THIS MAP THEY ARE APPROXIMATED
AND ARE LOCATED WITHOUT
KNOWLEDGE OF THE LOCATIONS OF
THE INTERIOR GRADE BEAMS. THE
CONTRACTOR SHALL MAKE FIELD
JUDGEMENTS BASED OFF OF THEIR
GRADE BEAM INVESTIGATIONS AND
OBSERVED SLAB QUALITIES TO FIELD
LOCATE THE FINAL INTERIOR PIER
LOCATIONS. FINAL SCOPE CHANGES
SHALL BE APPROVED BY THE ENGINEER
OF RECORD.
PLEASE NOTE: THIS DRAWING IS
PROVIDED FOR PRELIMINARY
PERMITTING AND CONSTRUCTION
PURPOSES ONLY. IF EXISTING PILINGS
ARE SHOWN ON THIS MAP, THEIR
LOCATION WAS PROVIDED BY THE
CLIENT AND IS APPROXIMATE. CE
DOES NOT CERTIFY THEIR
PERFORMANCE OR EXISTENCE. IF THE
READER WOULD LIKE TO DETERMINE
IF THEY ARE ACTUALLY PRESENT, THEY
MUST CONTACT THE OWNER OR
CONTRACTOR TO OBTAIN AN
ENGINEERING CERTIFICATE FOR THEM.
04.24.25