Date: July 3, 2025
Austin I Dallas I Fort «V
Attention: Emando Teixera (
Subject: Load Bearing Wall Evaluation
2715 Summer Wind Dr., Grapevine, TX
Good Afternoon:
:'edam A. Green. P.E. (TXI. MBA
CITY OF GRAPEVINE
THIS PAGE RELEASED FOR CONSTRUCTION
RELEASE DOES NOT AUTHORIZE ANY WORK IN CONFLICT
WITH THE BUILDING CODE OR ZONING ORDINANCE.
CITY APPROVED PLANS TO BE KEPT ON THE JOB SITE AT
ALL TIMES.
07/17/2025
BY: ARNOLDO RAMIREZ TSBPE: 1-3898
BUILDING INSPECTION DIVISION:
RELEASE DOES NOT APPLY TO CONSTRUCTION IN
EASEMENTS OR PUBLIC RIGHT OF WAY.
ALL CHANGES MUST BE APPROVED.
Crosstown Engineering (CE) was retained to inspect the subject load bearing wall and to provide an opinion.
No other information was provided regarding prior engineering reports, recommendations for foundation repairs
or construction documents relative to this structure. This report provides our reasonable professional opinion of
the condition of the load bearing wall on the date of our inspection and does not take into consideration any
changes in the condition of the load bearing wall after that date.
Scove of Work Limitations:
This report is for informational purposes only. The inspection excludes the detached buildings, privacy or retain-
ing walls, general site drainage away from the structure, material and soil sampling/testing, and verification of
concrete reinforcement or knowledge of the location of interior grade beams, boxed structural members not in
plain sight or previous repair work. Removal of floor coverings or performance of invasive tests or procedures is
not included.
Document ReWei r:
Documents were not provided for review.
Analysis and Recommendations:
Subject Item:
PROVIDE SIGNED AND SEALED LETTER
FROM REGISTERED ENGINEER CONFIRMING
SITE INSPECTION AND APPROVAL OF
STEEL BEAM WHEN WORK IS COMPLETE
A field inspection was made to determine the beam required to replace the columns between the kitchen and living
room in the first floor of the two-story, single family house.
Discoveries:
• The existing floor over the kitchen consists of 2x12 joists fastened into a glulam beam concealed in the
attic.
• The existing beam and columns can be replaced with a W10X22 x 22' Steel I -Beam, concealed in the
attic.
• The steel beam is to be supported by a minimum of 3.5" bearing length across the full width of the beam
on the interior side and by a minimum of 5.5" bearing length across the width of the beam on the exterior
end to support the notch at the top of the beam to fit under the roof decking.
• The recommended beams have been designed in compliance with the 2021 IRC.
• See attached drawings for more information.
RECEIVED: 0710/2025 1 of 5 INSPECTOR TO VERIFY AT
25-002639 FRAMING INSPECTION
2715 SUMMER WIND DR
INTERIOR ALTERATION
le
CROSSTOWN
STRUCTURAL ENGINEERING HOME a FOUNDATION INSPECTION
Disclaimer:
Adam A. Green, P.E. (TX), MBA
Austin I Dallas I Fort Worth I Houston I San Antonio I Waco (469) 751-7694
«sv. CrosstonnEngineering. com
We do not warrant the future performance of the subject load bearing wall and the reader is urged to review the
Disclosure & Disclaimer for other limitations and standard recommendations. The limit of liability is limited to
the fee paid for this opinion. No further agreement shall be made, altered, or varied except by written instrument.
Crosstown Engineering, its sub -contractors, and Adam Green, P.E., are not responsible for liability to the owner
or others for acts or omissions of the contractor to carry out the repairs in accordance with their agreement or for
the construction means, methods, techniques, sequences, procedures or the safety precautions incident thereto.
The contractor is solely responsible for the warranty of the work they performed in accordance with their agree-
ment.
Sincerely,
Crosstown Land Development Services
Texas Engineering Firm (F-15944)
Adam Green, P.E., MBA
Professional Engineer (TX #116597)
7/3/2
PROVIDE SIGNED AND SEALED LETTER
FROM REGISTERED ENGINEER CONFIRMING
SITE INSPECTION AND APPROVAL OF
STEEL BEAM WHEN WORK IS COMPLETE
1.
GRAPYUNE
CITY OF GRAPEVINE
THIS PAGE RELEASED FOR CONSTRUCTION
RELEASE DOES NOT AUTHORIZE ANY WORK IN CONFLICT
WITH THE BUILDING CODE OR ZONING ORDINANCE
CITY APPROVED PLANS TO BE KEPT ON THE JOB SITE AT
ALL TIMES.
07/17/2025
BY: ARNOLDO RAMIREZ TSBPE: 1-3898
BUILDING INSPECTION DIVISION
RELEASE DOES NOT APPLY TO CONSTRUCTION IN
EASEMENTS OR PUBLIC RIGHT OF WAY.
ALL CHANGES MUST BE APPROVED.
2 of 5
40
CROSSTOWN
STRUCTURAL ENGINEERING HOME i FOUNDATION INSPECTION
DISCLOSURE & DISCLAEMER
Adam A. Green, P.E. (TX), MBA
Austin I Dallas I Fort Worth I Houston I San Antonio I Waco (469) 751-7694
c«<z�•.Crosstonnl:. �. � _ '.. ;,com
NO WARRANTY IS rxrr noSED OR IMPLIED BY THIS =4vu4r=x AS TO THE rrxrukMANCE OF THIS LOAD
BEARING WALL OR THE REPAIRS THERETO.
This report is written for informational purposes only. The opinions expressed in this report are based on a visual evaluation
of current conditions observed at the time of the inspection. THERE IS NO WARRANTY, EXPRESSED OR IMPLIED,
CONCERNING THIS ENGINEERING REPORT.
The information in this report supersedes any verbal comments, expressed or implied, made by Crosstown Land Development
Services or its principals, agents or employees. The client agrees that neither CLDS nor its employees or owners will be
�-, , ...-Ale for:
1. Knowledge of the subsurface conditions without extensive geotechnical data obtained from onsite drilling and testing of
samples,
2. Knowledge of cracks, vertical differential displacement of floors without uncovering of the floor by the client; and
3. Any other element such as joists or beams and other Structural... 1 that is boxed or otherwise not readily available
to CE for viewing, and releases CE from any liability attributable to such knowledge or conditions.
Any prescribed repair or maintenance plan detailed by this report is based on observations of apparent peril` ..... P: of the
facility at the time of this structural survey. Compliance with any code or specification other than as expressly noted is
specifically excluded.
This report was prepared expressly for the client and expressly for the purposes indicated by the client. Permission for use
by any other person for any purpose, or by the client for different purpose is denied unless otherwise stated in writing by CE.
We recommend that the owner contact Crosstown to perform an inspection of the installations prior to drywall being placed
on the wall to ensure that the I is completed properly.
CE SHALL HAVE NO LIABILITY FOR ACTS OR O1Vuo6iL%ji4b BY THE CONTRACTOR OR HIS SUBCONTRAC-
TORS PERFORMING WORK ON THIS PROJECT, OR THE FAILURE OF THE CONTRACTOR TO PERFORM THE
WORK IN ACCORDANCE WITH THE REPAIR PLAN. CE IS NOT RESPONSIBLE FOR THE CONSTRUCTION
MEANS, M=inuLS, TECHNIQUES, SEQUENCE OR PROCEDURES OR THE PRECAUTIONS INCIDENTAL
1 r1n1z 10.
CE expressly DISCLAIMS ANY WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE and the client expressly
disclaims that it has contracted for or received any warranty of fitness for a particular purpose with respect to this report.
THE REPORT UNDER THIS AGREEMENT IS THE OPINION OF CE AND THERE ARE NO WARRANTIES THAT
EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS AGREEMENT.
3of5
0
M -0
z
m 5
0
z
0
O
'v 3
r -n
D
z
0 s
m
= o
N �
N
;LJ
A
C
D rri
r3
------ (1) r cp —
D
O N
7 1
o.
O
O
line of second floor � J
�
A m
o
CD � O m p m r 3 r m _
C �
m n C 0 z
o r Z cn z N
0 N 2
n
0
0
0
y rr
T
7
CD
N _
O_
CD
fA n
A
nt 0 ~
i= o
a
— o
2
...Ili_■...lt_1..�L■ � ■ � ■ ■ ■ � ■ _ ■ �
I of second floor W1 OX22 x 22' Steel I -Beam
000
CD CD in rm0
o c 3 m
N -'7IA
iD Zm
o
a �� z
0
o. s
o
44 / tE 5
A!!MA GREEN
p `597 S
0703'25 joi, <rcENSEpV*p
s,�ONAt F. r
Crosstown Engineering
Texas Engineering Firm (F-15944)
6119 Greenville Ave, Ste 320
Dallas. TX 75206
CROSSTOWN[ CROSSTOWNEh'GfNEERING
BCE FlRM %-�SY4 - vnaw TONIENGINEEiHC D>w
:M4�•51-7041 DALLAS%ErROPIE%
PROVIDE SIGNED AND SEALED LETTER
FROM REGISTERED ENGINEER CONFIRM[ G
SITE INSPECTION AND APPROVAL OF
STEEL BEAM WHEN WORK IS COMPLETE
2715 SU ER WIND DR. SHEET IOF2
GRAPEVINE, T� � '
(9FNFRAI NOT",
t,1 N 'Ai. I i!I1 I" I'II I n W Rn Y AI I MFA11111I 1.11_N `i PI IOR TO OROERNO OR CUTTING MATERIAL.
JOISTS INl1 RStQTI DSYNIIWII IISHSFAMSARi II.1IA:TFNF0TOBFAMSWIIN SIMPSON HUSTYPF HANOFRSOR FOUNALFNT
- FASTEN TRIPLE LVL INTO DOUBLE LVL WITH SIMPSON HU412 MANGER
O + O 0
Il0 Q*1 O
1 \
THROUGH -BOLT
AT WOOD FILLER
STAGGERED 24"
3.5" COILED STRAPS ON CENTER
16" LENGTH TO
STRAP BEAM TO
SUPPORTS
BELOW STFF� RFA�0 s1nr- )oc:w
CD
W W
iuUQLA.
DO0O
WU�U
_jWavn
V/ Z Q
O
zZQ�
Qw z
z
z�w
F-3:
Ncn(L
\ w FD cn w
W z m
9 W J
F-
W
N H 2X RAFTER
a U /
COILED STRAPS
12" LENGTH
48" ON CENTER
TO STRAP WALL
TO SIDE OF
BEAM
a r+A•1
CROSS SECTION VIEW OF BEAM
NOTCH BEAM
TO FIT ""'DER
ROOF DECKING
0
0 0
�'• W y
ICI W
ff 1U O�
1G�y1 i';< IPir
♦�� � 10 W:� — N
a,. oo € n
COILED STRAPS 5.5" min
16" LENGTH TO
STRAP BEAM TO o ? c7
SUPPUR I S
BELOW e s
N
0
N
W�
o:
0
z
�x
W LLj
2z
j W
Ln Q
CV 0
0
u
2W�
If
z
O
N
O
V
CROSSTOWN
STRUCTURAL ENGINEERING HOME i FOUNDATION INSPECTION
Date: August 22, 2025
Adam A. Green, P.E. (TT), MBA
Austin I Dallas I Fort Worth I Houston I San Antonio I Waco (469) 751-7694
Attention: Ernando Teixera (
Subject: Load Bearing Wall post -repair evaluation
2715 Summer Wind Dr., Grapevine, TX
To Whom It May Concern:
«-"zv.CrosstoN%mEngineering.com
Crosstown Engineering (CE) was retained to visually inspect the work completed on the subject Load Bearing
Wall.
We have determined the steel beam, supports and connections have been completed per our initial report and
drawing dated 7/3/25.
If you have any questions or need additional information, please call our office.
Sincerely,
Crosstown Land Development Services
Texas Engineering Firm (F-15944)
Adam Green, P.E., MBA
Professional Engineer (TX #116597)
08/22/2025
�iE of r%�,,
ADM A,GREEN
116597 ,;4
1 of 2
CROSSTOWN
STRUCTURAL ENGINEERING HOME A FOUNDATION INSPECTION
DISCLOSURE & DISCLAIMER
Adam A. Green, P.E. (TT), MBA
Austin I Dallas I Fort Worth I Houston I San Antonio I Waco (469) 751-7694
«-"zv.CrosstoN%mEngineering.com
NO WARRANTY IS EXPRESSED OR IMPLIED BY THIS ENGINEER AS TO THE PERFORMANCE OF THE BEAM
OR THE REPAIRS THERETO.
REPORT LLWrATIONS
This report is written for informational purposes only. The opinions expressed in this report are based on a visual evaluation
of current conditions observed at the time of the inspection. THERE IS NO WARRANTY, EXPRESSED OR IMPLIED,
CONCERNING THIS ENGINEERING REPORT.
The information in this report supersedes any verbal comments. expressed or implied, made by Crosstown Land Development
Services or its principals, agents or employees. The client agrees that neither CLDS nor its employees or owners will be
responsible for:
1. Knowledge of the subsurface conditions without extensive geotechnical data obtained from onsite drilling and test-
ing of the recovered samples,
2. Knowledge of cracks, vertical differential displacement of floors without uncovering of the floor by the client; and
3. Any other element such as joists or beams and other structural members that is boxed or otherwise not readily
available to CE for viewing, and releases CE from any liability attributable to such knowledge or conditions.
Any prescribed repair or maintenance plan detailed by this report is based on observations of apparent performance of the
facility at the time of this structural survey. Compliance with any code or specification other than as expressly noted is
specifically excluded.
This report was prepared expressly for the client and expressly for the purposes indicated by the client. Permission for use
by any other person for any purpose, or by the client for different purpose is denied unless otherwise stated in writing by CE.
CE SHALL HAVE NO LIABILITY FOR ACTS OR OMISSIONS BY THE CONTRACTOR OR HIS SUBCONTRAC-
TORS PERFORMING WORK ON THIS PROJECT, OR THE FAILURE OF THE CONTRACTOR TO PERFORM THE
WORK IN ACCORDANCE WITH THE REPAIR PLAN. CE IS NOT RESPONSIBLE FOR THE CONSTRUCTION
MEANS, METHODS, TECHNIQUES, SEQUENCE OR PROCEDURES OR THE PRECAUTIONS INCIDENTAL
THERETO.
CE expressly DISCLAIMS ANY WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE and the client expressly
disclaims that it has contracted for or received any warranty of fitness for a particular purpose with respect to this report.
THE REPORT UNDER THIS AGREEMENT IS THE OPINION OF CE AND THERE ARE NO WARRANTIES THAT
EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS AGREEMENT.
2of2