ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
PROJECT DATA GENERAL NOTES VICINITY MAP
SHEET INDEX
CODE REFERENCES
HOUSE PHOTO
COVER SHEET
PV-1
PHOTOVOLTAIC ROOF MOUNT SYSTEM
40 MODULES-ROOF MOUNTED - 17.800 KW DC, 17.600 KW AC
840 E TEXAS ST, GRAPEVINE, TX 76051
PROJECT
ADDRESS
840 E TEXAS ST, GRAPEVINE, TX
76051
OWNER:JAMES GRAVATT
DESIGNER:ESR
NEW SYSTEM:
17.800 KW DC ROOF MOUNT
SOLAR PV SYSTEM WITH
40 VSUN SOLAR VSUN445-144MH 445W
PV MODULES WITH
01 SOLAREDGE SE10000H-US (240V)
INVERTER AND
01 SOLAREDGE SE7600H-US (240V) INVERTER
40 SOLAREDGE S500 POWER OPTIMIZERS
AUTHORITIES HAVING JURISDICTION:
BUILDING: CITY OF GRAPEVINE
ZONING: CITY OF GRAPEVINE
UTILITY: ONCOR
PROJECT TO COMPLY WITH THE FOLLOWING:
2020 NATIONAL ELECTRICAL CODE (NEC)
2021 INTERNATIONAL RESIDENTIAL CODE (IRC)
2021 INTERNATIONAL BUILDING CODE (IBC)
2021 INTERNATIONAL FIRE CODE (IFC)
2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
1.ALL COMPONENTS ARE UL LISTED AND NEC CERTIFIED, WHERE WARRANTED.
2.THE SOLAR PV SYSTEM WILL BE INSTALLED IN ACCORDANCE WITH ARTICLE 690 OF THE NEC 2020.
3.THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM INSPECTED PRIOR TO PARALLEL
OPERATION.
4.ALL CONDUCTORS OF A CIRCUIT, INCLUDING THE EGC, MUST BE INSTALLED IN THE SAME RACEWAY, OR CABLE, OR
OTHERWISE RUN WITH THE PV ARRAY CIRCUIT CONDUCTORS WHEN THEY LEAVE THE VICINITY OF THE PV ARRAY.
5.WHERE METALLIC CONDUIT CONTAINING DC CONDUCTORS IS USED INSIDE THE BUILDING, IT SHALL BE IDENTIFIED AS
"CAUTION: SOLAR CIRCUIT" EVERY 10FT.
6.HEIGHT OF THE AC DISCONNECT SHALL NOT EXCEED 6'-7" PER NEC CODE 240.24.
7.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH NEC 2020 690.47 AND 250.50 THROUGH 60 AND 250-166 SHALL BE
PROVIDED. PER NEC GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED AND BONDED TO THE SERVICE
ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE OR INADEQUATE A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE USED
AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT. GROUND ROD WITH ACORN CLAMP. GROUNDING ELECTRODE
CONDUCTORS SHALL BE NO LESS THAN #8 AWG AND NO LARGER THAN #6 AWG COPPER AND BONDED TO THE EXISTING
GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM.
8.PHOTOVOLTAIC MODULES ARE TO BE CONSIDERED NON-COMBUSTIBLE.
9.PHOTOVOLTAIC INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS.
10.ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED AND LISTED FOR SUCH USE.
WIRING MUST BE PERMANENTLY AND COMPLETELY HELD OFF THE ROOF SURFACE.
11.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH THE LOCAL BUILDING CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV
RESISTANT. ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.
12.INVERTER(S) USED IN UNGROUNDED SYSTEM SHALL BE UL 1741 LISTED.
13.THE INSTALLATION OF EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTION SHALL BE PERFORMED ONLY BY
QUALIFIED PERSONS [NEC 690.4(C)]
14.ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED (OR BETTER), INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND
SWITCHES.
15.ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH NEC ARTICLE 250.
16.SYSTEM GROUNDING SHALL BE IN ACCORDANCE WITH NEC 690.41.
17.PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION IN ACCORDANCE WITH
NEC 690.12
18.DISCONNECTING MEANS SHALL BE LOCATED IN A VISIBLE, READILY ACCESSIBLE LOCATION WITHIN THE PV SYSTEM
EQUIPMENT OR A MAXIMUM OF 10 FEET AWAY FROM THE SYSTEM [NEC 690.13(A)]
19.ALL WIRING METHODS SHALL BE IN ACCORDANCE WITH NEC 690.31
20.WORK CLEARANCES AROUND ELECTRICAL EQUIPMENT WILL BE MAINTAINED PER NEC 110.26(A)(1), 110.26(A)(2) AND 110.26(A)(3).
21.ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED & IDENTIFIED IN ACCORDANCE WITH
UL1703
22.ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT EXPANSION JOINTS AND ANCHOR CONDUIT RUNS AS REQUIRED PER NEC.
23.IN ACCORDANCE WITH 2021 IFC 1205.5, 2018 IFC 1204.4, AND 2015 IFC 605.11.2 A CLEAR, BRUSH-FREE AREA OF 10 FEET(3048
MM) SHALL BE REQUIRED FOR GROUND-MOUNTED PHOTOVOLTAIC ARRAYS.
24. PANEL LAYOUT ORIENTATION IS SUBJECT TO CHANGE ON DESIGNED MOUNTING PLANES.
CONTRACTOR:CMS RENEWABLE LLC
2100 N HWY 360 #1004,
GRAND PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO:#35493
ELECTRICAL LICENSE NO: #213982
ESIID: # 10443720002327917
METER NO: # 145 851 046
PV-1 COVER SHEET
PV-2 SITE PLAN
PV-3 ROOF PLAN & MODULES
PV-4 ELECTRICAL PLAN
PV-5 STRUCTURAL DETAIL
PV-6 ELECTRICAL LINE DIAGRAM
PV-7 WIRING CALCULATIONS
PV-8 LABELS
PV-9 PLACARD
PV-10 OPTIMIZER CHART
PV-11+ EQUIPMENT SPECIFICATIONS
REPLACING DEFECTIVE EXISTING SYSTEM:
OLD SYSTEM:
10.440 KW DC ROOF MOUNT
SOLAR PV SYSTEM WITH
29 REC SOLAR: REC360AA BLACK 360W PV
MODULES WITH
01 SOLAREDGE SE10000H-US (240V)
INVERTER AND
29 SOLAREDGE S440 POWER OPTIMIZERS
SCOPE:
84'-7"
18
2
'
-
6
"
18
2
'
-
6
"
81'-9"
UM
MS
P
SL
C
IN
V
IN
V
AC
D
<10 FT.
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
PROJECT DESCRIPTION:
SITE PLAN
40 X VSUN SOLAR VSUN445-144MH 445W PV MODULES
ROOF MOUNTED SOLAR PHOTOVOLTAIC MODULES
DC SYSTEM SIZE: 40 x 445W = 17.800KW DC
AC SYSTEM SIZE: 01 x 10000W + 01 x 7600W = 17.600KW AC
PV-2
EQUIPMENT SUMMARY
40 VSUN SOLAR VSUN445-144MH 445W PV MODULES
01 SOLAREDGE SE10000H-US (240V) INVERTER
01 SOLAREDGE SE7600H-US (240V) INVERTER
40 SOLAREDGE S500 POWER OPTIMIZERS
1 SITE PLAN
SCALE: 1"=20'-0"PV-2
ROOF #3
(03) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
ROOF #1
(08) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
ROOF ARRAY AREA #1:- 190.24 SQ FT.
ROOF ARRAY AREA #2:- 166.46 SQ FT.
ROOF ARRAY AREA #3:- 71.34 SQ FT.
ROOF ARRAY AREA #4:- 95.12 SQ FT.
ROOF ARRAY AREA #5:- 166.46 SQ FT.
ROOF ARRAY AREA #6:- 214.02 SQ FT.
ROOF ARRAY AREA #7:- 47.56 SQ FT.
ROOF #4
(04) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
ROOF #2
(07) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
(N) SOLAREDGE SE10000H-US (240V) INVERTER
(E) UTILITY METER
(N) VISIBLE, LOCKABLE, LABELED
FUSED PV AC DISCONNECT
(E) MAIN SERVICE PANEL (OUTSIDE)
METER NO # 145 851 046
ESID # 10443720002327917
(E) GATE
- EXISTING PV MODULE
WHICH IS REMOVABLE
- NEW PV MODULE
PANEL LEGEND
EXISTING SYSTEM TO BE REMOVED
(29) REC SOLAR: REC360AA BLACK 360W
PV MODULES WITH SOLAREDGE S440
POWER OPTIMIZERS
NEW SYSTEM:
DC SYSTEM SIZE: 40 x 445 = 17.800 kW DC
AC SYSTEM SIZE: 01 x 10000W + 01 x 7600W = 17.600KW AC
(40) VSUN SOLAR VSUN445-144MH 445W PV MODULES WITH
(01) SOLAREDGE SE10000H-US (240V) INVERTER,
(01) SOLAREDGE SE76000H-US (240V) INVERTER
(40) SOLAREDGE S500 POWER OPTIMIZERS
REPLACING DEFECTIVE EXISTING SYSTEM:
OLD SYSTEM: 10.440 KW DC ROOF MOUNT
(29) REC SOLAR: REC360AA BLACK 360W PV MODULES
(01) SOLAREDGE SE10000H-US (240V) INVERTER
(29) SOLAREDGE S440 POWER OPTIMIZERS
(N) SOLAR LOAD CENTER
(E) TREES
(N) SOLAREDGE SE7600H-US (240V) INVERTER
PROPERTY LINE
PR
O
P
E
R
T
Y
L
I
N
E
PROPERTY LINE
PR
O
P
E
R
T
Y
L
I
N
E
E TEXAS ST
EXISTING
DRIVEWAY
1-STORY
HOUSE
ROOF #5
(07) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
ROOF #6
(09) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
ROOF #7
(02) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
(E) CHIMNEY (TYP.)
NOTE: VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED
ON ACCESSIBLE EXTERIOR WALL WITHIN 10' OF ONCOR METER
SOLAR MODULE SPECIFICATIONS
MANUFACTURER / MODEL #VSUN SOLAR VSUN445-144MH 445W MODULE
VMP 41.20V
IMP 10.81A
VOC 49.80V
ISC 11.42A
TEMP. COEFF. VOC -0.286%/°C
MODULE DIMENSION 82.99"L x 41.26"W x 1.38"D (In Inch)
INVERTER #1 SPECIFICATIONS
MANUFACTURER / MODEL #SOLAREDGE SE10000H-US
(240V) INVERTER
NOMINAL AC POWER 10.000KW
NOMINAL INPUT VOLTAGE 240 VAC
NOMINAL INPUT CURRENT 42A
INVERTER #2 SPECIFICATIONS
MANUFACTURER / MODEL #SOLAREDGE SE7600H-US
(240V) INVERTER
NOMINAL AC POWER 7.600KW
NOMINAL INPUT VOLTAGE 240 VAC
NOMINAL INPUT CURRENT 32A
(E) FENCE
MS
P
3'-0"
20'-10"8'-11"
3'-1"
17'-4"
7"
4'-0"
9'-4"29'-3"1'-3"
MODULE TYPE, DIMENSIONS & WEIGHT
SCALE: 3/32" = 1'-0"
ROOF PLAN AND
MODULES
NUMBER OF MODULES = 40 MODULES
MODULE TYPE = VSUN SOLAR VSUN445-144MH 445W PV MODULES
MODULE WEIGHT = 52.47 LBS / 23.8KG.
MODULE DIMENSIONS = 82.99" x 41.26" = 23.78 SF
VSUN SOLAR
VSUN445-144MH
445W MODULES
82
.
9
9
"
41.26"
PV-3
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
1 ROOF PLAN AND MODULES
PV-3 MSP - MAIN SERVICE PANEL
- VENT, ATTIC FAN
(ROOF OBSTRUCTION)
- ROOF ATTACHMENT
- RAFTER
LEGEND
ARRAY AREA & ROOF AREA CALC'S
TOTAL PV ARRAY
AREA
(SQ. FT.)
TOTAL ROOF
AREA
(Sq. Ft.)
ROOF
AREA COVERED BY
ARRAY (%)
951.20 3593.22 26
ROOF DESCRIPTION
ROOF TYPE ASPHALT SHINGLE
ROOF # OF
MODULES
ROOF
PITCH AZIMUTH RAFTER
SIZE
RAFTER
SPACING
#1 08 30°180°2"X8"24"
#2 07 30°90°2"X8"24"
#3 03 30°180°2"X8"24"
#4 04 30°270°2"X8"24"
#5 07 9°180°2"X8"24"
#6 09 30°180°2"X8"24"
#7 02 30°270°2"X8"24"
- EXISTING PV MODULE
WHICH IS REMOVABLE
- NEW PV MODULE
PANEL LEGEND
ROOF #3
(03) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
ROOF #1
(08) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
ROOF #4
(04) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
ROOF #2
(07) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
(N) IRONRIDGE XR 10 RAIL
(E) MAIN SERVICE PANEL (OUTSIDE)
(133) K2 SYSTEMS SPLICE FOOT XL ATTACHMENTS
18" FIRE SETBACK (TYP.)
EXISTING SYSTEM TO BE REMOVED
(29) REC SOLAR: REC360AA BLACK 360W
PV MODULES WITH SOLAREDGE S440
POWER OPTIMIZERS
ROOF #5
(07) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
ROOF #6
(09) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
ROOF #7
(02) VSUN SOLAR VSUN445-144MH
445W PV MODULES WITH SOLAREDGE
S500 POWER OPTIMIZERS
(E) CHIMNEY (TYP.)
ROOF #1
PITCH - 30°
AZIM. - 180°
ROOF #2
PITCH - 30°
AZIM. - 90°
ROOF #3
PITCH - 30°
AZIM. - 180°
ROOF #4
PITCH - 30°
AZIM. - 270°
ROOF #5
PITCH - 9°
AZIM. - 180°
ROOF #6
PITCH - 30°
AZIM. - 180°
18" FIRE SETBACK
36
"
F
I
R
E
S
E
T
B
A
C
K
1
8
"
F
I
R
E
S
E
T
B
A
C
K
1
8
"
F
I
R
E
S
E
T
B
A
C
K
18"
F
I
R
E
S
E
T
B
A
C
K
18"
F
I
R
E
S
E
T
B
A
C
K
18
"
F
I
R
E
S
E
T
B
A
C
K
18
"
F
I
R
E
S
E
T
B
A
C
K
1
8
"
F
I
R
E
S
E
T
B
A
C
K
1
8
"
F
I
R
E
S
E
T
B
A
C
K
18"
F
I
R
E
S
E
T
B
A
C
K
18"
F
I
R
E
S
E
T
B
A
C
K
18" FIRE SETBACK
36" FIRE SETBACK
36
"
F
I
R
E
S
E
T
B
A
C
K
NEW SYSTEM:
DC SYSTEM SIZE: 40 x 445 = 17.800 kW DC
AC SYSTEM SIZE: 01 x 10000W + 01 x 7600W = 17.600KW AC
(40) VSUN SOLAR VSUN445-144MH 445W PV MODULES WITH
(01) SOLAREDGE SE10000H-US (240V) INVERTER,
(01) SOLAREDGE SE76000H-US (240V) INVERTER AND
(40) SOLAREDGE S500 POWER OPTIMIZERS
REPLACING DEFECTIVE EXISTING SYSTEM:
OLD SYSTEM: 10.440 KW DC ROOF MOUNT
(29) REC SOLAR: REC360AA BLACK 360W PV MODULES
(01) SOLAREDGE SE10000H-US (240V) INVERTER
(29) SOLAREDGE S440 POWER OPTIMIZERS
ROOF #7
PITCH - 30°
AZIM. - 270°
18" FIRE SETBACK
18" FIRE SETBACK
36" FIRE SETBACK (TYP.)
UM
MS
P
SL
C
IN
V
IN
V
AC
D
<10 FT.
JB
JB
JB
JB
JB
JB
JB
SCALE: 3/32" = 1'-0"
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
PV-4
1 ELECTRICAL PLAN
PV-4
(N) JUNCTION BOX (TYP.)
UM
MSP
- UTILITY METER
- MAIN SERVICE PANEL
- CONDUIT
ACD - AC DISCONNECT
LEGEND
- JUNCTION BOXJB
- RAFTER
ELECTRICAL
PLAN
STRING #2
(8 MODULES)
STRING #1
(8 MODULES)
(N) CONDUIT
STRING #3
(8 MODULES)
BILL OF MATERIALS
EQUIPMENT QTY DESCRIPTION
SOLAR PV MODULES 40 VSUN SOLAR VSUN445-144MH 445W PV MODULES
INVERTER 1 SOLAREDGE SE10000H-US (240V) INVERTER
INVERTER 1 SOLAREDGE SE7600H-US (240V) INVERTER
POWER OPTIMIZERS 40 SOLAREDGE S500 POWER OPTIMIZERS
JUNCTION BOXES 07 JUNCTION BOXES
RAIL 28 IRONRIDGE XR 10 RAIL,168" SILVER
SPLICE 8 SPLICE KIT
MID MODULE CLAMPS 38 MID MODULE CLAMPS
END CLAMPS 84 END CLAMPS / STOPPER SLEEVE
ATTACHMENTS 133 K2 SYSTEMS SPLICE FOOT XL ATTACHMENTS
GROUND LUGS 21 GROUND LUGS
METER NO # 145 851 046
ESID # 10443720002327917
STRING #1/INV #1
STRING #2/INV #1
STRING #3/INV #1
STRING LEGENDS
(E) UTILITY METER
(N) VISIBLE, LOCKABLE, LABELED
FUSED PV AC DISCONNECT
(E) MAIN SERVICE PANEL (OUTSIDE)
- EXISTING PV MODULE
WHICH IS REMOVABLE
- NEW PV MODULE
PANEL LEGEND
STRING #4/INV #2
STRING #4
(8 MODULES)
(N) SOLAREDGE SE10000H-US (240V) INVERTER
(N) SOLAR LOAD CENTER
SLC - SOLAR LOAD CENTER
INV - INVERTER
(N) SOLAREDGE SE7600H-US (240V) INVERTER
NEW SYSTEM:
DC SYSTEM SIZE: 40 x 445 = 17.800 kW DC
AC SYSTEM SIZE: 01 x 10000W + 01 x 7600W = 17.600KW AC
(40) VSUN SOLAR VSUN445-144MH 445W PV MODULES WITH
(01) SOLAREDGE SE10000H-US (240V) INVERTER,
(01) SOLAREDGE SE76000H-US (240V) INVERTER AND
(40) SOLAREDGE S500 POWER OPTIMIZERSSTRING #5/INV #2
NOTE: VISIBLE, LOCKABLE, LABELED AC DISCONNECT LOCATED
ON ACCESSIBLE EXTERIOR WALL WITHIN 10' OF ONCOR METER
STRING #5
(8 MODULES)
EXISTING SYSTEM TO BE REMOVED
(29) REC SOLAR: REC360AA BLACK 360W
PV MODULES WITH SOLAREDGE S440
POWER OPTIMIZERS
E TEXAS ST
REPLACING DEFECTIVE EXISTING SYSTEM:
OLD SYSTEM: 10.440 KW DC ROOF MOUNT
(29) REC SOLAR: REC360AA BLACK 360W PV MODULES
(01) SOLAREDGE SE10000H-US (240V) INVERTER
(29) SOLAREDGE S440 POWER OPTIMIZERS(40) SOLAREDGE S500 POWER
OPTIMIZERS LOCATED UNDER
EACH MODULE
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
PV-5
STRUCTURAL
DETAIL
(2) 5/16"x3.5" SS LAG BOLT WITH MIN 2.5"
THREAD EMBEDMENT, SEALED
PENETRATION,K2 SYSTEMS- SPLICE FOOT XL,
ALUMN. "L" BRACKET W/3/8" SS BOLT & NUT
GROUNDING END/MID CLAMP
(N) IRONRIDGE XR10 RAIL
(E) ASPHALT SHINGLE ROOF
2"X8" RAFTER @ 24" O.C
(N) PV MODULE
(N) K2 SYSTEMS SPLICE FOOT XL
ATTACHMENTS
ATTACHMENT DETAIL (ENLARGED VIEW)
SCALE: NTSPV-5
2
1 STRUCTURAL ATTACHMENT (SIDE VIEW)
SCALE: N.T.SPV-5
(N) PV MODULE
SEE (2/PV-5) FOR
ENLARGED VIEW
(E) ASPHALT SHINGLE ROOF6
"
(N) BND T-BOLT & NUT 3/8"X1" SS
G
N
60A/2P
40A/2P
(N) SOLAR LOAD CENTER
240V, 1ɸ, 3W
125A RATED, NEMA 3R
L1
L2
N GL1L2
L1
L2
N
G
4
=
DC
SOLAREDGE TECHNOLOGIES LTD.
SE10000H-US (240V) INPUT: 240 VAC, 42A
99% CEC WEIGHTED EFFICIENCY
NEMA 3R, UL LISTED, INTERNAL GFDI
WITH INTEGRATED DC DISCONNECT
AC
-+
-++
-+
+++---
2
-+
-
1 3
=
=
=
=
=
=
=
=
=
=
-+
-++
-+
+++---
2
-+
-
1 3
=
=
=
=
=
=
=
=
=
=
1
STRING #4
STRING #5
SOLAREDGE POWER OPTIMIZERS S500 RATED
DC INPUT POWER - 500 WATTS
MAXIMUM INPUT VOLTAGE - 60 VDC
MPPT RANGE - 8 TO 60 VDC
MAXIMUM SHORT CIRCUIT CURRENT - 15 ADC
MAXIMUM OUTPUT CURRENT - 15 ADC
STRING LIMITATIONS - 8 TO 25 OPTIMIZERS,
5700 WATTS STC PER STRING MAXIMUM
(16) VSUN SOLAR VSUN445-144MH
445W PV MODULES
7 8
7 8
=
DC
SOLAREDGE TECHNOLOGIES LTD.
SE7600H-US (240V) OUTPUT: 240 VAC, 32A
99% CEC WEIGHTED EFFICIENCY
NEMA 3R, UL LISTED, INTERNAL GFDI
WITH INTEGRATED DC DISCONNECT
AC
JUNCTION BOX
600V, NEMA 3R,
UL LISTED
2
G
+
-
+
-
-+-+
-+-+
3A
3
N
G
INVERTER #1
INVERTER #2
LOAD
LINE
GN
100A
Fuses
FUSED PV AC
DISCONNECT
240V, 1ɸ, 3W
100A RATED
NEMA 3R
-+
-++
-+
+++---
2
-+
-
1 3
=
=
=
=
=
=
=
=
=
=
-+
-++
-+
+++---
2
-+
-
1 3
=
=
=
=
=
=
=
=
=
=
-+
-++
-+
+++---
2
-+
-
1 3
=
=
=
=
=
=
=
=
=
=
1
STRING #1
STRING #2
STRING #3
7 8
(24) VSUN SOLAR VSUN445-144MH 445W PV
MODULES
7 8
7 8
JUNCTION BOX
600V, NEMA 3R,
UL LISTED
2
G
+
-
+
-
+
-
-+-+
-+-+
-+-+
SOLAREDGE POWER OPTIMIZERS S500 RATED
DC INPUT POWER - 500 WATTS
MAXIMUM INPUT VOLTAGE - 60 VDC
MPPT RANGE - 8 TO 60 VDC
MAXIMUM SHORT CIRCUIT CURRENT - 15 ADC
MAXIMUM OUTPUT CURRENT - 15 ADC
STRING LIMITATIONS - 8 TO 25 OPTIMIZERS,
5700 WATTS STC PER STRING MAXIMUM
VISIBLE, LOCKABLE,
LABELED AC DISCONNECT
LOCATED ON ACCESSIBLE
EXTERIOR WALL WITHIN 10' OF
ONCOR METER
(N) #6 BARE CU VIA
IRREVERSIBLE CRIMP TO
EXISTING GROUNDING
ELECTRODE SYSTEM
L1
L2
5
N
SUPPLY SIDE CONNECTION
REF 2020 NEC 705.11(D), 230.46 AND IN
ACCORDANCE WITH 110.14,
300.5(E),300.13 AND 300.15
M
BI-DIRECTIONAL
UTILITY METER
1ɸ, 3-W, 120/240V
METER NO # 145 851 046
(ONCOR UTILITY)
NL2L1
TO UTILITY GRID
LINE
LOAD
LINE SIDE
INTERCONNECTION
AT MAIN PANEL
PER ART. 705.11,
230.82(6)
G
N
G
N
GEC
200A/2P
(E) MAIN SERVICE
PANEL,
200A RATED, 240V
EXISTING GROUNDING
ELECTRODE SYSTEM TO EARTH
REF. NEC 250.52, 250.53(A)
(SEE GROUNDING & GENERAL
NOTES #8 & 9)
(E) MAIN BREAKER TO
HOUSE 240V, 200A/2P
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
SCALE: NTS PV-6
DC SYSTEM SIZE: 40 x 445W = 17.800KW DC
AC SYSTEM SIZE: 01 x 10000W + 01 x 7600W = 17.600KW AC
(40) VSUN SOLAR VSUN445-144MH 445W PV MODULES WITH
(01) SOLAREDGE SE10000H-US (240V) INVERTER,
(01) SOLAREDGE SE7600H-US (240V) INVERTER AND
(40) SOLAREDGE S500 POWER OPTIMIZERS ARE
LOCATED UNDER EACH MODULE
(05) STRINGS OF 08 MODULES ARE CONNECTED IN SERIES
1 ELECTRICAL LINE DIAGRAM
PV-6
ELECTRICAL LINE
DIAGRAM
METER NO # 145 851 046
ESID # 10443720002327917
QTY CONDUCTOR INFORMATION CONDUIT TYPE CONDUIT
SIZE
(10)CU#10AWG -
N/A N/A(1)1 CU #6AWG -BARE COPPER IN FREE AIR
PV WIRE (POSITIVE & NEGATIVE)
(10)CU#10AWG -
EMT, LFMC OR PVC 3/4"(1)2 CU#10AWG -THWN-2 GND
THWN-2 (+, -) (EXTERIOR)
(3)
(1)THWN-2 OR THHN GND
THWN-2 OR THHN L1, L2 & NCU #3AWG -
CU #6AWG -4 1"EMT, LFMC OR PVC
(2)
(1)
CU #3AWG -
CU #3AWG -
1"EMT, LFMC OR PVC5
(3)
(1)THWN-2 OR THHN GND
THWN-2 OR THHN L1, L2 & NCU #8AWG -
CU #10AWG -
3A EMT, LFMC OR PVC
(3)
(1)THWN-2 OR THHN GND
THWN-2 OR THHN L1, L2 & NCU #6AWG -
CU #10AWG -
3 EMT, LFMC OR PVC 3/4"
3/4"
THWN-2 OR THHN N
THWN-2 OR THHN L1 & L2
INTERCONNECTION NOTES:
1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE
DETERMINED IN ACCORDANCE WITH [NEC 705.12], AND [NEC 690.59].
2. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9],
[NEC 230.95].
3. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING.
4. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE
BUSBAR RELATIVE TO THE MAIN BREAKER.
DISCONNECT NOTES:
1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN
THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE
CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY
THE UPPER TERMINALS)
2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY
PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH
3. DISCONNECT MEANS AND THEIR LOCATION SHALL BE IN
ACCORDANCE WITH [NEC 225.31] AND [NEC 225.32].
GROUNDING & GENERAL NOTES:
1. GROUNDING ELECTRODES AND GROUNDING ELECTRODE CONDUCTORS.
ADDITIONAL GROUNDING ELECTRODES SHALL BE PERMITTED TO BE
INSTALLED IN ACCORDANCE WITH 250.52 AND 250.54.GROUNDING ELECTRODES
SHALL BE PERMITTED TO BE CONNECTED DIRECTLY TO THE PV MODULE
FRAME(S) OR SUPPORT STRUCTURE PER [NEC 690.47(B)]
2. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE.
3. DC GEC AND AC EGC TO REMAIN UNSPLICED, OR SPLICED TO EXISTING
ELECTRODE
4. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS
FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL
INSPECTION.
5. JUNCTION BOXES QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE
FIELD - JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE
TYPE TRANSITIONS.
6. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER
AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT.
7. RACEWAYS AND CABLES EXPOSED TO SUNLIGHT ON ROOFTOPS SHOULD BE
INSTALLED MORE THAN 7/8" ABOVE THE ROOF USING CONDUIT SUPPORTS.
8. ALL NEW SERVICE INSTALLATIONS AND REPLACEMENTS REQUIRE A
SURGE-PROTECTIVE DEVICE (SPD) IN ACCORDANCE WITH [NEC 230.67]. THE
SPD SHALL BE TYPE 1 OR TYPE 2 AND IS REQUIRED TO BE AN INTEGRAL PART OF
THE SERVICE EQUIPMENT OR LOCATED IMMEDIATELY ADJACENT THERETO.
RACKING NOTE:
1.BOND EVERY OTHER RAIL WITH #6 BARE COPPER
REPLACING DEFECTIVE EXISTING SYSTEM:
OLD SYSTEM: 10.440 KW DC ROOF MOUNT
(29) REC SOLAR: REC360AA BLACK 360W PV MODULES
(01) SOLAREDGE SE10000H-US (240V) INVERTER
(29) SOLAREDGE S440 POWER OPTIMIZERS
SOLAR MODULE SPECIFICATIONS
MANUFACTURER / MODEL #VSUN SOLAR VSUN445-144MH 445W MODULE
VMP 41.20V
IMP 10.81A
VOC 49.80V
ISC 11.42A
TEMP. COEFF. VOC -0.286%/°C
MODULE DIMENSION 82.99"L x 41.26"W x 1.38"D (In Inch)
INVERTER #1 SPECIFICATIONS
MANUFACTURER / MODEL #SOLAREDGE SE10000H-US
(240V) INVERTER
NOMINAL AC POWER 10.000KW
NOMINAL INPUT VOLTAGE 240 VAC
NOMINAL INPUT CURRENT 42A
INVERTER #2 SPECIFICATIONS
MANUFACTURER / MODEL #SOLAREDGE SE7600H-US
(240V) INVERTER
NOMINAL AC POWER 7.600KW
NOMINAL INPUT VOLTAGE 240 VAC
NOMINAL INPUT CURRENT 32A
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
PV-7
PERCENT OF
VALUES
NUMBER OF CURRENT
CARRYING CONDUCTORS IN EMT
.80 4-6
.70 7-9
.50 10-20
SOLAR MODULE SPECIFICATIONS
MANUFACTURER / MODEL #VSUN SOLAR VSUN445-144MH 445W MODULE
VMP 41.20V
IMP 10.81A
VOC 49.80V
ISC 11.42A
TEMP. COEFF. VOC -0.286%/°C
MODULE DIMENSION 82.99"L x 41.26"W x 1.38"D (In Inch)
AMBIENT TEMPERATURE SPECS
RECORD LOW TEMP -8°C
AMBIENT TEMP (HIGH TEMP 2%)40°C
MODULE TEMPERATURE COEFFICIENT OF Voc -0.286%/°C
WIRING
CALCULATIONS
ELECTRICAL NOTES
1.ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION.
2.ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT.
3.WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE RINED DIRECTLY TO, AND LOCATED AS CLOSE AS
POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.
4.WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.
5.DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY INLETS,
SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS.
6.WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM
ACCORDINGLY.
7.ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE.
8.MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE
GROUNDING CLIP MANUFACTURER'S INSTRUCTION.
9.MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.
10.TEMPERATURE RATINGS OF ALL CONDUCTORS, TERMINATIONS, BREAKERS, OR OTHER DEVICES ASSOCIATED WITH THE
SOLAR PV SYSTEM SHALL BE RATED FOR AT LEAST 75 DEGREE C.
11.CONDUIT INSTALLED AT MINIMUM DISTANCE OF 7/8 INCHES ABOVE ROOF .....NEC 310.15(B)(3)(C)
INVERTER #1 SPECIFICATIONS
MANUFACTURER / MODEL #SOLAREDGE SE10000H-US
(240V) INVERTER
NOMINAL AC POWER 10.000KW
NOMINAL INPUT VOLTAGE 240 VAC
NOMINAL INPUT CURRENT 42A
INVERTER #2 SPECIFICATIONS
MANUFACTURER / MODEL #SOLAREDGE SE7600H-US
(240V) INVERTER
NOMINAL AC POWER 7.600KW
NOMINAL INPUT VOLTAGE 240 VAC
NOMINAL INPUT CURRENT 32A
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
LABELS
PV-8
480 V
27.00 A
MAXIMUM VOLTAGE
MAXIMUM CIRCUIT CURRENT
MAXIMUM RATED INPUT
CURRENT OF THE CHARGE
CONTROLLER OR DC-TO-DC
CONVERTER (IF INSTALLED)
LABEL LOCATION:
INVERTER
CODE REF: NEC 690.7(D)
LABEL- 11:
TERMINALS ON THE LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION
WARNING!
ELECTRICAL SHOCK HAZARD
!WARNING DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
LABEL LOCATION:
PRODUCTION METER
UTILITY METER
MAIN SERVICE PANEL
SUBPANEL
CODE REF: NEC 705.30(C) & NEC 690.59
LABEL- 2:
TURN OFF PHOTOVOLTAIC AC
DISCONNECT PRIOR TO
WORKING INSIDE PANEL
WARNING!
LABEL LOCATION:
MAIN SERVICE PANEL
SUBPANEL
MAIN SERVICE DISCONNECT
COMBINER
CODE REF: NEC 110.27(C) & OSHA 1910.145 (f) (7)
LABEL- 3:
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRIC
PV PANELS
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
PHOTOVOLTAIC
AC DISCONNECT
LABEL LOCATION:
AC DISCONNECT
CODE REF: NEC 690.13(B)
LABEL- 7:
PHOTOVOLTAIC
AC DISCONNECT
NOMINAL OPERATING AC VOLATGE 240 V
WARNING
POWER SOURCE INPUT
CONNECTION. DO NOT
RELOCATE THIS
OVERCURRENT DEVICE
!
MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT
LABEL LOCATION:
MAIN SERVICE DISCONNECT (ONLY IF MAIN SERVICE
DISCONNECT IS PRESENT)
CODE REF: NEC 690.13(B)
LABEL- 9:
RATED AC INPUT CURRENT
LABEL LOCATION:
AC DISCONNECT
COMBINER
MAIN SERVICE PANEL
SUBPANEL
MAIN SERVICE DISCONNECT
CODE REF: NEC 705.20(7) and NEC 690.13(B)
LABEL- 1:
LABEL LOCATION:
MAIN SERVICE PANEL (ONLY IF SOLAR IS BACK-FED)
SUBPANEL (ONLY IF SOLAR IS BACK-FED)
CODE REF: NEC 705.12 (B)(2)
LABEL- 4:
LABEL LOCATION:
MAIN SERVICE PANEL
CODE REF: IFC 605.11.3.1(1) & 690.12(D)
LABEL- 5:
LABEL LOCATION:
AC DISCONNECT
CODE REF: NEC 690.12(D)(2)
LABEL- 6:
LABEL- 8:
LABEL LOCATION:
MAIN SERVICE PANEL
SUBPANEL
AC DISCONNECT
CODE REF: NEC 690.13(B)
74.00 A
INVERTER #1
AC DISCONNECT
NOMINAL OPERATING AC VOLATGE 240 V
RATED AC INPUT CURRENT
LABEL- 10:
LABEL LOCATION:
MAIN SERVICE PANEL
SUBPANEL
AC DISCONNECT
CODE REF: NEC 690.13(B)
42.00 A
INVERTER #2
AC DISCONNECT
NOMINAL OPERATING AC VOLATGE 240 V
RATED AC INPUT CURRENT
LABEL- 12:
LABEL LOCATION:
MAIN SERVICE PANEL
SUBPANEL
AC DISCONNECT
CODE REF: NEC 690.13(B)
32.00 A
480 V
20.00 A
MAXIMUM VOLTAGE
MAXIMUM CIRCUIT CURRENT
MAXIMUM RATED INPUT
CURRENT OF THE CHARGE
CONTROLLER OR DC-TO-DC
CONVERTER (IF INSTALLED)
LABEL LOCATION:
INVERTER
CODE REF: NEC 690.7(D)
LABEL- 13:
CAUTION
POWER TO THIS SERVICE IS
ALSO SUPPLIED FROM ON-SITE
SOLAR/WIND GENERATION
AC SYSTEM DISCONNECT
LABEL LOCATION:
AC DISCONNECT
LABEL-14:
CAUTION
ALTERNATIVE POWER SUPPLY
AC SYSTEM DISCONNECT
LABEL LOCATION:
AC DISCONNECT
LABEL-15:
UM
MS
P
SL
C
IN
V
IN
V
AC
D
JB
JB
JB
JB
JB
JB
JB
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
PLACARD
PV-9
JUNCTION BOX (TYP.)
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE
SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM.
(ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS INLINED WITHIN:
NEC 690.56(B)&(C), [NEC 705.10])
LABELING NOTES:
1. LABELS CALLED IN ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE EXACT
REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS.
2. LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRIC CODE, OSHA STANDARD 19010.145, ANSI Z535.
3. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC 110.21]
5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLY
AFFIXED [IFC 605.11.1.1]
NEW PV ARRAY
SOLAREDGE SE10000H-US
(240V) INVERTER
UTILITY METER
PV AC DISCONNECT
MAIN SERVICE PANEL
(OUTSIDE)
EXISTING PV ARRAY (TO BE REMOVED)
SOLAR LOAD CENTER
SOLAREDGE SE7600H-US
(240V) INVERTER
840 E TEXAS ST, GRAPEVINE, TX 76051
MULTIPLE SOURCES OF POWER
CAUTION:
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
OPTIMIZER
PV-10
11
12
13
14
15
16
17
18
19
20
1-20
2
3
4
21-40 41-60
5
6
7
8
9
10
1
11
12
13
14
15
16
17
18
19
20
OPTIMIZER CHART
CHART
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
MODULE
DATASHEET
PV-11
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
INVERTER
DATASHEET
PV-12
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
INVERTER
CERTIFICATION
PV-13
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
OPTIMIZER
DATASHEET
PV-14
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
DATASHEET
PV-15
ATTACHMENT
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
DATASHEET
PV-16
RACKING
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
DATASHEET
PV-17
RACKING
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
DATASHEET
PV-18
RACKING
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
JA
M
E
S
G
R
A
V
A
T
T
RE
S
I
D
E
N
C
E
84
0
E
T
E
X
A
S
S
T
,
GR
A
P
E
V
I
N
E
,
TX
7
6
0
5
1
ANSI B
11" X 17"
DATEDESCRIPTION
REVISIONS
PROJECT NAME & ADDRESS
DRAWN BY
ESR
03/18/2025INITIAL
CMS RENEWABLE LLC
2100 N HWY 360 #1004, GRAND
PRAIRIE, TX 75050, USA
PHONE: +14694285563
EMAIL: edgar@cmsrenewable.com
LICENSE NO: #35493
ELECTRICAL LICENSE NO: #213982
JUNCTION BOX
DATASHEET
PV-19