HomeMy WebLinkAboutSFRA2025-004572RECEIVED: 12/08/2025
25-004572 DATE OF ISSUANCE:
407 TURNER RD
SOLAR PANELS PERMIT #:
BUILDING PERMIT APPLICATION
407 Turner Rd Grapevine TX USA 76051 SUITE #
BUILDING CONTRACTOR (company name): SUNRUN INSTALLATION SERVICES INC
CURRENT MAILING ADDRESS: 2503 N BELTLINE RD STE 130
CITYSTATE/ZIP: GRAND PRAIRIE, TX 75050 PH: # 385-491-6788 Fax
CURRENT MAILING ADDRESS: 407 Turner Rd
CITY/STATE/ZIP: Grapevine TX USA 76051 PHONE NUMBER:
PROJECT VALUE: $ 31,144 FIRE SPRINKLERED? YES
WHAT TRADES WILL BE NEEDED? ELECTRIC X PLUMBING
USE OF BUILDING OR STRUCTURE: SINGLE FAMILY RESIDENCE
Total Square Footage under roof. Square Footage of alteration/addition:
13H
El I hereby certify that plans have been reviewed and the building will be inspected by a certified energy code inspector in accordance with
State Law. Plan review and inspection documentation shall be made available to the Building Department (required for new buildings,
alterations and additions)
LI I hereby certify that plans have been submitted to the Texas Department of Licensing and Regulation for Accessibility Review.
Control Number: (Not required for 1 & 2 family dwellings)
L] I hereby certify that an asbestos survey has been conducted for this structure in accordance with the regulatory requirements of the Texas
Department of Health.
(REQUIRED FOR DEMOLITIONS, ADDITIONS AND OR ALTERATION TO COMMERCIAL AND PUBLIC BUILDINGS)
i*rP;igj9 iW "i Akfir,&Ixf
Mij ujualluc Fug
41,1111-40-91 111, 1@
-1-lating uolistructio[j. it is unuerstooa tnal the issuance or=
this permit does not grant or authorize any violation of any code or ordinance of the City Of Grapevine. I FURTHERMORE UNDERSTAND
THAT PLANS AND SPECIFICATIONS ARE NOT REVIEWED FOR HANDICAPPED ACCESSIBILITY BY THE CITY, AND THAT THE
DESIGN PROFESSIONAL/OWNER IS RESPONSIBLE FOR OBTAINING SUCH APPROVAL FROM THE APPROPRIATE STATE AND
OR FEDERAL AGENCY(S).
PRINT NAME: THOMAS LONG SIGNATURE V'A&'r ,f
.. .. ...... PHONE#: 385-491-6788 EMAIL.
THE IV6-L—LOWING IS TO BE COMPLETED BY THE BUILDING INSPECTION DEPARTMENT
Construction T� pe:
Permit Valuation: $
. .... .. ....
Setbacks
Apiroval to Issue )
Occuranc\ Group:
Fire Soh er: YES No
i Front:
Electrical
Division:
Buildinu, Depth:
Left:
P ,
lumbim
Zoning:
Buildin,, Width:
Rear:
echan'cal M
Occupancy Load:
Grease TraU
RL!ht:
Hood
Plan Review Approval;
Date.
Buildin,.,. Permit Fee:
Site Plan Approval:
Date:
Plan Review Fee:
Fire Derartment.
Date:
Lot Drainage Fee:
Public Works Department:
Date:
Sewer Availability Rate:
Health Department:
Date:
Water Availabilit,, Rate:
Approved for Permit:
Date:
Total Fees:
Lot Drainage Submitted:
Approved:
Total Amount Due:
P.C. BOX 95104, GRAPEVINE, TX 76099 (817) 410-3165
T
6:1FORMS\DSPERMITAPPLICATIONS 1102-R.v.11104,5/06,2JO7.11/09,4/11,Wl9
City of aBuilding - Residential
`• Box 95104Alteration
Grapevine,.19
817) t r125-004572
Project Description: r panels & ►.ttery backup
to exciting solar panels.[ELECTRONIC
Issued on: 1 . i26 at 11:09 a
ADDRESS
INSPECTIONS
F,J
Grapevine, TX 76051 1. MISC. Building Inspection
2. Building Setback
LEGAL 3. Building Foundation/Footing
Hayley Addition Blk 1 Lot 4. Building Pier
5ra
S 5. Building Framing
Chili's Bar & Grill #207 6. Building Bracing / Sheathing
PERMITINFORMATION
FIELDS
PAUL JOYC
SUNRUN ISTLLATI
`APPLICANT NAME (Individual)
N SERVICES IC
"APPLICANT PHONE NUMBER
(385) 91-6788
APPLICANT E-MAIL
COLLABORATORS
VALUATION
-PAULJOYCE
Square Footage
SUNRUN
* CONSTRUCTION TYPE
INSTALLATION
* OCCUPANCY GROUP
SERVICES INC
(385) 491-6788
DOCUMENTS - MISC 01
OWNERS DOCUMENTS - MISC 02
• Antony Barron "ZONING DISTRICT
APPROVED TO ISSUE ELECTRIC
944
UN111ff riff
r
i i r r;
9. Building Energy d
1. Lot Drainage Inspection
11. Building Final
PAUL JOYC
326270330
31144
11
VB
-3
407 TURNER RD PLANS AND
SUPPORTING DOCUETS.pf
GRAPEVINE BLDG A.pdf
-5.0
YES
TOTAL PAID
$ 150.00 $150.00 $150.00
$ 150.00 $ 150.00 $0.00
• i; ��i r .
_......... . , Page 1/2
MYGov.us 25-004572, 01/16/2026 at 11:09 AM Issued by: Amanda Robeson
DOES NOT GRANT •; AUTHORIZE ANY VIOLATION OF ANY CODE OR
ORDINANCE OF THE CITY OF GRAPEVINE.
I FURTHERMORE UNDERSTAND THAT PLANS AND SPECIFICATIONS ARE
NOT REVIEWED FOR HANDICAPPED ACCESSIBILITY BY THE CITY AND THAT
THE DESIGN PROFESSIONAL / OWNER IS RESPONSIBLE FOR OBTAINING
SUCH APPROVAL FROM THE APPROPRIATE STATE AND OR FEDERAL
AGENCY(S).
January 16, 2026
Signature Date
it of Grapevine Building - Residential Alteration
Project # 25-004572 d.
1) ALL work must be done in compliance with the 2021 INTERNATIONAL BUILDING CODE.
"ALL work ISSUED prior to January 1, 2024, must be done in compliance with the 2006 INTERNATIONAL
BUILDING CODE.
2) City Approved Stamped Plans must be on -site for ALL INSPECTIONS.
3) Project address must be clearly posted at the job site.
NOTES
> 24 HOUR INSPECTION NUMBER
METRO (817) 410-3010, CUT OFF TIME FOR A.M. INSPECTION IS 7:30 A.M. --- CUT OFF TIME FOR RM.
INSPECTION IS 12.30 P.M.
> PERMIT ISSUED IN ACCORDANCE WITH APPLICATION ON FILE IN THIS OFFICE.
Page 2/2
MYGOV.US 25-004572, OV1612026 at 11:09 AM Issued by: Amanda Robeson
SHEETINDEX
PAGE # DESCRIPTION
PV_l .o
COVER SHEET
PV-ZO
SITE PLAN
PV-3.0
LAYOUT
PV4.0
ELECTRICAL
PV-5.0
SIGNAGE
PV_5. 1
SIGNAGE 2
R
11
AMPERE
'c
ALTERNATING CURRENT
AFC
ARC FAULTCRCUIT INTERUNER
AZIM
"ZIMUM
( Omp
c "MIX'stl 1011
Oc
NT
CIREI,'T CURRENT
(F)
IMFING
Ess
E N L RG Y S T 0 RA'o C $, Y ' l U4
msr
MAN 'ILRVIOr. PANEL
(Nf
NEIN
PRUAB
PRE-FABRICATEO
PiF
POJNUb PEN YQUANF r001
pv
P111TOVOLT.0
f" : D
WID MUTDOWN DEVICE
Tt_
I RAW ' FRMERLE,S
v
VOUS
lw
VIATI
� w* *�k 0 M,
SYSTEM SIZE: 3.28KW DC, 11.5KW AC
MODULES: (8) HANWHA O-CELLS: Q.PEAK DUO BLK
ML-Gl 0,C+ 410 (MD06GI00A-01 7)
- RAPID SHUTDOWN: (3) TESLA MID CIRCUIT INTERRUPTER
(MCI) ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE
- ENERGY STORAGE SYSTEM W/ INTEGRATED PV INVERTER:
(1) TESLA: POWERWALL 3 1707000-XX-Y, 135KWH, 11.5KW
INVERTER OUTPUT, LITHIUM -ION BATTERY (WEIGHT: 291.2 LB
EACH)
- BACKUP GATEWAY: (1) 200A TESLA POWERWALL CONTROL
PANEL
RACKING: ALPHATRACK TO DECK- SNR-DC-00370
EXISTING SOLAR SYSTEM INSTALLED,
ENERGY MANAGEMENT SYSTEM ENABLED ON SPAN PANEL
SPAN PANEL TO BE INSTALLED AS MAIN PANEL
NEW 225A SPAN MAIN PANEL WITH 200A MAIN BREAKER TO
BEINSTALLED
L P, S 1� i'AL L ;Z-1 4E FAI ol 11 N4 -1 FE
n-
NEC 2020: 705.12 (6)(3)(3)
THIS EQUIPMENT FED BY
MULTIPLE SOURCES, TOTAL
RATING OF ALL OVERCURRENT
DEVICES EXCLUDING MAIN
SUPPLY OVERCURRENT DEVICE
SHALL NOT EXCEED AMPACITY OF
BUSBAR
- ALL WORK SHALL GENERALLY CONFORM WITH 2021 IRC/IBC/IEBC, ASCE 7-16 & 2018 NDS, MUNICIPAL CODE, AND
ALL MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS,
PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020.
ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020.
PHOTOVOLATIC SYSTEM IS UNGROUNDED. NO CONDUCTORS ARE SOLIDLY GROUNDED IN THE INVERTER. SYSTEM
COMPLIES WITH 690,41(A)
MODULES CONFORM TO AND ARE LISTED UNDER UL 61730.
INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741
RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
SNAPNRACK RACKING SYSTEMS, IN COMBINATION WITH TYPE 1. OR TYPE 11 MODULES, ARE CLASS A FIRE RATED.
RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL CONDUCTORS ARE WITHIN ARRAY
BOUNDARIES PER NEC 690.12(1).
CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G).
ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT,
11.26 AMPS MODULE SHORT CIRCUIT CURRENT,
17,59 AMPS DERATED SHORT CIRCUIT CURRENT [690.8 (a) & 690,8 (b)].
THE CAPACITY OF THE STANDALONE SYSTEM SUPPLY SHALL BE EQUAL To OR GREATER THAN THE LOAD POSED
BY THE SINGLE LARGEST UTILIZATION EQUIPMENT CONNECTED TOTHE SYSTEM PER NEC ARTICLE 710.15(A)
- ALL PASS -THROUGH CONDUCTORS MUST COMPLY WITH NEC 312.8
G 'IE Al-11- REC�!Jll-
�PPROVAL Wit. RE -15ED
il'i A ivg'
y IW4
,;LPER"FE
A%W
i- 1W
RECEIVED: 12/08/2025
25-004572
407 TURNER RD
SOLAR PANELS
REV NAME
�T, 17141 .7111
DATE COMMENTS
afto 90% a 9A%
bu IRI"W I
28447
11110I
5050
CUSTOMER RESIDENCE:
ANTONYBARRON
407 TURNER RD, GRAPEVINE,
TX. 76051
TEL (806) 577-6974
APN, NONE
PROJECT NUMBER:
351 R-407BARR2
DESIGNER: (415) 580-020 ex3
FRANK NGABO
SHEET
COVER SHEET
REV: A 11130/2025
PAGE PV-1.0
SITE PLAN - SCALE = 1/32" = V-0-
9
(N) ARRAY AR-02
ROOFPATHWAYS
(TTYP)
(N) ARRAY AR-01
ROOF PATHWAYS
(TTYP)
(E) DRIVEWAY
(E) PV ARRAY
(E) RESIDENCE
LINVE
rf
(E) FENCE
MP
AC SE
MD 1
(E) PV
EQUIPMENTS
ARRAY
TRUE
MAG
PV AREA
PITCH
AZIM
AZIM
(SOFT)
AR-01 27-
271'
268'
147,95
AR,02 27'
271'
357'
63.41
NOTES:
RESIDENCE DOES NOT CONTAIN ACTIVE FIRE
SPRINKLERS.
ARRAY DETAILS:
TOTAL ROOF SURFACE AREA, 35119 SO FT,
TOTAL PV ARRAY AREA: 211 A SO FT(NEW)
• TOTAL PV ARRAY AREA: 441.42 SOFT (EXISTING)
TOTAL PV ARRAY AREA:652,82 SOFT
NOTE: ROOFTOP MODULE LEVEL RAPID • PERCENTAGE PV COVERAGE:
SHUTDOWN DEVICE INSTALLED PER NEC (TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE
69012 AREA)" 100 = 18.55%
afts
bLj I Li I
28447
CUSTOMER RESIDENCE:
ANTONY BARRON
407 TURNER RD, GRAPEVINE,
TX. 76051
TEL (806) 677-6974
APN, NONE
PROJECT NUMBER:
351R-407BARR2
SOLAR DESIGNER; {4151580.6920 eX3
LEOEND SCALE: MICROGRID F- 7 INTERIOR EQUIPMENT MODULES FRANK NGABO
NOTE:_N01 AA 14TI, RDs REMOTE DISCONNECT INVERTER(S) BACKUP LOADS PANEL SHOWN AS DASHED
0 EN INTERCONNECT DEVICE L -3
IN LL6Ff'r' 19 SWITCH m
7,4t_C_APPFARlN.'-,llr. PLAN E SHEET
SE
SERVICE ENTRANCE
C AC DISCONNECT(S)
EA
FRANKLIN GENERATIONPANEL
APBOX
(FBI 0
METER ADAPTER
BATTERY SITE PLAN
ENERGY STORAGE
MP MAIN PANEL
FDC� DC DISCOqNECT(S)
PV LOAD CENTER
10 COMBINER BOX 10:1
MAC METER ADAPTER
Fm CONTROLLER
Zj= SYSTEM (ESS) SNR MOUNT
SNR MOUNT & SKIRT
REV: 11130/2025
PAGE
I
EEDI
PV-2.0
SUB -PANEL
ROOF INFO
Name Type
COMP SHINGLE -ALPHATRACK
AR-01 [DECKANCHOR]
AR-02 COMP SHINGLE - ALPHATRACK
[DECKANCHOR]
01 - AR-01 - SCALE: 3/32" = V-0"
AZIM: 271'
PITCH:27*
02 - AR-02 - SCALE: 1/8" = I
AZIM: 271"
PITCH:27'
ATTACHMENT INFORMATION
DESIGN CRITERIA
Height
Detail Max Landscape Max Landscape Max Portrait
Max Portrait
Comiguration MAX DISTRIBUTED LOAD: 3 PSF
OC Spacing Overhang OC Spacing
Overhang
SNOW LOAD: 5 PSF
WIND SPEED:
2-Story
ALPHATRACK TO DECK - SNR-DC-00370 4'-10" 0'-6- T-2"
0'-6-
STAGGERED 115 MPH 3-SEC GUST.
FASTENERS:
(2) DECK ANCHORS FULLY
2-Story
ALPHATRACK TO DECK - SNR-DC-00370 4'-10" 0'-6" 3',2'
0*-6'*
STAGGERED PENETRATING THROUGH WOOD
DECK
2'-1
3 -1 1 " 64p, 2'-7"
3111
51-9. - 8'-2"
- A' - , T-T�
4'-2" 12'-5" 6'-1'
f7
......................
MANOUCREHR WHARANE SRI
AVWS &A011111 I
INSTALLERS SHALL NOTIFY ENGINEER OF ANY R
POTENTIAL STRUCTURAL ISSUES OBSERVED
PRIOR TO PROCEEDING W/ INSTALLATION.
IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12' (48' FOR TILT KITS) BOUNDARY
REGION OF ANY ROOF PLANE EDGES (EXCEPT VALLEYS),
THEN ATTACHMENTS NEED TO BE ADDED AND OVERHANG REDUCED WITHIN
THE 12" (48' FOR TILT KITS) BOUNDARY REGION ONLY AS
FOLLOWS:
- ALLOWABLE ATTACHMENT SPACING INDICATED ON PLANS TO BE
REDUCED BY 501.
-- ALLOWABLE OVERHANG INDICATED ON PLANS TO BE 115TH OF
ALLOWABLE ATTACHMENT SPACING INDICATED ON PLANS,
28447
40-111Tk
`
i1117 "1
CUSTOMER RESIDENCE:
ANTONYBARRON
407 TURNER RD, GRAPEVINE,
TX. 76051
TEL (806) 677,6974
APN, NONE
PROJECT NUMBER:
351 R-407BARR2
DESIGNER: 1416) 580,6920 ex3
FRANK NGABO
LAYOUT
REV: A 11/30/2025
PAGE PV-3.0
NEW 225A SPAN MAIN PANEL
WITH 200A MAIN BREAKER
BACK UP LOADS PANEL
4
A
RELOCATED BACKUP (E)
LOADS
NEW 200A
BACKLP GATEVfA
GATIDAFZ
VVITFfOID 200A
MAIN BREAKER
A
4—r7--VPo
QA 0CPD
D
E
60A
(N) INTERNAL PANELECARD
yjil H 1) tN)QIA E"'I'V BREAKER
(E) 30A PV BREAKER
TAG CIRCUIT DESCRIPTION
1 Inverter Input
2 Inverter Input
3 Inverter Output
4 Backup Panel Feeder
5 Service Feeder
Existing Enplllso
Energy Q7-630-2-U-S
Existing EnNme
Ewe, 107.1,0-x-US E E
E Existing21 LONG Green
Ene,gy'reChnology 0,) Ltd
LR4-60HPE4 355M
AC DISCONNECT Ex,,,n.j Enphile Ex,stina rnvKtens�
Combiner Panel
• POINT OF INTERCCINNIECTION NPC 2020 705 BREAKER IN GATEWAY
_
•
METED NUMBER 1TqW117&-G
• EaIPPAENT CHARXTERISTICS INCLUDED IN SPEC SI-1ELT9
• NOTE COM&NED SYSTEM BAIKFEED = 90 QA USED FOR INTERCONNECTION CALCULATIONS
INITESLA REMOTE METER
f 1 ISC-CAR PV CURRFNT
TRANSFORMER
WNl LOCKABLE
BLADEIYPE
AC` DIS'-ONNECT INVERTER TESLA
POWERWALL '61707000-Xky,
ENERGY STORAGE
TFSLA:POVVFRIJVAI-L
17Q7000-)O(,Y 115COV�Al T
3 24-7V INVERTER 2 1 8 HANWHA Q-'ELLS
Q PEAK DUC- E�K ML-GIO C, 410 (MIDOGG100A 0171
10-10 STRING I WITH 8 MODULES
WI TH 3 MCI 401-NT , MCCULE LEVEL
RAPID SHUTDOWN DEVICES
J-B"jx
SOUARE D --L—
DIJ222136
3R,rDA,2P
120/240VAC
LOAD RATED ED
DISCONNECT WITH A RAPID
SHUTDOWN OOMPLIANT
CONDUIT SCHEDULE
CONDUCTOR
NEUTRAL
(2)10AWG (PV WIRE)
NIA
(2) 10 AWG
N/A
THHNITHWN-2
(2) 6 AWG
(1) 6 AWG
THHNtTHWN-2
THHNfTHWN-2
(2) 310 AWG
(1) 310 AWG
THHNiTHWN-2
THHN/THWN-2
(2) 3/0 AWG
(1) 310 AWG
THHNITHWN-2
THHNITHWN-2
GROUND CONDUIT
10 AWG (BARE) Open Air
IOAWG THHNrTHVVN-2 314 EMT
8 AWG THHNITHWN-2 314 EMT
4 AWG THHNITHWN-2 2 EMT
NONE 1 1/2 EMT
ESS EQUIPPED WITH CAPACITY TO CHARGE
FROM GRID POWER
INSTALLER MUST CHECK THE CONDITION,
iNSTALLABILITY AND CODE COMPLIANCE OF
EXISTING EQUIPMENT-
SU IR"
28447
CUSTOMER RESIDENCE:
ANTONY BARRON
407 TURNER RD, GRAPEVINE,
TX. 76051
TEL (806) 677.6974
APN, NONE
PROJECT NUMBER:
351R-407BARR2
DESIGNER; 14115l580-6920eX3
FRANK NGABO
SHEET
ELECTRICAL
REV: A 11130/2025
PAGE
PV-4.0
RNING 1 It
------
ELECTRICAL SHOCK HAZARD
TERMINALS ON LINE AND LOAD LABEL LO--ATI ON
SIDES MAY BE ENERGIZED IN INVERTER(,'), DO DOCOI`,NECT,S)
THE OPEN POSITION PER rOOE(S! NEC 2020 690,53
LABEL LOCATION
INVEMER(S), AC,rCDIS-,ONNFCr(Sl,
AC _OMPINER PANEL or APPLICABLE)
PERCCDEIS) NEC 2020 00 13IRj
ffmc���
THREE POWER SUPPLY
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
LABEL LOCATION
UTILITY SERVICE METER AND MAIN
SERVICE PANEL
PER CODE($) NEC 2020 705 121C)
POWER souRcE ouvu-r CONNECTION
DO NOT RELOCATE THIS
OVERCURRIENT DEVICE
LABEL LOCATION
ADJACENT TO PV BREAKER AND ESS
OC P D(IF APPLICABLE)
PER CDE(S) NEC 2020: 705 12(8)(3)(2)
zt WARNING
THIS EQUIPMENT FED BY
MULTIPLE SOURCES. TOTAL
RATING OF ALL OVERCURRENT
DEVICES EXCLUDING MAIN
SUPPLY OVERCURRENT DEVICE
SHALL NOT EXCEED AMPACITY OF
BLISBAR
LABEL LOCATION
PVLOAD CENTER (IF APPLICABLE) AND
ANY PANEL THAT' UTILIZES "THE SUM
OF BREAKERS RULE"
PER OODIO1% NEC 2020 705 12 (8)(31(-1
mm s
LABEL LOCATION
INSTALLED WITHIN TOF RAPID SHUT DOWN
SWITCH PER CODEf S) NEC 2020 690 I FC
2018 12045,
LABEL LOCATION
INTERIOR AND EXTERIOR DO CONDUIT EVERY 10 FT,
AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
ON EVERY JBIPULL BOX CONTAINING D.CCIRCUITS
PER CODEtS! NEC 2020 00?,l(Dj(21
LABEL
LOCATION
ENERGY STORAGE SYSTEM 4'
PER CODE(S I NEC "020 706
LABEL. LOCATION
AC DISC ONNEOT(SI, PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION
PER'OODEi S) NEC 2020 690 54
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF" F _01IECTRftR
C PV
POSITION TO SHUT DOWN PV
SYSTEM AND REDUCE SHOCK
HAZARD IN THE ARRAY,
LABEL LOCATION
ON OR NO MORE THAT I M I,' FT) FROM THE,-,ERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED
PER CODE(S) NEC 2020 690 %C), CEC 2022 690 56tQ
NOTES AND SPF CIFICATtON,
• SIGNS AND LAPELS SHALL MEET THE REQUIREMENTSOF THE NEC 2020 ARTICLE
110 21fE, UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR
IF REQUES' I 'ED BY I ' HE LOCAL AHJ
SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
WORDS, COLORS AND SYMBOLS
• LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
METHOD AND SHALL NOT BE HAND WRITTEN
LABEL 13HALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED
SGNH AND LABELS SHALL COMPLY WITH ANSI Z535 4-21011, PRODUCT SAFETY
SIGNS AND LABELS.
UNLESS OTHERWISE SPECIFIED
DO NOT COVER EXISTING MANUFACTURER LABELS
TCAUTION
ENERGY STORAGE SYSTEM
PREMISES WIRING MAY REMAIN
ENERGIZED AFTER LOSS OF
UTILITY POWER
I I
bu RUM' I
LABEL LCCATION�
INVER I TERI% AC,DC DISCONNECT(S), AC COMBINER PANEL dF APPLICABLE,
PER CODES! NEC 2020 706 15(C)
28447
I I 'l ITI 1;l.W -, ill I I w, v m;,-,
1 41 IE 011
CUSTOMER RESIDENCE:
ANTONYBARRON
407 TURNER RD, GRAPEVINE,
TX. 76051
TEL (806) 677,6974
APN, NONE
-7
PROJECT NUMBER:
351 R-407BARR2
UUT�l
DESIGNER: (416) 580-6920 ex3
FRANK NGABO
SHEET
SIGNAGE
REV:A 11/30/2025
IPAGE
wmt
PV-5.0
SOLAR PANELS (E)PV ARRAY
ON ROOF
(E)PV
EQUIPMENTS
AC DISCONNECT
ENERGY STORAGE
SERVICE SYSTEM AND INVERTER(EXT)
ENTRANCE
GATEWAY(ESS+PV)
BREAKER
DISCONNECTS
407 TURNER RD, GRAPEVINE, TX, 76051
PER ljCDE,S) NEC 204: 705 10.710 10
LABELING FORMAT
LABELS SHALL BE RED PLASTIC MATERIAL WITH ENGRAVED WHITE LETTERS
MADE OF DURABLE ADHESIVE, WEATHER RESISTANT MATERIAL SUITABLE FOR
THE ENVIRONMENT, LETTERS SHALL BE MINIMUM 3/8" IN SIZE.
4111111,162 90% a &'Aft
bu StA I
28447
'CUSTOMER RESIDENCE:
ANTONY BARRON
407 TURNER RD, GRAPEVINE,
TX. 76051
TEL (806) 677-6974
APN, NONE
PROJECT NUMBER:
351R-407BARR2
DESIGNER; 14151 580-6920 eX3
FRANK NGABO
SHEET
SIGNAGE 2
REV:A 1113012021
PAGE PV-5. 1
FMIGHTY
6 ENGINEERING CO.
November 30,2025
RE:
Project Adc[IYS5:
Design Criteria:
CERTIFICATION LETTER
ANTONY BARRON RESIDENCE
407 TURNER RD
GRAPEVINE,TX, 76051
Applicable Codes = 2021 IRC/IEBC/lBC, ASCE 7-16 and 2018 NDS
Risk Category = II
Wind Speed = 115 mph. Exposure Category B, Partially/Fully Enclosed Method
Ground Snow Load = 5 psf
To Whom It May Concern,
A job site survey of the existing framing system of the address indicated above was performed . Ali structural evaluation is based on the site
inspection observations and the desien criteria listed above.
Existing roof structural framing has been reviewed for additional loading due to installation of Solar PV System on the roof. The structural
review applies to the sections of roof that is directly supporting the Solar PV System.
Based on this evaluation, I certify that the alteration to the existing structure by installation of the Solar PV System, meets the prescriptive
compliance requirements of the applicable existing building and/or new building provisions adopted/referenced above.
Additionally, the Solar PV System assembly (including attachment hardwares has been reviewed to be in accordance with the manufacturer*s
specifications and to meet and/or exceed the requirements set forth by the referenced codes.
Installer shall inspect the existing roof framing to verify it is in suitable condition and does not exhibit any signs of damage which may
diminish the capacity of its members or connections prior to commencement of PV installation.
Sincerely.
I'ligitally signed by
Manouchehr
Hakharnaneshli
#'ate: 2025.11.30
14:03:25 --05'00'
MIGHTY
ENGINEEPING CO.
MOUNTING PLANE
ROOF AR-01 & AR-02
ANTONY BARRON RESIDENCE, 407 TURNER RD, GRAPEVINE,TX, 76051
MOUNTING PLANE STRUCTURAL EVALUATION
ROOF PITCH RESULT GOVERNING ANALYSIS
27' IE8C IMPACT CHECK
Limits of Scope of Work and Liabifitv.
The existing structure has been reviewed based on the assumption that it has been originally designed and constructed per appropriate
codes. The structural analysis of the subject property is based or the provided site survey data. The calculations produced for this
structure's assessment are only for the roof framing supporting the proposed PI! installation referenced in the stamped plan5etand were
made according to generolly recognized structural analysis standards and procedures. Ali PV modules, racking and attachment
components shall be designed and installed per manufacturers approved guidelines and specifications. These plans are not stomped for
water leakage or existing damage to the structural component that was not accessed during the site survey. Prior to commencement Of
work, the PVsystern installer should verify that the existing roof and connections are in suitable condition and inspect framing noted on
the certification letter and inform the Engineer of Record of any discrepancies prior to installation. The installer should also check for any
damages such as water damage, cracked framing, etc. and inform the Engineer of Record of existing deficiencies which are unknown
andlor were not observable during the time of survey and have not been included in this scope of work. Any change in the scope of the
work shall not be accepted unless such change, addition, or deletion is approved in advance and in writing by the Engineer of Record,
MIGHTY IE8C IMPACT CHECK
[1\ on ENGIN,EEPING CO.
ROOF AR-01 & AR-02
ANTONY BARRON RESIDENCE, 407 TURNER RD, GRAPEVINE,TX, 76051
EXISTING
WITH PV PANELS
Roof Dead Load (DL) =
630
9,70
psf
Roof Live Load (Lrl
1&00
0.00
psf
Roof Snow Load {SL')
3,90
2,90
osf
EXISTING
WITH PV PANELS
(DL + Lr),'Cd
1936
10.78
psf
(DL + SL)/Cd
9.22
10.87
psf
Maximum Gravity Load =
19,76
10,87
psf
Load Increase ( '/n) = 1 -44.99%
The requirements of section 805.2 of 2021 IEBC are met and the structure is permitted to remain unaltered.
li�u' N::! C?
TNE4yj'MIGHTY
WIND UPLIFT CALCULATION
G CCL a ENGINEEPIN
ROOF AR-01 & AR-02
ANTONY BARRON RESIDENCE, 407 TURNER RD, GRAPEVINE,TX, 76051
"raff?'Mrifin "00
Ultimate Wind Speed = 115.00 mph Roof Pitch = 27'
Risk Category = H Roof Type = Hip
Exposure Category = B Velocity Pressure Exposure Coefficient, Xz = 0,65
Mean Roof Height = 23.00 ft Topographic Factor, Kzt = 1.00
Solar Array Dead Load = 100 psf Wind Directionality Factor. Kd = 0,85
a = 100 If Ground Elevation Factor, Ke =1 1,00
DESIGN CALCULATIONS
Wind Velocity Pressure, qh - 1&69 psf (0.00256'Kz'Kzt*Kd*Ke*(V^2))
Solar Array Pressure Equalization F� 1 0.6
Hardware Type -JALPHATRACK TO DECK
Allowable Load = 765,00 lbs JD. Fir - L, 5/16" Lag Screw x 1, 2.25" Embedment
Array Edge Factor, vE = 1.50 Exposed Condition
Max. X - Spacing (Zone 1) = 4,83 ft Effective Wind Area
Max. Y - Spacing (Zone 1) = 172 ft 17,97 ft' II
Max. X - Spacing (Zone 2e & 2r) = 4.83 ft Effective Wind Area
Max. Y - Spacing (Zone 2e & 2,' = 1,72 ft 17.97 ft'
Max. X - Spacing (Zone 3) = 4.83 ft Effective Wind Area
Max. Y - Spacing (Zone 3) = 3.72 ft 17.97 ft'
ROOF 70NE j GCp FT UPLIFT PRESSURE PULLOUT FORCE
1 -11
— (-) UPLIFT
r 5 -10,98 psf 197.40 bs
2e & 2r _1.8() -16,61 psf 298.43 t
3 _1.80 -16,61 psf t 298.43 ibs
NOTE.-
- Wind calculation is based on ASCE 7-16,29,4 - C&C, LC #7:0.6DL + 0,6WL is used.
�1 7
. . . .... ... ....
Article 220 - Service/Feeder calculation for (address): Job Code
351R-407BARR2
407 Turner Rd Grapevine TX USA 76051-3351
Section 220.83 Existing Dwelling Unit
Part #1- Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft*
Building Square Footage VA (watts) Amps
House 2754 8262 34,425
Bus Rating 225 Total for Part #I: Amps Box A (VA)
Main Rating 200 34,43 ( 8z6z11
Dedicated circuit Size in VA Dedicated circuit
Size in VA
Laundry 1500
N/A
Appliance Circuit(s) 3000
N/A
Dishwasher(s) 1000
N/A
Disposal(s) 600
N/A
Refrigerator(s) 1000
N/A
Microwave(s) 1600
N/A
Dryer 5760
N/A
PW3 5000
N/A
Oven 7680
N/A
N/A
Amps
Box 8 (VA)
Totals for Part #2:
N/A
113,08
27i4ii
Total VA from Parts #1 and #2 combined: Box
A + Box B =
35402
Total VA 35402
First 8,000 VA @ 100% 8000 Remaining VA @ 40%
Remaining VA = 27402 27402 x 40% =
10960,8
VA
Adding First 8000 VA
8000
VA
Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:
18960.8
vA
Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:
79.00
Amps
Part #3 - Section 220.83 (B) Heating and A/C loads
*Campine the larger loads of either the Heating or the A/C loads togther
100% of all the Heating or A/C loads in VA:
8,352
VA
100% of all the Heating or A/C loads in Amps:
34.80
A
Totals from all Parts
VA
Volts
Amps
Parts #1 & #2 18960.8
240
79.00
Part #3 8,352
240
34.80
Total VA for all Parts: 27,313
390-41OWp I 132Cells
20.9% Maximum Module Efficiency
HIONT-TWOOST M.
Rooftop array, on
residental burldings
ZrI Breaking the 20% efficiency barrier
j"JN4 _j
f
2P A reliable investment
Enduring high performance
_rr Extreme weather rating
Innovative all-weather technology
The most thorough testing
programme in the industry
j I
PVn L
SERIES
Format 740,n - 41^!�
Weight 4;A,, qt
Front Cover
Back Cover Ti.,::T'J'o 'if 2', b::n tv,! T-4 i, q" J
Cell ANT '^'M "Ir
Junction box 09
Cable 44qrC--,J p to
41
Connector'
■ Electrical Characteristics
POWER CLASS 390
395
400
406
410
--
Power at MPP� F"', -190 4266
'
395
432.1 40-a 4375
405 A41 , 1)
411f)
84g 5
Short Citcult Current' il.oi 12 (15
1104
12 08 1,107 12 V
11 ii) 1215
1113
12:18
Open Circuit vaitgqe7 V -11149 45165
45 E,2
45 c=8 45 55 4� 72
45 59 4675
4 S G 2
45 ?R
Current at MPP ?A! -10,9 t` Q7
Ir,)45
11143 10 ;1149
10 56 1155
1061
it 61
Voltage at MPP _Vl ;7,54 3753
3781
3&09 3808
3&316 38 35
3? 63
3962
Efficiencyt9 9
20 1
- 2CA
�206
209
i
3-.i -A
'Vr
A7 k�'. *,r',"'
Power at MPP pT 292 fi
296
3100 1
307,
Short Circuit Current W 2'P7
8. 111:1,
d 94
13,97
Open Circuit Voltage IV 42 90
42 lj3
4296
421,,9
4 3 03
Current it MPP W a 16
8,21
8 26
�. "I
h "I G
Voltage at MPP �V 35,36
3610
36 3'-1
36,57
3t,80
Ocells PERFORMANCE WARRANTY
PERFORMANCE
AT LOW IRRADIANCE
J—t of P"—
At cr
Ail
TEMPERATURE COEFFICIENTS
Temperature Coefficient of 1,,:
Temperature Coefficient of V..
Temperature Coefficient of P
Nominal
Module Operating Temperature
teu`
Maximum System vattage
v-..
PV module classification
Class 11
Maximum Series Fuse Rating
Fire Rating based on ANSVUL 61730
7 A E
Max, Design Load, Push,Puli'
il'.
Permitted Module Temperature
Max. Test Load, PushiPull
on Continuous Duty
4:: JI
a Oualifications and Certificates
-'"2;�Q't Pv )'iJV
'E�* 121 Srr
2C 1C, JEC
U S Nc 1, ?93 21v "r"r
C E
19 ®R
ocells
Snap rack,
Solar Mounting Solutions
im q'i 11111
A
Flash Track with Patented Umbrella Technology
• Single Umbrella tag screw secures flashing and flash track to roof
in one complete action
• Umbrella technology provides weatherproofing with a long-
lasting mechanical seal
• Flash track is designed for rnaximurn versatility with 6 inches of
North -South adjustability for all Mounts
Mounts
• Single mount used at all locations on array
• Extreme time saver by eliminating link interference through the flexibility
Of the Mount to change orientation
• Features a rock -in channel nut design for easy attachment to Flash Track
• Slotted riser provides leveling for easy height adjustments
Links
• Simple design provides mounting platform between two to four
modules
Clamps onto top of modules securing them in place while providing
lhoe
row -to -row aI I "c�
• Next row of modules easily slides into place as with the Mounts
in
• Easily locks to bottom of module mounts and links for clean
aesthetics
• Ensures a strong structure for leveling and alignment of first
row of modules
• Skirt length is compatible with both portrait and landscape
module orientations
'y IVAE
INEEp,IMGlOAPPL ' CV591A -TACT
SNAPNRACY !EN,5pf-l% M135T 5E.METk'F -N-V,CON
"�,f F- NOT SUOICIF
CR.,� -PIA 5140"� HEREIN
Ap,
CANNOT BE MET OSPUPPOPT).
FOR 0
SNAPKRAC�- STP'LLATION MANUAL fop, 1'�
FN ApNPAC�Sl pINECITFIIOCglONS pTr,H:fEEPP
"vo Fp
pVffplo S-pOUE NvoR
VppDNAfoSpZCIFICA
MANUAcUERIRFMr%,Ts`
TOP
Q,JF- Pf Qu
-m
VL
-- ROOF N
13UVL IDETP11L
E6SVAO\NN)
D Y 'Atic"Op,
STRUCTURAL 00V MEMBER -
ORWTFR)vpv
.CATKINS SCALE N'TS
[)Ave 91161
UtSIGNEP
suv)(unrnAn DRAFTER:'.
: 2la f
WIN
t*—OV
*' -8jqj2QZ4 2S8--
t4UppC14 DEC 15132�'
F ROOFING MR
A'y"A19ACK
PWf DfCyl,,G
DeCK 't4S'Tp"glON
COMPLETF-D MATERIAL,
V�OofjNG
2, 112" MI" MEMBER,
114 'To s 'TP, UCUPAIL
mfTep,
_ 4.
'Oof DECKING
RAFTER'
rotApLFTED RA INS REV:
�CNMENT DETAIL,
OM\IqING NUMBER:
-00370
R- A FTERY SHALL BE MIOUNVIPE'D TCSLA
"`PE""�FK'ATION'3S ()R SUPPOIFOFED ATGRf,,,U'N'rJ
1
System Technical Model Number
Specifications Nominal Grid Voltage (Input & Output)
Grid Type
Frequency
Overcurrent Protection Device
Solar to Battery to Home/Grid Efficiency
Solar to Home/Grid Efficiency
Supported Islanding Devices
Connectivity
AC Metering
Protections
Customer Interface
Warranty
1707000-xx-y
120/240 VAC
Split phase
60 Hz
60 A
89%12
975%3
Gateway 3, Backup Switch, Backup Gateway 2
Wi-Fi (2.4 and 5 GHz), Dual -port switched Ethernet,
Cellular (LTE/4G 4)
Dry contact relay, Rapid Shutdown (RSD) certified switch
and 2-pin connector, RS-485 for meters
Revenue Grade (+/- 0,5%)
Integrated arc fault circuit interrupter (AFCI), Isolation
Monitor Interrupter (IMI), PV Rapid Shutdown (RSD) using
Testa Mid -Circuit Interrupters
Testa Mobile Apo
10 years
Solar Technical
Maximum Solar STC Input
20 kW
Specifications
Withstand Voltage
600 V DC
PV DC Input Voltage Range
60 — 550 V DC
PV DC MPPT Voltage Range
60-480VDC
MPPTS
6
Maximum Current per MPPT kd
13 A'
Maximum Short Circuit Current per MPPT (IJ
15A5
Battery Technical
Nominal Battery Energy
1&5 kWh AC
Specifications
Maximum Continuous Discharge Power
11,5 kW AC
Maximum Continuous Charge Power
5kWAC
Output Power Factor Rating
0 - 1 (Grid Code configurable)
Maximum Continuous Current
48 A
Maximum Output Fault Current
10 kA
Load Start Capability (1 s)
185 A LRA
Power Scalability
Up to 4 Powerwall 3 units supported
Typical solar shifting use case,
'Values provided for 25'C (77" F), at beginning of life. 3.3
kW charge/discharge power,
2 Tested using CEC weighted efficiency methodology.
`The customer is expected to provide internal connectivity for Powerwall 3; cellular should not be used as the primary mode of
connectivity. Cellular connectivity subject to network operator service coverage and signal strength,
5 Where the DC input current exceeds the MPPT rating, a
juniper can be used to combine two MPPTs into a single input to
intake DC current up to 26 A 1, 130 A I_,
2024
Environmental
Operating Temperature
—20-C to 50°C (-4-F to 122-F)
Specifications
Operating Humidity (RH)
Up to 100%, condensing
Storage Temperature
—20'C to 30 =C (-4- F to 86'F), up to 95% RH, non -
condensing, State of Energy (SOE): 25% initial
Maximum Elevation
3000 m (9843 ft)
Environment
Indoor and outdoor rated
Enclosure Rating
NEMA 3R
Ingress Rating
IP67 (Battery & Power Electronics)
IP45 (Wiring Compartment)
Pollution Rating
PD3
Operating Noise C 1 rn
< 50 db(A) typical
<62 db(A) maximum
"Performance rnay be de -rated at operating ternpe�atrjres above 401C (1041F).
Compliance
Certifications
UL 1642, UL 16998, UL 1741, UL 1741 SA, UL 1741 SB, UL
Information
1741 PCS, UL 3741, UL 1973, UL 1998, UL 9540,
IEEE 1547-
2018, IEEE 15471, UN 383
Grid Connection
United States
Emissions
FCC Part 15 Class B,
Environmental
RoHS Directive 2011/65/EU
Seismic
AC156, IEEE 693-2005 (high)
Fire Testing
Meets the unit level performance criteria
of UL 9540A
Mechanical
Dimensions
1099 x 609 x 193 mm (43,25 x 24 x 7.6 in)
Specifications
Weight
130 kg (287 lb)
Mounting Options
Floor or wall mount
0ti
05 0
0
L
si
193
W9 mm
mm
Krom
Electrical
Model
MCI-1
MCI
Specifications
Nominal Input DC Current Rating (I
13 A
13 A
Maximum Input Short Circuit Current (Ij
19 A
17 A
Maximum System Voltage (PVHCS)
600 V DC
1000 V DC'
Maximum System Voltage is limited by Powerwall to 600 V
DC,
RSD Module
Maximum Number of Devices per String
5
5
Performance
Control
Power Line Excitation
Power Line Excitation
Passive State
Normally Open
Normally Open
Maximum Power Consumption
7 W
7 W
Warranty
25 years
25 years
Environmental
Operating Temperature
-400C to 50'C
-45'C to 70`C
Specifications
(-40'F to 122c'F)
(-49`F to 158°F)
Storage Temperature
—30'C to 70'C
—30'C to 70'C
(-22`F to 158'F)
(-22°F to 153-F)
Enclosure Rating
NEMA 4X / IP65
NEMA 4X / IP65
Mechanical
Electrical Connections
MC4 Connector
MC4 Connector
Specifications
Housing
Plastic
Plastic
Dimensions
125 x 150 x 22 mm
173 x 45 x 22 rem
(5x6x1in)
(6.8 x 1.8 x 1 in)
Weight
350 g (0.77 lb)
120 g (0.261b)
Mounting Options
ZEP Nome Run Clip
Wire Clip
M4 Screw (#10)
M8 Bolt (5/16")
Nail / Wood screw
Compliance
Certifications
UL 1741 PURSE, UL 3741,
Information
PVRSA (Photovoltaic Rapid Shutdown Array)
RSD Initiation Method
External System Shutdown Switch or
Powerwall 3 Enable Switch
UL 3741 PV Hazard Control
(and PVRSA) Compatibility See Powerwall 3Installation Manual
ko— 0 L-3n- '*J11L*V14 #
* 11 0
#146aftlif a
Model Number
1841000-01-y
Nominal Grid Voltage
120/240 V AC
Grid Configuration
Split phase
Grid Frequency
60 Hz
Continuous Current
200 A
Rating
Maximum Supply Short
22 kA with Square D or
Circuit Current
Eaton main breaker
25 kA with Eaton main
briaaker4'
IEC Protective class
Class I
Overvoltage Category
Category IV
`--Only Eaton CSR or 0WH main breakers are 25 kA rated,
Operating Temperature
Maximum Elevation
Environment
Enclosure Type
Certif !cations
Emissions
Mechanical Dimensions 660 x 411 x 149 mm;
Specifications (26 x 16 x 6 in)
Weight 16.3 kg (36 lb)
Mounting options Wall mount
Krom
AC Meter
Revenue accurate (+/- 05%)
Communication
CAN
User Interface
Tesla App
Backup Transition
Automatic disconnect for
seamless backup
Overcurrent
100-200 A
Protection Device
Service entrance rated
Eaton CSR, BWH, or BW, or
Square D QOM breakers
Internal Panelboard
200 A
8-space/16 circuit breakers
Eaton BR, Siemens OF, or
Square D HOM breakers rated
to 10-125A
Warranty
10 years
—20'C to 50'C (-4'F to 122°F)
Up to 100%, condensing
3000 m (9843 ft)
Indoor and outdoor rated
NEMA 3R
CSA 22.2107.1, CSA 22.2 29
FCCII Part 15, ICES 003
A
660
mm
411 mm 149
%m
Performance
Model Number
1624171-xx-y
Specifications
Continuous Load Rating
200 A, 1201240 V split phase
Maximum Supply Short Circuit Current
22 kA with breaker
Communication
CAN
AC Meter
Revenue accurate (+/- 0.50/D)
Expected Service Life
21 years
Warranty
10 years
° Breaker mayiniurn supply short circuit current
rating must be equal to or greater than the available fautt cur rent.
Environmental
Operating Temperature
-40'C to 50'C (-40°F to 122'F)
Specifications
Storage Temperature
-40'C to 85-C (-40'F to 185'F)
Enclosure Rating
NEMA3R
Pollution Rating
PD3
Compliance
Safety Standards
USA: UL 414, UL 414 SB, UL 2735, UL
916, CA Prop 65
Information
Emissions
FCC, ICES
Mechanical
Dimensions
176 x 205 x 74 mrn (6.9 x 81 x 2.9 in)
Specifications
Weight
2.8 lb
Meter and Socket Compatibility
ANSI Type 2S, ringless or ring type
External Service Interface
Contactor manual override 10
Reset button
Conduit Compatibility
1/2-inch NPT
Manually overrides the contactor position during a service event,
176
A
205 mm,
...........
. . . . . . . . . . .
74 mm
room
Ar-A -I -
sifiza"111"M 9 a
From
Model Number
1232100-xx-y
AC Voltage (Nominal)
120/240 V
Feed -in Type
Split phase
Grid Frequency
60 Hz
Current Rating
200 A
Maximum Supply Short
10 kA
Circuit Current
Overcurrent Protection
100 - 200 A, Service
Device
entrance rated'
Overvoltage Category
Category IV
Internal Primary
Revenue accurate
AC Meter
(+/-0,2%)
Internal Auxiliary
Revenue accurate
AC Meter
(+/- 20%)
Primary Connectivity
Ethernet, Wi-Fi
Secondary Connectivity
Cellular (3G, LTE/4G)
.............. .........
Maximum Elevation
Environment
Enclosure Type
Certif ications,
Emissions
Dimensions 660 x 411 x 149 mm
(26 x 16 x 6 in)
Weight 20A kg (45 lb)
Mounting options Wall mount,
Semi -flush mount
User Interface Tesla App
Operating Modes Support for solar self -
consumption, time -based
control, and backup
Backup Transition Automatic disconnect for
seamless backup
Modularity Supports up to 10 AC -
coupled Powerwalls
Optional Internal 200 A 6-space / 12 circuit
Panelboard breakers
Siemens OP or Square D
HOM breakers rated 10 -
80A or Eaton BR breakers
rated 10 - 125A
Warranty 10 years
"When protected by Class J fuses, Backup Gateway 2 is
suitable f or use in circuits capable of delivering not more
than 22kA symmetrical amperes.
'Cellular connectivity subject to network operator service
coverage and signal strength,
—20'C to 50°C (-4'F to 122'F)
Up to 100%, condensing
3000 m (9843 ft)
Indoor and outdoor rated
NEMA3R
CSA 22.2 0,19, CSA 2Z2 205
FCC Part 15, ICES 003
411 mm
Whole Home Backup
0
T Meter
Grid Meter socket panel
Solar
7
Load center
Sackuploads
Powerwall 3 with Backup Switch
Whole Home Backup
""
Solar
T E
Meter'j 1
Grid Meter socket panel Load center
Backup loads
Powerwall 3 with Backup Gateway 2
Partial Home Backup
Utility Meter
----------
Main
Breaker
Hi
Jut
Grid Meter load center Load center
O\v
Non -essential loads Backup loads
RUIM
Solar
%
Electrical Model McI-1 MCI-2
Specifications Nominal Input DC Current Rating (1MP) 13 A 13 A
Maximum Input Short Circuit Current (Isc) 19 A
Maximum System Voltage (PVHCS) 600 V DC
'O!Ylaximum System Voltage is limited by Powerwall+ to 600 V DC,
RSD Module Maximum Number of Devices per String
Performance Control
Passive State
Maximum Power Consumption
Warranty
Environmental Operating Temperature
Specifications
Storage Temperature
Enclosure Rating
Mechanical Electrical Connections
Specifications Housing
Dimensions
Compliance Certifications
Information
RSD Initiation Method
LGKO:EZITJ2� �*�
HM
5
Power Line Excitation
Normally Open
7 W
2S years
MC4 Connector
Plastic
125 x 150 x 22 mm
(5 x 6 x I in)
3SO g (0.77 to)
ZEP Home Run Clip
M4 Screw (#10)
M8 Bolt (S/16")
Nail / Wood screw
17 A
1000 V DOD
5
Power Line Excitation
Normally Open
7 W
25 years
-45°C to 70'C
(-49°F to 1S8°F)
-30*C to 70'C
(-22°F to 158°F)
NEMA 4X / IP65
MC4 Connector
Plastic
173 x 4S x 22 mm
(6.8 x 1.8 x I in)
120 g (0,26 lb)
Wire Clip
UL 1741 PVRSE, UL 3741,
PVRSA (Photovoltaic Rapid Shutdown Array)
External System Shutdown Switch
See Powerwatl+ Installation Manual
�06��
Unprecedented cost saving Custornizable, flexible backup
home energy insights when paired with battery storage
Electrical
• Revenue -accurate energy monitoring
100 - 200A Main Breaker with built in
Microgrid interconnection Device (MID)'
• 225A busbar rating
Installation
Indoor and outdoor -rated
• Surface or semi -flush mounted
• Compatible with standard I" breakers
Connectivity
• Ethernet, WiFi, cellular
Free over -the -air updates
- Tesla, Franklin'
MORTWIMAUVIEZ •. * =
SPAN goes beyond monitoring with
the SPAN Home App" for real-time
control and energy insights to bring
your hornes energy to life.
Combined with battery storage, SPAN
gives homeowners the power to
choose and change backup priorities
whenever they want.
L q*Amff
W --
Grid Connection
Single phase Additional Features
Grid Frequency
60Hz
Customizable whole -home batter y storage
Bus Bat Rating
225A Backup time rernaintng estimates
Controllable Circuit Spaces (up to)
40 Real-time toad control
Energy monitoring & insights
Feed-Thru Lugs
Yes, two feeds L-oad management toi upgrade avoidance
Enclosure Rating
NEMA 3R
Max Branch Circuit Size
100A DP
Energy Management System
SPAN PowerUp"'A, capable, Backup overload protection
AC Metering
Revenue accurate +/- 0.5% oil mains + all branch circuits
Breaker Compatibility
SquareD, Siernens, Eaton, and GE
Mounting Style
Surface or serni-flush MOUnt
AC Voltage (Nominal)
208 / 240 VAC, L-L
Main Overcurrent Protection Device
Max 200A Main Breaker , built in Micros rid Interconnection Device (MID)
Maximum Input Short Circuit Current
22kA
Enclosure Dimensions
46.0 x 14.3 x 6.5 in (H x W x D)
Weight
109 lb (49.5 kg)
(enclosure no door or deadfront)
25 Its (11,3 kg)
(Partelboard)
411 b (18,6 kg)
Connectivity
Ethernet, Wifi (2.5, 5 GHz)
Warranty
SPAN Panel: 10 years; SPAN Home Gateway: 5 years
Environmental
Compliance
Operating Temperature -22 to 122°F (-30 to 501C) Certifications 11L 61. tj!- 916, UL 86')A. UL 3141 IPC S1,
Operating Humidity (RH) 0-100%
Emissions f-UC Par! IS (-Iw;s a
Maximum Elevation 3000m
Other NU i 'cotmAmnt nsted isower Control
Sy;t,±in for loari inanagemeni
Environment Indoor, outdoor
S173/aN
"
"VN �� V, -PAI � f
'A, , .10
I
All spoofeat oro, and doscrpfons Camp nod in d,rs document are secumte at tie firrio of
cub6ca5un In the viurest of a Out miprovemenicier us
t SPAN resees the. roh-z to cook-
rw
product coup scorers ah any i,mc -thout a&avco notics,
For ft latest SPAN product and nchbipiiron, docuinerns, visit
For actors or orrassons contact Support gspan a
For complete' product spor�llcs,6,crs and infornnatort on product kstng; and cerhfication,
refer to Inc Product Dwashett at wom, soan .L
Ail installat,ors must co1orn to tht laws, regulario.1s codes and standards app4oado 'n fire
'.np&ctmi of ostaiatlix, Before starting anostallation, consult a bcas shirking or elec'sical
ineNc,o, for Current equ.no-nents Local codas mat .-any 'lot are adopted and enforced !a
promote safe electrical ins'alpnans A zermit may be: recdcd to do and some
coijes ropy roqurc. On wsipeci'On of "I'e elect, car 'Nork
Jurisdiction Code
United States National Eielncal Code,ANSkNFPA
SPAN asownes ire iotorb, fir lary or amport, denriage duc to or scroco InWARNING Risk of clecioc shock. Risk of fir,: Only qualifedviectrcal personnel
-�
attempted , unqualified nd,,d�lilf or due to failure of insokliors or SON cc tCchnO'ans to A should arc all, source':. of felsiacu, too equ, P Mht
propurty follov, safety iiistarlation and scirv,ce nstrucrv!�s WARNING Risk of douthc crock Apply apncure ate forsoral protective
� 2021 SPAN 10, h,All rirni resoNco
All nf(:,rnra1,rc!,, ir th s docarriGrn;s correct ',a copyught and Other rintill swat plopurb, ngths
of SPAN iCt riC T!,,;s c-rawful -nav rot pomcrd�fcd, reproduced or soared, stared in a
fa,!Ouvio syonic, or Oanscmt,"j, mi whole or r, par- ot,thour of
SPAN r0 Adis tonahnformat chs available Upon request
Trademarks
Too fialomrg are tradOma,ks or og,51crud tradurnwks of SPAN cx, Unite States and
other pou,ri es
SPAN SPAN 10 SPAN Pa,;ei
All other radennano, in Me document are the property of tire I respect ve ovinon, and their
use .unfit does not imply' onsforsennom of thrnr producis or serces The unauthorized use
of any track -nark 6stipryed;- hits document or on tie p.,oduct 0, toni'1y prohibited
Electronic Device Waste Disposal
Proper disposal of demonic aqua; ,merit is rcquzred. Refer to local codes for disposal
requirencrents To ansingo, for omper disposal of this sieduct. co,rac; your local aut"Orltras
or dearer for proper dsprsal requiremcrits
Warranty
To secure the full Product Cvana"h r the: SPAN Parel must be fugstered 'of Completing the
comrnisslani^,, process wopo sands to SPAN For co,ieuslic souranty
,nformar-of, refer a the Product Warranty alovm span z
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Fullw, these tnstruct,onS diffirg r1jamtentoice and occerrom', of too, uquipmeot
This sect cor, contains safetyrorancialw friar must se observed at all orris wher works g on
0' USIN the
In Case of Fire or other emergency:
If safe to do so, switch off the nrais* or upstream icireafcr for the panel
Contact me fire deparv-cont or a' ner =Nquired emergency rospo"se town
Euacuahe the area and start Gthcrso the area
In case of unusual noise. smidt or smroke;
E,:stoc noterng s in cents,:!, win ins SPAN Pane) or other Cqojprno^f
Ventilate the space
Comas. your Ipswilor or SPAN Customer Support.
Symbols Used
Threiv sVmbors hid,calc mcnant safeu,rformatoin in the documclutartc, or on' the
equ conont
WARNING Ind,Nres a tctuackon covere faIve to use,
proper materials may Do a sarfoly oizard that may result n serious indry
ICSs Of ffc. Or LICStroCtOn Of hqU!p$nQnt Use caution and do riot prouced until
the indicatuni condinors fe, required proceduros art, f0y understood and,ricl
CAUTION ind rates a siluaton r0here failure to falfev,n5cuct Qrs or use
proper ioif on ol
Is rnav he a sarety hazard that mav result ri minor in).ry or
damage kj equip-noot Do eio: proceed wtl the .ixficatcrd ocinditcons or
toqu:nid pronchures are fortly understood and mot
NOTE 11rcoates an -otportain step or ado trx'aI,nfo,n-soioo that
best prannOvs o, procoduros f'ollois inrurt an's Carefully
RISK OF ELECTRIC SHOCK, trrdicmfcs co,mponer-, twat PLse;rt r sk of
ele'lor, shock
PROTECTIVE CONDUCTOR TERMINAL 4,dica:ns local an Of grounding
coilneul"Iq On tne vuu;PnNik'
REFER TO INSTRUCTIONS ffol,Lahts trial user should nfor to operating or
instalbit'Gr-iciructio-s before conceed rig
ATTENTION Read all r,strucirams and cautronary hrarii9s iri,Ns doeurriont and on the
Qqu patent before =istaffing the SPAN Parci, Failure In do so opiry result in equPment
damage oleciric shock, serous ni or ics& of J,fo Fa,krig to fdflov� ahy Of those
Inir structions -nay also tad Inc llarraih,
SPAN 1-00800-xx Installation Manual (rev, 2022-05-30)
equipmont fPPEI prof folkri, safe. oloctnoal work practices Cauca nstallat or) and
service Turn Off all cocror suppty,g tim equicrno,t before,,.Otrking on or ir&do
equtpri-to,it Arvaar,s use, a properly rated voltage sens.og device to confirm oowpr
s off Replace all devees, covers and doors toefore tpm,ng on o0war to the
equ'prnerit
WARNINGS To protect the equipment and its componcrits front damage other,
trans;;ching, randlO .site care To helnorcl c,.,,t damage, leave all equipment imts
sh,ppirg packagrig uhsht a ready to be ,nslal]Ld
WARNING: Insooet the equ;Pment for damage before nstai6rig Donot install rc,
&qwpu sop rf,t has poor, damaged in any way.
WARNING Do noi an foreign onticts,Ino any part of the cqu,lorient
WARNING Do not a,qaC6v The, equatow,t or any Of v',s comeownts to direct
f1ame
WARNING Do 1101 at',QTT1PttU open daassemblO L;Da;f 'Lampe.' N'th, or modify
the hqu,joiliult orner that- Alat's aec:ndtod in this niahoo The squip'ne"t
COOMOS PG UScr-seraoeabrc, parts O1hCf.ha1 frold-th'Starild Ctrodit brnaaars
Contact tho :, Ihailhr 1,110 ;nnalk,"I the eau'prilerit for airy ruzafs
WARNING Do na rormiuct life-support syeronm -,,y1L,rncOic-W Lquipmeni, Or
any u1no, use vo,em infeduct failure could load tompry lu persons or 13ob of tire
,a c,rcu;% wlfccan ce remotely srlcnod.
CAUTION. Donor use solvents to dvan nie eu,1rp,,nLrrt or expose the qu:phnQnl
to flairimatec Of raish chemicals or vat-rs Do no! af!ov, oUirvicurn-posed paints
solvcrits, or scrays to co,-,lact ou,notall;c parts Of the equipment
CAUTION Do not use parts oraccussurres once, fhoon mose svecfied far use
wirt, the equomort
Installation and Use
WARNING Risk of elhcmc shack Risk of frc, Only use elcOnicif stecorn
C."Ponents approvc d far wet ktcwore.
WARNING, Risk of clectoc shook Rick of tire Ensure tat ail rkv,ng is comext
and that once of :tic mros are perished or damaged
WARNING Risk cf eleckti; shock RisO of fire Sakai, makirg any cormoctcos
verify treat the c,rouittereakeusi are,ri lot, off posrwri Coub3ccoccl, all wrr"'g
before appilorig power
WARNING Risk of crecaic snocM lmoropL, sonars-ng of the cqu pment or is
comporronts, copy result n a rsk of snocvc at fro To reduce mosc, rNks
disconric"t oil u:;Finc' Oster , ,, athe"icting any rnarrhanance or prep cf;nq
WARNING Rsk of clectuc shock Always do-ontraizc fle equipment bofoic,
scNicing INhile ccihector, are ratof fo,1sco,ied u-der load, r,!s cast practice
to do-ururgrze before dscornccfing
WARNING Risk of eleckc stoCk Do not use cqu,puncnt in a rui,,no, not
spt,crified by the manufacturer. Derrig so may cause sniury Or loss of life or
damage Tdieluirpnicnit
WARNING Risk of clear c shock . To mrkntav, the Aaaaoty donolmrrd;orthe
doadfro, q mbef than to rurnow filter Oates As needed
e'r, % NOTE The equipment is intended to OPufato Wflu a connect on to the, thrums,
'0� Foible to marpdt ,r an nhjfnet uchnuctiot, nta, irrivact zurformoh co
NOTE This device cornplieswth Fiat! ';sat ;tic FCC RuIcs Opefator—sunject
lathe foliowirg two cofid,for's i ' ; This devee may riot cause iowinful
rnterfcrunce, and t21the de,ou must acr:Uyt any mtorferelce reserved 'n.ricdog
nterforcoce crs,ray cause undesired otteration Cnanqck or Owdificanons no'
expressly aporoved ist the party oispens:Dle for compliance i;wfiJ vad thn riser a
aumornO to oproad, the equ:prri-t
Environmental Conditions
WARNING Tms Cerro ', -
Onto intended far oferatione, an envusimenthaw;ng a
mm, mru r, icorceraturd, of -30'C ; -22 F, and a rckur, much
temperature of 5� C ; Q2 FI
WARNING inscaJi the equornert in a tocator that prevents damage from
fooding Ensure that rip oator sources are a L or near the oqurprcwru'
ricludniq dcow.sketuts. sprinkfurs, or faucc`s
ABOUT YOUR SPAN PANEL
PREPARING TO INSTALL
and -�-Isoectk---7 0lanc."!
-On�g, ,,he insuil L o m:a,
INSTALLATION
E ;cP , zi na,�,, el ,, Sef,Li�rf. 11 e r
I Selecting,
�v 0 pa n knng .1
6, ""11-,.'l')i�;',ZLI�-ii;,'`f, the Dotiwr Svvip,,,
7, instakin�-, Rush N;Iounll: Trim K�?
8, Rnai ,nvsnect!cimp anci zi-te U'fir"T
TROUBLESHOOTING & SERVICING
APPENDIX A: CIRCUIT BREAKER COMPATIBILITY
APPENDIX B: SURGE PROTECTIVE DEVICE COMPATABILITY
APPENDIX C: MAIN LUG PART
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 3
The SPAN Panel is an intelligent breaker panel with integrated connectivity, monitoring, and control for home loads, solar PV generation,
energy storage, electric vehicle charging equipment, and the utility grid. SPAN is wall -mounted and sirnilar in size, weight, and
configuration to traditional electrical panels, allowing it to be installed in place of a typical 1201240VAC bf eaker panel using standard
tools and materials.
SPAN Panel installations can be designed to support both DC -coupled energy storage systems (where the solar generation and battery
storage systems are managed by a single inverter) and AC -coupled systerris (where the solar generation and battery storage systerris
each have their own invertei). See Storage System Integration Manual for complete details.
SPAN Panel with door removed (top), deadfronL removed ,bottom)
SPAN I -00800-xx Installation Manual (rev. 2022-05-30) 4
Inspect the packaging and SPAN Panel for damage. Ensure you have received The following components:
• SPAN Panel (with main bonding jurnper pre -installed) and door (packaged separately)
• Getting Started car d (with instructions for homeowner to download SPAN Home App)
• Breaker label schedule sheet
• Accessories:
• (1) Conduit hub closing plates (SquareD ACPCP) (pi e-installedl
• (2) SquareD service entrance bat t let covers (pre -installed)
• Squat eD 200 A main breakei (pre -installed)
0 Spare fastener kit
JAI
' --C, "
WARNING: If the unit is darnaged in any way, do not proceed with the installation, Contact SPAN for further instructions.
IS g
WITURTUICTTITAUNT mp,
The SPAN Panel requires at) inter net connection to enable monitoring and control features, and to receive the latest software Updates.
Be sure to register the product to establish c0runlUnication with SPAN. Failure to do so may affect product performance or affect the
terms of the warranty. If a Wi-Fi signal is not available at the install location, establish an Ethernet connection between the SPAN Panel
and the custorner's router. Cellular LTE Should only be relied on as a backup connection.
Required Equipment
• Branch circuit breakers for load and generation circuits. See
• Main breaker (100-200 A) using SquareD type QOM2 breakers
• Conduit, concluit fittings, and SoUareD A-Sej res threaded conduit hub suited to the installation
• Four #10 lag bolts or screws, 3 inches long (depending on attachment wall) for panel mounting, and washers (for use
between fasteners and enclosure)
• Conductors rated to minimum of 75'C. See table below and markings on breakers for acceptable wire gauge.
• Cable for communication between the SPAN Panel and solar inverter(s) (Minirriurn 300 V rated, shielded, twisted -pair,
copper, 22-16 AWG)
• Smat tphone or tablet with SPAN Installer App for coal missionin.-
Personal Protective Equipment (PPE) should be worn by all persons at the installation site and properly rated for residential applications.
MMIMMU=
• Torquing tools capable of 20-275 in-lbs (2.3-31.1 Nrn)
• Allen bits (3/8-inch and 5/16-inch)
• Phillips, slotted, and square -drive driver
• Standard installation tools: wise cutters/strippers, rnultirneter, stud finder, level, tape measure, market, and flashlight
NOTE; Verify that the site mechanical, electrical, and clearance requirements outlined in this document and the product
datasheet are compatible at the planned installation location.
e/k,' NOTE: install only compatible circuit breakers, herbs, accessories, conductors, and other accessoies, Failure to do so may affect safety,
product per foi mance, and may void the warranty.
NOTE: NEIVIA, 3R rated conduit fittings are required for outdoor installations.
NOTE: For 22 kA short-circuit rating, branch breakers must be series -listed with the SqUareD main bi eaker. Otherwise,
rating will be 10 kA
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 5
Electrical, Mechanical, and Environmental Requirements
• The SPAN Panel is service entrance rated. When used as service equipment, primary overcurrent protection for the site is
i equired in the forin of all installed main lot eaker not to exceed 200 A.
• The SPAN Panel is intended to be walknounted between studs (2x4'or equivalent) with 16-inch spacing, using all 4
mounting points. It is typically mounted semi -flush, so the front of the unit extends slightly beyond the SUrface of the wall.
• Verify
y that the wall construction is adequate to support the weight of the panel. The installation should conform to applicable
building codes. Consult a structui at engineer slid local standards for 10(al mounting requirements,
Site Electrical Service
Service Feed
Intel nat Bussing
Overcurrent Protection (Main Breaker)
Location
Ambient Temperature
Enclosure Dimensions
Flush Trim Kit Din -tensions (on wall)
Weight (without circuit breakers)
I �
240/120 V, 60 Hz split -phase
200 A maximurn
225 A maximum
100 - 200 A
Indoor or Outdoor (NEMA 3R)
-22°F to 122'F (-30'C to 504C)
998 x 362 x 153 rnrn (39.3 x 14.3 x 6,0 in)
1123 x 405 min (44.2 x 15.9 in)
34 kg 175 lbs (38 kg 184 lbs fully Populated with breakers)
CAUTION: Follow all local codes and standards when planning for and installing the SPAN Pallet.
CAUTIOk Do not exceed panel capacity. Ensure that the installation conforms to applicable code, and that appropriate
overcurrent protection is in place.
Dimensions, Clearances, and Access
• Do not install the SPAN Panel neat- an erneigency exit or other building evacuation route.
• Do not install the SPAN Panel in a location or place any objects near it that Would prevent its door from; opening to 90',
or that would restrict access to the unit,
• Do not mount objects on the wall within the minimun-, i eqUired clearances indicated below, with the exception of items
required by the installation, such as electrical conduit or junction boxes,
• Do not recess the SPAN panel beyond the door hinges,
0
,7--Z
NOTE: The door may be configured to open from either direction. Ensure door may swing open to 90' per NEC 11 0,26(A)(2)
. .... ....
SPAN 1-00800-xx Installation Manual (rev, 2022-05-30) 6
Accessories
The following accessories may be used with SPAN Panels
SPAN Main Lug Assembly
SPAN PN: 1-01934-01
SPAN Flush Mount Trim Kit
SPAN PM 1-01046
SPAN Networking Kit (for InUlti-panel sites)
SPAN PN: 1-00921
Service entrance barrier cover
SquareD PN: PKSB I HA
Top hub closing plate
Squaf eD PN: ACPCP
Top threaded conduit hub, rainproof
Squai eD A series hubs
Filler plate for branch bi eakei knockouts
Squate[) PN: HOMFPCP
Add -on Neutral I GND lugs (Field- installed)
ILSCO NOST-2/0
Squas,eD HOMIOOAN
GE TLK20
Add -on GND bar kit (Field -installed)
UL Recognized ground bars may be installed by tapping threaded holes in
the SPAN Panel enclosure, according to NEC requirements,
Powerline Ethernet Adapter Kit
Recommended options:
TP-Link AV1000
TP-Link AV600
SPAN I -00800-xx Installation Manual (rev. 2022-05-30) 7
# Using a flat screwdriver, loosen the single deadfront fastener so ew and i ernove the deadfront cover.
• Ensut e the wait space can accommodate the flush section without interference frorn pipes of conductors inside the wail space.
• Using a drill and level, mount the SPAN Panel enclosut e on the wall, observing site and mechanical requirements, and
applicable building codes. Secure the unit at all 4 mounting points.
• When flush 1110LOnting. drill pilot holes, marked by interior markings of the panel. Install fasteners through the side walls to
secure the panel to the studs, as shown below.
Wall Mounting Points for Surface -Mount (left) and Flush -Mount (right)
WARNING: Risk of electric shock, if you are replacing an existing electrical panel, make sure power is turned off before
removing the old panel and when installing the SPAN Panel, Always make sure all electrical equipment is safely de-
e energized before beginning wot k
ne�
CAUTION: The unit must be installed within 10 degrees of vertical, and level from side -to -side.
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 8
• The SPAN Panel allows conduit entry tht ough the top, bottom, lower sides, and rear section of the panel.
• Foi top conduit entry, install a SquareD A -set ies tht ended hub.
• Before removing knockouts, plan conduit routes and corresponding knockout locations and sizes oil the enclosure. Be sure to
allow adequate clearance for conduit routing and anchoring. Conduit installation must comply with applicable fill limits and
electrical codes,
Allowable Conduit Entry Locations (shown in blue)
CAUTION: Do not punch conduit holes in any location on the enclosure that would allow moisture to enter the unit,
CAUTION. Follow guidance in NEC Chapter 3 and any local AHJ t equirernents for cable type selection. Consider extet ior
surface and flush triounted installations as wet/damp conditions and use conduit accordingly, When installed in wet/damp
locations cable routed through the bottom face must be wet- or damp -rated,
NOTE: Additional conduit holes can be punched in the top sections of the panel. Note the locations of antennas and wires
inside the panel before cutting. Be careful to keep metal shards from coming into contact with any energized parts. Use
appropriate fittings for the location.
NOTE: use care when drilling and confirm that fittings are the correct size and N E MA t acing lot- the installation location
before proceeding.
NOTE: When top Conduit entry locations are not used for wire entry, it must be seated pi opeily with top hub closing plate,
SPAN I -00800-xx installation Manual (rev, 2022-05-30) 9
Verify Neutral -to -Ground Bonding
• When used as service equipment, ensure the factory -installed main bonding jumper is securely in place,
• When not used as service equiptnent, i emove the n-tain bonding jumper.
tF'
A
WARNING: When the SPAN Panel is not installed as service equipment, the factory -installed main bonding jumper MUST
? Ground are properly bonded at the upstream service equipment.
Xr be removed. in this case, ensure Neutral and Gi
_0
CAUTION: Do nor rnodify car rewire any factory -installed mm connections except the ain bondin-jupet,
NOTE. When the SPAN Panel is installed as service equipment, ensure the panel's main breakei is appropriately labeled
as "SERVICE / MAIN DISCONNECT"
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 10
• The SPAN Panel accepts a 100-200 A main breaker and up to 32 branch breakers in the panel for load circuits.
• Install each branch breaker byrocking it down to seat it fully onto the bulbar stab and engaging the clips that hold it in
position. Ensure each breaker is firmly in place,
CAUTION: Install oi -ily listed and labeled circuit breakers compatible with the SPAN Panel, Branch circuits Most not exceed
the load lin-rits specified below.
General Use
90 A
Full Load Inductive/Motor Amps
60 A
Locked Rotot Incluctive/Motor Amps
270 A
Breakers Listed for Use
SPAN is tnUlti-listed for use with 1 -inch (2,54 cm) standard, tandern, AFCI, and GFC1 branch rii cult breaker s frorn Siemens/Murray, Eaton,
and Squarel) types listed in table below. See Apia, i , -errd-i-x A for complete details on breaker cornpatibility and shot t circuit ra ting,
• Squared type HOM, HOMT
• Eaton type BR, BD, BQ
• Siernens/hAurray type QP, QT
SqUareD QOM2 type:
* 100 A QOM21 OOVH
0 125 A QOM2125VH
* 150 A QOM2150VH
& 175 A QOM2175VH
* 200 A QOM2200VH
* SPAN Panels trantifactured with Serial Number (SN), xx-2223-xxxxx lmiddfe 4 dipts) and higher are not compatible with any
plug -on neutral style branch circuit breakers, When AFCIIGFCI branch breakers are required, a pigtail neutral breaker style
must be installed with the neutral pigtail wire connected to the panel's neutral wiring terminal bar.
CAUTION: Use only appropriately sized, compatible circuit breakers according to the type of load. Ensure breaker selection
is in accordance with NEC, CEC, and local code articles for any field modifications. Additional or replacement bt eakers
should be of the same manufacturer, type designation, and equal or greater interrupting rating.
CAUTION: Refer to the specific breaker location instructions for each grid -forming hybrid inverter in the Storage System
Integration Manual. Hybrid inverter breakei (s) must be connected to the position(s) indicated for the system to operate
as intended,
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 11
Installing a Main Breaker
The SPAN Panel must have either a main breaker installed (see above for compatible main breakers} or a SPAN Main Lug Assembly (PN:
1-01934-01). Main breakers and Main Lug parts may be field installed according to this manual,
To remove:
To install:
Remove the two (2)1 1 /12 fastening nuts using a 7/16-inch hex socket.
Remove the fastening screw using a #2 Philips bit.
Slide the main breaker or inin lug kit downwards,
Insert
the main breaker or main log part as show below.
Install the (1) Phillips 4i2 fastening screw, torquing to 31 in-lbs (3,5 N-its),
Install the two (2) fastening nuts and washers, torquing to 45 in-lbs (5.1 N-m) using a 7/16-inch hex socket,
4191
7@1
L
Fastener Torques for SPAN Main Lug Part
NOTE: Use a torque toot to avoid over -torquing the main breaker fastener s,
r, CAUTION: Maximum CLO-rent rating of the main breaker and main lug configuration is 200A. Bussing is rated to 225A.
k�111
SPAN 1-00800-xx Installation Manual (rev, 2022-05-30)
IN
Size all conductors with reference to the overcurrent protection device, ampacity, and voltage drop requiremients in accordance with all
local electrical codes. Use conductors rated to minimum of 75'C.
• Connect Supply-side Line 1 and Line 2 conductors to the inain breaker terminals.
• Connect supply Neutral and Ground conductors to their respective terrnina# blocks,
• Refer to the table below for suitable conductor gauges and torque requirements.
• SPAN sub -feed lugs are fated to 200A max.
WARNING: Risk of electric shock. Check that all circuits are de -energized before wiring including generation equipment
such as solar inverters and storage batteries,
0' CAUTION: The SPAN Panel is only intended for use on 1201240 V split -phase electrical service.
• Connect Line conductors for all circuits to the respective breaker.
• Connect Neutral and Ground conductors to their respective wire terminals,
• once all conductors are connected and secured, check that there are no exposed conductors or stray wiles. Clean tip
conductor routing to ensure no wires will be pinched when re -assembling the autotransformer cabinet and deadfront
assembly.
NOTE Keep track of circuit labelling. This infot matiort will be required during commissioning,
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 13
Terminal Wire Gauge, Strip Lengths, and Torque Values
Main Breaker See instructions on breaker
SPAN Main Lug Part #6 - 250 kcind 125 in (32 nirn) 3/8-in hex 250 (28.2)
Main Neutral & Main GND ter nninal #6 - 250 kcrnil 1.25 in (32 rnni) 3/8-in hex 250 (28,2)
Larger Neutral tern-iinals #14 - 1/0 0,75 in (20 rni-n) 5 nirn 35 (4,0) for '04-10
slotted 40 (4,5 ) for #8
45 (51) for #6-4
50 (5.6) for #3 -1 /0
Stiiallet-Neutiaite4,tiiir)als& #14 - 4 O5 in (12 min) 5 111n) 20 (2.3) for #14-10
GND terminal block slotted 25 (2.8) for #8
35 (4,0) for #6-4
Feed -through lugs (0/1-2) #6 - 250 kcinit 1,25 in (32 nirn) 5/16-in hex 250 - 275 (28,2 - 31.1)
NOTE, Torque circuit breaker terminals to values specified on the breakers.
NOTE: Terminals integral to the Span panef are suitable for 60/751C AUCU wire. Refer to circuit breaker markings for
breaker tei rninals'temperature rating.
SPAN I -00800-xx installation Manual (rev, 2022-05-30) 14
• Use mimmurn 300 V rated, shielded, twisted -pair, copper conductors only for communication wiring,
• Connecting the SPAN Panel to the Internet with a wired Ethernet is strongly recommended.
6
\�4 NOTE: To insert wiring into RS485 terminal, use a 2mm flat head driver to depress the tab while inserting stripped wire.
SPAN I -00800-xx installation Manual (rev, 2022-05-30) 15
To configure the door to open from the other direction:
• Using a #2 Philips driver, remove the 2 hinge brackets and 2 latch brackets from the enclosure,
• Re -install the hinge and latch brackets on the desired side, tightening each screw (2 per bracket] and torque to 26.5 in-lbs (3
Nrn).
• On (he inside of the door, remove and swap the mating hinge and latch hardware, and re -install and torque to 26.5 in-lbs (3
Nrn),
.41
9.5
�� 1
Swapping Door Mounting Hardware
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 16
The Flush Mount Tun) Kit(PN: 1-01046)is used fnr indoor installations to easily cover square holes cut into the wall duo it
Tice overall dimensions when Inputted are 1123 x 405 mn-i (44.2 x 15.9 in).
• Place the two (2) metal Trim Mounting Brackets directly against the SPAN Panel's top and bottorn faces, using the triangular
decals to center.
• Affix the upper and lower Trin-) MOUutirlg Brackets to the wall of stud using four (4) mounting screws.
• Snap the Trim Piece in place, ensuring all fOUr mounting sockets are fully engaged.
V W
Installing Trim Mounting Brackets
Snapping Trim Piece in Place
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 17
• Confirm that all connections are correct. pi operly grounded, and secure,
• Replace the deadfront and securing using the flathead screw,
• Install the door by sliding down onto the hinges-
• Only after fully replacing the deadfront as5ernbly, restore power.
• Lock the panel closed with the hasp at the bottorn of the panel door using lock provided by the horneowner,
f;> WARNING: Risk of electric shock. Do not n-todify the deadfront other than to configure the door hinges or to remove or
replace breaker fillet- plates, as needed.
,oC R
The Panel must be configured with the SPAN Installer App prior to use.
Download the SPAN Installer App from _ ,, � _ c, . �, -
Follow the on -screen instructions. When prompted to connect to the panel, refer to the panel Serial Number located on the product
label inside of the door.
/0 NOTE: When SPAN's relays open/close they will sound like a digital carnera taking a photo. When SPAN transitions on- or
off -grid, several relays may open/close at once which sounds like a digital carnera taking multiple photos. This is normal.
SPAN Installer App home screen
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 18
For additional troubleshooting and support visit
Follow these troubleshooting steps to establish communication and verify operation of the SPAN Installer App:
• Wait at least 3 minutes after powering on before attempting to connect to the Panel.
• Ensure the panel is connected to the inter net, using the Installer App.
• Ensure the battery backup system is communicating with the SPAN Panel using the Installer App.
• Ensure all circuits and circuit locations are correctly identified In the Installer App,
• To i estart the systewi, press and hold the Reset button for 10 seconds (see "Resetting the Systern" below),
For further assistance, contact support@spanJo.
WARNING: Do not attempt to open, disassemble, repair, tamper with, or modify the equipment. The equipment contains
no user -serviceable parts other than field -installed bi eakers. Contact the installer who installed the equipinent for any
V-0 repairs. only qualified electrical personnel should remove the deadfront panel.
Status LEDs
Main newel
Om
Green
Solid
Main PCBA powered
Off
Off
No AC power to panel
Fault: Hybrid inverter and/or
Green
Solid
in autotransforer autoinaticaltv
Warning
A
disconnected from main bussing.
Off
Off
Normal operation
Green
Solid
Grid voltage detected
Grid Status
Off
Off
Grid voltage not detected
Gi een
Solid
Gateway PCBA powered
Gateway Power
Off
Off
No power to Gateway PCBA
(Future Use)
x
(Future Use)
Y
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 19
if it becomes necessary to restart the system rise a sniall tool to press the Reset button, located below the CrinlroUnication terminals.
Hold the button for 10 full seconds before releasing.
if it is necessary to manually reconnect your horrie to the grid, SPAN Support may direct YOU to operate the manual override in
the SPAN Panel,
• To reconnect to the gi id manually, peel away the protective label, insert a large flathead screwdriver, and turn
counterclockwise until you beat- a click.
CAUTIW Do not rernove the protective label or operate the manual override unless directed to do so by SPAN Support.
_"v' Impt oiler operation of the manual override may damage the unit.
Branch circuit position numbers are labelled adjacent to the breaker. A specific space location can be associated with the physical circuit
position in the SPAN panel by viewing the space in either the SPAN installer or SPAN Home app,
To add, remove, or change branch circuit breakers:
* Follow instructions above in this rrianUal to select, install, and wire circuit breakers.
* Use the SPAN Installer app to make changes to the of anch breakers, following on screen inso uctions.
Homeowners should be instructed to contact SPAN Support for any future branch breaker additions, removals, or changes.
CAUTION: To per routine service or maintenance on circuits, confirm that the con esponding Circuit breakers are
switched off. Powering down Circuits using the SPAN internal relays should not be considered a suitable Off position for
servicing equipment,
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 20
SPAN has been evaluated per the UL Standard for Panelboards for use with the branch breaker types below in Table A.I.
informational notes:
• National Electric Code (NFPA 70) does riot prohibit the use of different branch circuit breakers in panelboards provided it does
not violate the listing of any eqUiprinent. NEC article 11 0,3(B) states "Equipment that is listed, labeled, or both shall be installed and
used in accordance with any instructions included in the listing or labeling, "
• The standard for Molded -Case Circuit Breakers (UL 489) does not require listing circuit breakers for use in specific panel, riot
does this standard cover panelboards. Such testing is covered by the UL standard for Panelboai cis ( " UL 67), which does require
the panelboard to be listed with specific breaker types. SPAN is certified to the UL 67 standard via a Nationally Recognized
Testing Lai) (NRTL) for use with the branch circuit breakers below. This is reflected in this installation information as well as
riarked on the product itself.
For additional information visit,%v, v, :Il' ;i,,
Table A.1
Series Specified Main Breaker Specified Branch Breakers
Rating
Amps Amp Manufacturer Catalog Manufacturer Style
Ratings Numbers
22,000 100to200 Square QW21,25W, Eaton
QON!2125VH,
QOM21 SOVH,
QOM2175VH,
QON12200VH
Murray
SPAN 1 -00800-xx Installation Manual (rev. 2022-05-30)
General
Duplex (tandem)
Quadplex (tandem)
Combination arc fault
Cii-G-Jit 1r.-terFUptet'
(.AFC!}
Ground fault cli cuit
4iterrupter (GFCI';
Type
Poles
Max
Catalog Numbers
Amp
BR
i, 2
90
BR or BRH 1'ollwwed by I 10 to
290
BD
K
BlDfollovved by 1010to 5050
BQ and BQC
1,2
50
BQ followed by 2152", 5 zo
2502120
BR
1,2
20
BRN, GRC,o, BRL fofloviied by
110 to 1261;foirowed by AF at-
CAF
GFi CS and
1,2
60
BRN, GFTCB, BRHN, or
GFEP
GPTCBH. foliowed by 1 110 to
Ground fault GFEP
equipment protection
DUai function BR
combination ground
fault and arc -fault
Protection
General TOP-T
Duplex {tandem) loH-T
Triplex (tandem) MH-T
Quadplex (tandem; NIH-T
Branch -feeder arc fault MR-AT2
circuit inter-upter
Combinadonarc fault MP-AT2
citcult inter uptei
(AFG)
Ground fault cit cuit &1P-GT
inter i upter (GFCI)
260; may be followed by GF
1, 2 50
BRN or GFEP fiollowed by 115
to 250; may be followed by
FP
20
BRN or BRA,'GF followed by
110 to 120; may be followed
by DF
90
MPOI-MPH f6fowea byllO
to 2Kmay be followed by
KH
11 311
MP followed by 1010 to 3030�
may be followed by N
1,2 30
MP followed by 21010 to
25020
2 40
NIP followed by 21515 to
24040: followed by CT2
1,2 20
MPA followed by 115 to 120;
followed by AF: may be
followed by H
1, 2 20
NIP or MPA followed by 110
to 220; followed by AFC,, rnay,
be followed by H
1,2 60
MP followed by 110 to 260;
followed by UA; may be
followed by H
21
Siemens
Square D
(Homciine)*
Dual function
PIAP-G
comb;nat,or� ground
fault and arc -fault
I
protect
General
QP
Duplex �Itandeml,
QT
Triplex ?tandem)QT
Quadplex {tandem)
QT
Branch -feeder' arc fault
QAf:2
circuit interrupter
A72 1
Combination arc fault QAF and
circuit interrupter QAF-2
(.AFCI)
Tandem combqnaTron CAPO
arc fault circuit
interrupter (AFCk
Ground fault circuit QPF and
interrupter (GFCI) QPF2
Ground fault QE
eqWpruent protection
Dual function QFGA2
ccoo.bination ground
fault and arc -fault
protection
General HOM
Tandem (duplex) HOW
Quad (tandem) HONIT
1,2
1,2
2
1,2
2
1,2
1
1,2
2
Combination arc fault
1-10%I-CAR 7, 2
Circuit interrupter
(,AFCI)-
Ground fault circuit
HONI-GR 1,2
intetrupter(GFU
Ground fault
HOM-EPD 1, 2
equsprnent protection
Dual function
HOM-DF I
combination ground
fault and arc -fault
protection*
20 NIP followed by 110 to 220;
followed by DF; may be
followed by H
90 Q followed by 110 to 290;
may be followed by H
Sri}Q rollcrwed by 1010 to 3030
nay be fo!lo�eed by NC
30 Q followed by 2 1, 010 to
2-3030; followed by C-T
40 Q followed by 21515 to
24040; followed by CT2
20 QA followed by l 15 to l 20�
followed by AF; may be
fo
llowed by H
20 Q or QA 'oltowed by 110 so
2201; followed by AFC; may be
followed by H
20 Q followed by 1010 to 2020;
followed by AFC
60 QF followed by 1, 10 to 26U
followed by A; may be
followed by H
60 QE followed by 115 to 260;
may be followed by H
20 Q follcroved by 1 ' 10 to 120;
followed by DF; may be
followed by H
9(j HOM followed by 110, to 29,^j
30 HO MT followed by 1; 010 to
30201
50 HOMTfoiiovjcd by? 515215
to 2020250
50 HOME folio -wed by 215215 to
E0250
20 HOM followed by 110 to 220;
,ollowed by CAR
50, HOMfollowedby 11 r- to 250;
followed by CR
50 HOM fokwed by 115 to 250�
followed by EPD
20 HOMfollovied by 1110, to 120;
f ollowed by DF
10,000 None n/a me All specified All specified types
(Marta Lug; manufacturers
'SRAN Panels manuaactured with Senal Nurnber(SN)xx-2223-xxxxx (middIe4 digits) and higherare not cornpatiblev,,ith plug -on neutral style branch circuit
breakers, and pigtail neutral breaker styles must be inszalied. SPAN Parcels with Serla@ Numbei (SN) xx-2222-xxxy.x (middle 4 digits} and lower are compatible
with SquareD Homellne plug -on neutral, as indicated by catalog numbers:
• HOV. followed by 110 to 220; followed by P: followed by CAR,
• HOM followed by 110 to 251v; followed by P: followed by GFI.
• HOM followed by 11 Oto 120; followed by P; followed by DF.
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 22
Per 2020 NEC 230.67 Surge Protection
• A surge protective device (SPD) shall be installed in all new and ieplacement services supplying dwelling Units.
• Shall be Type 1 or Type 2 SPD,
• Shall be attached to the service equipment or immediately adjacent. Exception: The SPD shall not be required to be in the
service equipment if located at each next level distribution equipment downstream toward the load.
SPAN is compatible with Virtually any standat cl SPD connected to a 2-pole breaker or installed on a 2-space slot in equivalent SquareD
HOM, Eaton 6R, or Siemens/Murray QP/MP panelboards.
• When installing an SPD. mark it as an essential circuit in the SPAN installer App under Advanced settings, depicted below.
• If using an SPD with usable circuits, be sure to only have essential items on those circuits (e.g., internet router, alarms, fire
detection). Hon-teowners will not be able to turn this circuit off via the SPAN Home app.
Breaker)
2-pole (Breaker 3)
iac 0, (WV ) -,
....... .
.....
SPAN I -00800-xx Installation Manual (rev, 2022-05-30) 23
The SPAN Main Lug Assembly (SPAN PN: 1-01934-0) is designed and listed only for use in the SPAN Panel (PN 1-00200-xx, 1-00800-
XX).
Dimensions
4-7/3 x 5-1/8 x 2-118 in
(124 x 130 x 54 n) ni)
Weight
0,66 lbs (0.30 kg)
Wire Type
Copper or Aluminum (CU7AL)
Wire Gauge
�6 - 250 kcmil
Current Rating
200 A
AC Voltage (norninal)
1201240 VAC
Max lriput Short Circuit
10 kA
Operating Temperature -22 to 122-F (-30 to 50-C)
NOTE: See Installing a Main Breaker" section above for complete installation steps, torques, etc.
SPAN I -00800-xx installation Manual (rev, 2022-05-30) 24
Z.
2021-05-15
•
First revision
2021-06-04
#
Corrected product weight in spec table
•
Added Netwoi king Kit and Trim Kit to accessory list
#
Added Servicing instructions regarding breaker replacement or additions
2021 -066-21
0
Added main breaker replacement details
*
Added FlushMWUnt Ti im Kit installation instructions
2021-06-29
0
Added dimensions for Rush Mount Trine Kit
2021-12-04
•
Added Appendix A: Circuit Breaker Cornpanbifity
2022-01-21
•
Added Appendix B: Surge Protective Device Compatibility
•
Updated figure in Instal[ Conduit section to include Conduit Entry Location dimensions
0
Updated Wiring the Panel section to include sub -feed lug rating
2022-01-28
•
Updated Image and information under section "Dimensions, Clearances, and Access"
*
Minor updates to "Preparing to Install" section
2022-04-19
•
Updated breaker compatibility list
2022-05-30
•
Updated format of Appendix A
•
Added information for Main Lug Kit (Appendix C)
2022-06-24 0 Minor updates to Main Lug Part (Appendix Q and installing a Main Breaker section
2022-08-30 • Minor updates installation recomn-rendations
SPAN 1-00800-xx Installation Manual (rev, 2022-05-30) 25
Lntertek
ToW 0-1hy. Arwed
This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may
Applicant: Span,10, Inc, Manufacturer: OnCore Manufacturing LLC dba NEO
Tech
Address: 679 Bryant St_ Address:
San Francisco CA 94597
Country: USA Country:
Party Authorized To Apply Mark: Same as Manufacturer
Report Issuing Office: Intertek Testing Services NA, Inc,, Cortland, NY
Control Number: 5017188 Authorized by:
.;;_ ;� --.� --A-- —
for 'i . Matthew Snyder, Certification Manager
T us
T4-'
Intertek
This document supersedes all previous Authorizations to Mark for the noted Report Number.
This AUtban2ation is Marl, is for the etoduswe use of IntertsKsClient and is provided pursuant to the Cefificatinit, age,entem bet'�,Van Inte'tel, and itsCiienl unharzer S lestronsibility and flattioly we
lintted to the ;error and conditions of the agreement Irtepek as-to-ne, on liability to art, pad,, runs, than to the Client in accordance vmh the aguoeruent for any loss eupense or damage occasioned
by the use of this Averanzatotri to Mark Only the Client is authorized to pernot , copylmj or distribution stints Authorization to Mal, and then only in its entirety Use of Wistek s Certification mart is
nestriolld to the conditions laid out in the aq,aentent and m this Aulhorrzation to Mark 4" further use of dle intenek name on the sale or a&eniseneentof the tested rnster:ai product orsemce must
Brat be approved in "Ming bj Intelek Wtuil Factor, Assessments and Follo,,; up Services are for the purpose of assuring appropriate usage of :he Certification mark in accordance ,,,"lh the agreement
they are not to, hie purposes at praducoor, quaint control and do not reliese the Client of their obliclabons in this respect
Intertek Testing Services NA Inc,
545 East Algonquin Road, Arlington Heights, IL 60005
Telephone 800-345-3851 or 847439-5667 Fax 312-283-1672
Standard(s): Energy Management Equipment(Energy Monitoring Equipment)>Expires on: 22JuI2022< JUL 916,2015
Ed.5)
Product: Smart Panel
Models: 1-00200- followed by 01 or 02 or 12; may be followed by RG or IVIL or NX,
1-00800- may be followed by 00 to 99,
ATM for Report 104174176CRT-001 Page I of 1 ATM Issued: 19-May-2022
ED 16 3 15 ; 16-Oct-2021 i Mandatory
RECEIVED: 12/0812025 DATE OF ISSUANCE:
25-004572
407 TURNER RD
7
#
SOLAR PANELS PERMIT :
f-
BUILDING PERMIT AVYLIEWYMN
j
JOB ADDRESS: 407 Turner Rd Grapevine TX.,USA 76051 SUITE #
LOT: BLOCK: SUBDIVISION:
BUILDING CONTRACTOR (company name): SUNRUN INSTALLATION SERVICES INC
CURRENT MAILING ADDRESS: 2503 N BELTLINE RD STE 130
CITY/STATE/ZIP.- GRAND PRAIRIE, TX 75050 PH: # 385-491-6788 Fax #
PROPERTY OWNER: Stephanie Barron
CURRENT MAILING ADDRESS: 407 Turner Rd
CITY/STATE/ZIP: Grapevine TX USA 76051 PHONE NUMBER:
PROJECT VALUE: $ 31,144 -, FIRE SPRINKLERED? YES NO _
WHAT TRADES WILL BE NEEDED? ELECTRIC X PLUMBING — MECHANICAL
DESCRIPTION OF WORK TO BE DONE: ROOFTOP SOLAR WITH BACKUP BATTERY AND MAIN PANEL UPGRADE - EXISTING SOLAR PANELS
USE OF BUILDING OR STRUCTURE: SINGLE FAMILY RESIDENCE
Total Square Footage under roof: Square Footage of alteration/addition:
I hereby certify that plans have been reviewed and the building will be inspected by a certified energy code inspector in accordance with
State Law. Plan review and inspection documentation shall be made available to the Building Department (required for new buildings,
alterations and additions)
E3 I hereby certify that plans have been submitted to the Texas Department of Licensing and Regulation for Accessibility Review.
Control Number-. (Not required for I & 2 family dwellings)
EI I hereby certify that an asbestos survey has been conducted for this structure in accordance with the regulatory requirements of the Texas
Department of Health.
(REQUIRED FOR DEMOLITIONS, ADDITIONS AND OR ALTERATION TO COMMERCIAL AND PUBLIC BUILDINGS)
I hereby certify that the foregoing is correct to the best of my knowledge and all work will be performed according to the documents approved by
the Building Department and in compliance with the City Of Grapevine Ordinance regulating construction. It is understood that the issuance of
this permit does not grant or authorize any violation of any code or ordinance or the City Of Grapevine. I FURTHERMORE UNDERSTAND
THAT PLANS AND SPECIFICATIONS ARE NOT REVIEWED FOR HANDICAPPED ACCESSIBILITY BY THE CITY, AND THAT THE
DESIGN PROFESSIONAL/OWNER IS RESPONSIBLE FOR OBTAINING SUCH APPROVAL FROM THE APPROPRIATE STATE AND
OR FEDERAL AGENCY(S).
PRINT NAME: THOMAS LONG SIGNATURE
PHONE #: 385-491-6788 EMAIL: CALLA SPERMITT I ING@DSUNRUN I COM
0 CHECK BOX IF PREFERRED TO BE CONTACTED BY E-MAIL
THE FOLLOWING IS TO BE COMPLETED BY THE BUILDING INSPECTION DEPARTMENT—
.... . ....... _ -----
onsttin TyI : -mit Valuation: $ Setbacks Ape ,roval to Issue
Cruc-,e
Occui �aiic Group: Fire Sorinkler.- YES NO Front: Electrical
Division: Building Depth: Left: Plumbing
Zoning: Building Width: Rear: Mechanical
4
Occupancy Load: Ri,-ht: Hood
Grease TraL_...1-' 1.1.1- 11
Plan Review Ai,i °rovaj Date:
1 Building Pe it Fee:
o Site Pkui Aporo'val: Date: Plan Review Fee
Fire Department: Date: Lot Draina,_,e Fee:
Public Works Department: Date: Sewer Availability Rate:
Health Department: Date: Water Availability Rate:
Approved for Pe rrn it: Date:
Lot Drainage Submitted: Approved: Total Amoutit Due:
0:FORMSOSPERMIT
P D. BOX 95504, GRAPEVINE, TX 78499 (017) 410-3165 APPLICATIONS 1102-Rev.11/04,5/06,2/07,11/09,4/11,2119
i •
-O Box 95104
Grapevine, Texas 76099
817) 410-3166
ADDRESS
07 Turner Rd.
Grapevine, TX 76051
LEGAL
Hayley Addition Blk 1 Lot
5ra
S
Chili's Bar & Grill #207
PERMIT HOLDER
PAULJOYCE
N SERVICES INC
491-6788
ng - Residential
Alteration
1. MISC. Building Inspection 7. Building Wall Tie Inspection
2. Building Setback
! «
« « i
—APPLICANT NAME (individual)
**APPLICANT PHONE NUMBER
APPLICANT E-MAIL
VALUATION
Square Footage
* CONSTRUCTION TYPE
* OCCUPANCY GROUP
OWNERS DOCUMENTS - MISC 02
• Antony Barron * ZONING DISTRICT
APPROVED TO ISSUE ELECTRIC
Building Permit Fee, ($150.00
Flat Fee) Simple Alteration
TOTALS
1.#A4Jfffl6QtR
8. Building I
9. Building Energy Code
f • .! Inspection
11. Building
PAULJOYCE
326270330
dallaspermitting@sunrun.com
31144
211
V
-3
407 TURNER RD PLANS AND
SUPPORTING DOCU ENTS.pdf
GRAPEVINE BLDG APP.df
-5.
YES
TOTAL PAID DUE
$ 150.00 $ 10.00 $150.00
$ 150.00 $150.00 $0.00
I HEREBY CERTIFY THAT THE FOREGOING IS CORRECT TO THE BEST OF
Y KNOWLEDGE AND ALL WORK WILL BE PERFORMED ACCORDING T
THE DOCUMENTS APPROVED BY THE BUILDING DEPARTMENT AND I
COMPLIANCE WITH THE CITY OF GRAPEVINE ORDINANCE REGULATING
CONSTRUCTION. IT IS UNDERSTOOD THAT THE ISSUANCE OF THIS PERMIT
Page 1/2
MYGOV.US 25-004572, 01/16/2026 at 11:09 AM Issued by: Amanda Robeson
DOES NOT GRANT OR AUTHORIZE ANY VIOLATION OF ANY CODE OR
ORDINANCE OF
GRAPEVINE.
r
I FURTHERMORE UNDERSTAND THAT PLANS AND SPECIFICATIONS ARE
NOT REVIEWED FOR HANDICAPPED ACCESSIBILITY BY THE CITY AND THAT
THE DESIGN PROFESSIONAL OWNER IS RESPONSIBLE FO' OBTAINING
SUCH APPROVAL FROM THE APPROPRIATE STATE AND OR FEDERAL
January 16, 2026
Signature Date
City of Grapevine Building- Residential Alteration
j Project # 5-004572
NOTICES
1) ALL work must be done in compliance with the 201 INTERNATIONAL ILDIN CODE.
"ALL work ISSUED prior to January 1, 2024, must be done in compliance with the 2006 INTERNATIONAL
BUILDING CODE.
) City Approved Stamped Plans must be on -site for ALL INSPECTIONS.
3) Project address must be clearly posted at the job site.
NOTES
> 24 HOUR INSPECTION
METRO (17) 10-310, CUT OFF TIME FOR A.M. INSPECTION 17:0 A.M. --- CUT OFF TIME FOR P.M.
INSPECTION IS 1:0 P.M.
> PERMIT ISSUED IN I APPLICATION I IN THIS.
•`ate•.
MyGWus004 0111612026i :d by: Amanda Robeson
GrapevineCity of
PO Box 95104
Project"
Grapevine, Texas 76099
817) 410 3166
ProjectDescription: ROOFTOP SOLAR WITH BACKUP
BATTERY AND MAIN PANEL UPGRADEEXISTING
SOLAR
SYSTEM INSTALLED
,
Issued on: 01/16/2026 at 11:12 A
ADDRESS
INSPECTIONS
407 Turner Rd.
1. IC. Electrical Inspection
5. Electrical Underground
Grapevine, T 701
2. Electrical T-Pole
elly Steel & Bonding
LEGAL
3. Electrical Rough
7. Deck Steel Bonding
Hayley Addition Blk 1 Lot
4. Electrical Service
8. Electrical Final
5r
S
INFORMATION I
Chili's Bar & Grill #207
—APPLICANT NAME (individual)
PAUL JOYC
HOLDERPERMIT
'*APPLICANT PHONE NUMBER
8326270330
PAUL JYGE
SUNRUNINSTALLATIO
VALUATION
31144
VICES INC
Square Footage
211
(385)41-6788
DOCUMENTS - MISC 01
GRAPEVINE ELEC AP.pdf
COLLABORATORS
DOCUMENTS - ISC 02
07 TURNER LA AND
SUPPORTING DOCUMENTS.pdf
-PAULJOYCE
SUNRUN
INSTALLATION
FEE
TOTAL PAID
SERVICES INC
Electrical Miscellaneous Fee
$ 7.00 $ 37.00 $ 37.00
(38) 491-6788
_, ... __..._..._
TOTALS
$ 37.00 $37.00 $ 0.00
OWNERS
- Antony Barron
READ AND SIGN
I HEREBY CERTIFY ,, THE FOREGOING IS CORRECT
MY KNOWLEDGE AND ALL iRK WILL BE PERFORMED ACCORDING
THE DOCUMENTS APPROVED BY r DEPARTMENT AND
COMPLIANCE CITYOF -*-EVINE CODES REGULATIN
CONSTRUCTION. IT IS UND- i•D THAT THE ISSUANCEOF RMI
DOES NOT-* OR AUTHORIZEANY i OF it J
ORDINANCE OF THE CITY OF GRAPEVINE.
I FURTHER CERTIFY THAT ALL WORK THAT IS REQUIRED TO COMPLY WIT
*NY FEDERAL,S AND OR LOCAL* REGARDING ENE-
LAWS,CONSERVATION WILL BE PERFORMED IN ACCORDANCE WITH THOS
AND THAT VERIFICATION OF •rCOMPLIANCE
SUBMITTED TO THE CITY UPONREQUEST.
i
Page 1/2
MYGOv.us 25-004573, 01/16/2026 at 11:12 AM Issued by: Amanda Robeson
Electrical
iignature
P.
-25-004573
A] alibi] o] NLYA M! !,
NME
wwr�
NOTES
> 24 HOUR INSPECTION
METRO (17) 410-3010, CUT OFF TIME FOR A.M. INSPECTION IS 7: 0 A.M. --- CUT OFF TIME FOR P.M.
INSPECTION IS 12: 0 P.K
> PERMIT ISSUED IN ACCORDANCE WITHAPPLICATION IL IN THISOFFICE.
�♦ is . .f !� ,...i ! � i,
i # # # !
_.... .. . _ Page 2/2
MYGOV.US004 i ::. 1 a .. AM Issued E.Amanda Robeson