Loading...
HomeMy WebLinkAboutSFRA2026-002038SHEET INDEX SCOPE OF WORK PAGE # DESCRIPTION SYSTEM SIZE: 12.71 KW DC, 11.5KW AC PV-1.0 COVER SHEET MODULES: (31) HANWHA Q-CELLS: Q.PEAK DUO BLK ML-G10.C+ 410 (MD06G100A-017) PV-2.0 SITE PLAN • RAPID SHUTDOWN: (13) TESLA MID CIRCUIT INTERRUPTER PV-3.0 LAYOUT (MCI) ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE • ENERGY STORAGE SYSTEM W/ INTEGRATED PV INVERTER: PV-4.0 ELECTRICAL (1) TESLA: POWERWALL 3 1707000-XX-Y, 13.5KWH, 11.5KW INVERTER OUTPUT, LITHIUM -ION BATTERY (WEIGHT: 291.2 LB PV-5.0 SIGNAGE EACH) PV-5A SIGNAGE 2 • BACKUP GATEWAY: (1) 200A TESLA POWERWALL CONTROL PANEL RACKING: ALPHATRACK TO FRAMING - SNR-DC-00370 RECEIVED: 05/29/2026 26-002038 3318 BRIDLEWOOD DR SOLAR PANELS ABBREVIATIONS VICINITY MAP A AMPERE - - AC ALTERNATING CURRENT - L AFC ARC FAULT CIRCUIT INTERUPTER AZIM AZIMUTH COMP COMPOSITION 8 DC DIRECT CURRENT ; (E) EXISTING ESS ENERGY STORAGE SYSTEM Hall - Johnson Rd MSP MAIN SERVICE PANEL (N) NEW 15 PRE-FAB PRE-FABRICATED4 ood Ur K PSF POUNDS PER SQUARE FOOT ¢Y �a � m PV PHOTOVOLTAIC RSD RAPID SHUTDOWN DEVICE Sprind¢R•¢e DI c` TL TRANSFORMERLESS E y ��Qa40r V VOLTS g 3 S W WATTS s e GENERAL NOTES • ALL WORK SHALL COMPLY WITH 2O21 IRC/IBC/IEBC, ASCE 7-16 & 2018 NDS, MUNICIPAL CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS. PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020. ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020. PHOTOVOLATIC SYSTEM IS UNGROUNDED. NO CONDUCTORS ARE SOLIDLY GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.41(A) MODULES CONFORM TO AND ARE LISTED UNDER UL 61730. INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741. RACKING CONFORMS TO AND IS LISTED UNDER UL 2703. SNAPNRACK RACKING SYSTEMS, IN COMBINATION WITH TYPE I, OR TYPE II MODULES, ARE CLASS A FIRE RATED. RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1). CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G). ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT. 11.26 AMPS MODULE SHORT CIRCUIT CURRENT. 17.59 AMPS DERATED SHORT CIRCUIT CURRENT [690.8 (a) & 690.8 (b)]. THE CAPACITY OF THE STANDALONE SYSTEM SUPPLY SHALL BE EQUAL TO OR GREATER THAN THE LOAD POSED BY THE SINGLE LARGEST UTILIZATION EQUIPMENT CONNECTED TO THE SYSTEM PER NEC ARTICLE 710.15(A) ALL PASS -THROUGH CONDUCTORS MUST COMPLY WITH NEC 312.8 NEC 2020 705.12(B)(3)(3): THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE SHALL NOT EXCEED AMPACITY OF BUSBAR. ALL CHANGES REQUIRE APPROVAL OF REVISED PLANS APPROVED PLANS SHALL BE KEPT ON JOBSITE AT ALL TIMES CONSTRUCTION HOURS 7:00 A.M. - 7:00 P.M. MONDAY - SATURDAY ONLY NO WORK PERMITTED ON SUNDAY SEPERATE PLUMBING, MECHANICAL, ELECTRICAL AND SIGN PERMITS SHALL BE REQUIRED GRAI 'ICE._ PLANS HAVE BEEN REVIEWED & APPROVED BY A THIRD PARTY CONTRACTOR Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 CONTRACTOR SHALL CALL FOR INSPECTIONS: (817) 410-3010 CONTRACTOR REGISTRATION WILL BE REVOKED UPON PERMIT EXPIRATION. REV NAME DATE COMMENTS SLnRLn 28447 -III STATE HIGHWAYa SURE Zap. GRAND PRAIRIE. n /spso Pnorvean-sn-wer der ana cn a,00 CUSTOMER RESIDENCE: ABBEY DARKO 3318 BRIDLEWOOD DR, GRAPEVINE, TX, 76051 TEL. (817) 682-2383 APN: 04782968 PROJECT NUMBER: 351 R-318DARK DESIGNER: (415) 580-6920 ex3 Jean Claude IRADUKUNDA SHEET COVER SHEET REV: A 5/28/2026 PAGE PV-1.0 SITE PLAN - SCALE - 1/16"=1'-0" FIRE SETBACKS (3 TYP) PL I �l C MP SE ROOF PATHWAYS �- (3' TYP) (N) ARRAY AR-02 E NOTE: ROOFTOP MODULE LEVEL RAPID SHUTDOWN DEVICE INSTALLED PER NEC 690.12 NOTES: • RESIDENCE CONTAINS ACTIVE FIRE SPRINKLERS. ARRAY DETAILS: • TOTAL ROOF SURFACE AREA: 3395 SO FT. • TOTAL PV ARRAY AREA: 655.2 SO FT. • PERCENTAGE PV COVERAGE: (TOTAL PV ARRAY AREA/TOTAL ROOF SURFACE AREA)' 100 = 19.3% ARRAY TRUE MAG PV AREA PITCH AZIM AZIM (SOFT) AR-01 M. 850 82° 295.90 AR-02 M. 265° 262° 84.54 AR-03 26' 175° 172' 274.76 (E) RESIDENCE D - (N) ARRAY AR-01 r (N) ARRAY AR-03 INV AC f"- o (E) DRIVEWAY BRIDLEWOOD OR Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 LEGEND SCALE: NTS NoreNOT ALLITEMSINLEGEND wI'LLAIN SITE PLAN RDS ® REMOTE DISCONNECT SWITCH INV INVERTER(S) BPPPEAR BACKUP LOADS PANEL ❑MICROGRID MD INTERCONNECT DEVICE SOLAR INTERIOR EQUIPMENT MODULES L SHOWN AS DASHED SE SERVICE ENTRANCE AC AC DISCONNECT(S) GP GENERATION PANEL +1 F BATTERY MA METER ADAPTER J APB FRANKLBOX IN P MP MAIN PANEL 0 DC DISCONNECT(S) LC PV LOAD CENTER ENERGY SYSTEM (E S) APT MAC CONTROMETER L ER ER CB IO COMBINER BOX SNR MOUNT SP SUB -PANEL pM DEDICATED PV METER SNR MOUNT & SKIRT SLnRLn 28447 -II STATE HIGHWAY -I SUR II GRAND PNAIRIE CUSTOMER RESIDENCE: ABBEY DARKO 3318 BRIDLEWOOD DR, GRAPEVINE, TX, 76051 TEL. (817) 682-2383 APN: 04782968 PROJECT NUMBER: 351 R-318DARK DESIGNER: (415) 580-6920 ex3 Jean Claude IRADUKUNDA SHEET SITE PLAN REV: A 5/28/2026 PAGE PV-2.0 ROOF INFO Name Type Height AR-01 COMP SHINGLE - 1-STORY ALPHATRACK AR-02 COMP SHINGLE - 1-STORY ALPHATRACK AR-03 COMP SHINGLE - 1-STORY ALPHATRACK D1 - AR-01 - SCALE: 1/16" = V-0" AZIM: 85° PITCH: 34° D2 - AR-02 - SCALE: 1/16" = V-0" AZIM: 265° PITCH: 34° FRAMING INFO Type Max OC Detail Span Spacing 2X6 RAFTERS 12'-11" 24" ALPHATRACK TO FRAMING - SNR-DC-00370 2X6 RAFTERS 11'-8" 24" ALPHATRACK TO FRAMING - SNR-DC-00370 2X6 RAFTERS 14'-2" 24" ALPHATRACK TO FRAMING - SNR-DC-00370 T-10" 2' 4" - - 6'-2" Li "/ 5'-1 / OD 6' TYP# f 31511 3'-_11" n 24'-1" ATTACHMENT INFORMATION DESIGN CRITERIA Max Landscape Max Landscape Max Portrait Max Portrait Configuration MAX DISTRIBUTED LOAD: 3 PSF OC Spacing Overhang OC Spacing Overhang SNOW LOAD: 5 PSF WIND SPEED: 6'-0" 2'-4" 4'-0" 2'-0" STACKED 115 MPH 3-SEC GUST. FASTENERS: (1) 5/16" DIA S.S. LAG SCREW: 6'-0" 2' 4" 4'-0" 2' 0" STACKED 2.5" MIN EMBEDMENT INTO FRAMING 6-0" 2'4" 4'-0" 2'-0" STACKED Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 D3 - AR-03 - SCALE: 1/16" = V-0" AZIM: 175° PITCH: 26° -11'-3" - 12'-5" — 3' - T-3—/{�-#\ - 2' I/ `I 15'-5" - I 4 2N 6' TYP # fi 6' 13" 8" J 6'-11" 6' TYP 3'-6" 4'21" I 4'-5" — 31-411 #— — �1'-6" STRUCTURAL NOTES AND OVERHANG REDUCED WITHIN THE 12" (48" FOR TILT KITS) BOUNDARY REGION • INSTALLERS SHALL NOTIFY ENGINEER OF ANY POTENTIAL STRUCTURAL ISSUES ONLY AS FOLLOWS: OBSERVED PRIOR TO PROCEEDING W/ INSTALLATION. •• ALLOWABLE ATTACHMENT SPACING INDICATED ON PLANS TO BE REDUCED BY 50%. •• ALLOWABLE OVERHANG INDICATED ON PLANS TO BE 1/5TH OF ALLOWABLE • IF ARRAY (EXCLUDING SKIRT) IS WITHIN 12" (48" FOR TILT KITS) BOUNDARY REGION OF ATTACHMENT SPACING INDICATED ON PLANS. ANY ROOF PLANE EDGES (EXCEPT VALLEYS), THEN ATTACHMENTS NEED TO BE ADDED OF rrxgi1, � I i JAMES htpTTHEW ..IALSH i 0 S " DigbH, Slgnetl QWSI 92026 F-19352 28447 ? N STATE HIGHWAYS SUHE200. -ND PNAINIE CUSTOMER RESIDENCE: ABBEY DARKO 3318 BRIDLEWOOD DR, GRAPEVINE, TX, 76051 TEL. (817)682-2383 APN: 04782968 PROJECT NUMBER: 351 R-318DARK DESIGNER: (415) 580-6920 ex3 Jean Claude IRADUKUNDA SHEET LAYOUT REV: A 5/28/2026 PAGE PV-3.0 EXISTING 200A BACKUP LOAD PANEL WITH 2O0A MAIN BREAKER 4A20D Surge protector BACKUP( required in this enclosure NEW 200A METER NUMBER:139362131LG BACKUP GATEWAY - GATEWAY 3 (1841000-X1-Y) WITH 2O0A MAIN BREAKER (N)INTERNAL P B WITH(1)60A PV- BREAKER Grounds and Neutrals shall be bonded together in this enclosure Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 Grounds and Neutrals shall be separated in these enclosures (N)LOCKABIE (N) CKABLE BLADE TYPE B TYPE AC DISCONNECT AC DIS .ONNECT INVERTER_ TESLA 11500 WATTSPOWERWALL3 A 1707000-XX-Y, ENERGY STORAGE. TESTA POWERWALL 3 31 HANWHA O-CELLS 1707000-XX-Y (24OV) O.PEAK DUO BLK ML-G10.C+ 410 (MDO6G100A-017) 3 3 3 2 1 STRING 1 WITH 7 MODULES WITH 3 MCI COUNT _ STRING 2 WITH 7 MODULES WITH 3 MCI COUNT ` STRING 3 WITH 7 MODULES Y J-BOX WITH 3 MCI COUNT S(}U/1FE'N.-/ S D STRING 4 WITH 4 MODULES DU222RB DU R WITH 2 MCI COUNT 3R, 60A, 2P 3R, 60A, 2P /U T STRING 5 WITH 6 MODULES 120240VAC 1201240VAC WITH 2 MCI COUNT, MODULE LEVEL RAPID SHUTDOWN DEVICES LOAD RATED OC DISCONNECT WITH AFCI RAPID SHUTDOWN COMPLIANT POINT OF INTERCONNECTION: NEC 2020 705.12(6)(3)(3), INTERCEPT METER EQUIPMENT CHARACTERISTICS INCLUDED IN SPEC SHEETS NOTE: TOTAL SYSTEM BACKFEED = 60.OA USED FOR INTERCONNECTION CALCULATIONS CONDUIT SCHEDULE TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL 1 Inverter Input (10) 10 AWG (PV WIRE) N/A 2 Inverter Input (10) 10 AWG N/A THHN/THWN-2 3 Inverter Output (2) 6 AWG (1) 6 AWG THHNtTHWN-2 THHN/THWN-2 4 Backup Panel Feeder (2) 210 AWG (1) 2/0 AWG THHN/THWN-2 THHN/THWN-2 5 Service Feeder (2) 2/0 AWG THHN(THWN-2 (1) 210 AWG THHN/THWN-2 GROUND CONDUIT 10 AWG (BARE) Open Air 10 AWG THHN/THWN-2 1" EMT 8 AWG THHN/THWN-2 3/4"EMT 6 AWG THHN/THWN-2 2" EMT NONE 1-1/2"EMT swnun I•%m ? N STATE 1IGHWAY3 SURE200. GRAND PRAIRIE CUSTOMER RESIDENCE: ABBEY DARKO 3318 BRIDLEWOOD DR, GRAPEVINE, TX, 76051 TEL. (817)682-2383 APN: 04782968 PROJECT NUMBER: 351 R-318DARK DESIGNER: (415) 580-6920 ex3 Jean Claude IRADUKUNDA SHEET ELECTRICAL REV: A 5/28/2026 PAGE PV-4.0 �l WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION: INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE). PER CODE(S): NEC 2020: 690A3(B) WARNING I THREE POWER SUPPLY SOURCES: UTILITY GRID. BATTERY AND PV SOLAR ELECTRIC SYSTEM LABEL LOCATION: UTILITY SERVICE METER AND MAIN SERVICE PANEL. PER CODE(S): NEC 2020: 705.12(C) WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE 1 LABEL LOCATION: ADJACENT TO PV BREAKER AND ESS OCPD (IF APPLICABLE). PER CODE(S): NEC 2020: 705-12(6)(3X2) 6 0 WARNING THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE SHALL NOT EXCEED AMPACITY OF BUSBAR LABEL LOCATION: PV LOAD CENTER (IF APPLICABLE) AND ANY PANEL THAT UTILIZES "THE SUM OF BREAKERS RULE". PER CODE(S): NEC 2020: 705.12 (6)(3)(3) INVERTER 1PHOTOVOLTAIC DC DISCONNECT OTES AN J� S F, F C�T`�]('{ .JSIGNS AND LABC�LS Mff ttET THE REQUIREMENTS OF THE NEC 2020 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ. VOLTAGEMAXIMUM SYSTEM 550VDC SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE WORDS, COLORS AND SYMBOLS. LABEL LOCATION: • LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING INVERTER(S), DC DISCONNECT(S)_ METHOD AND SHALL NOT BE HAND WRITTEN. PER CODE(S): NEC 2020: 690,53 • LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. • SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED. • DO NOT COVER EXISTING MANUFACTURER LABELS. Approved for Construction by LABEL LOCATION: W. Scott Leavelle JR) INSTALLED WITHIN T OF RAPID SHUT DOWN 6-2-26 SWITCH PER CODE(S): NEC 2020: 69e56(Cx2), CEC 2022: 690-56(C)(2), IFC 2015: 1204.53 • • • ZCAUTION LABEL LOCATION: ENERGY STORAGE SYSTEM INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT, AT EACH TURN, ABOVE AND BELOW PENETRATIONS, ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS. PER CODE(S): NEC 2020: 690.31(D)(2) Alj � LO 10 AC ISC IEC 5), PHOTOVOLTAIC SYSTEM POINT OF INTERCONNECTION_ PER CODE(S): NEC 2020: 690.54 PREMISES WIRING MAY REMAIN ENERGIZED AFTER LOSS OF UTILITY POWER i SU ,^{ ■L411 LABEL LOCATION: INVERTER(S), AC/DC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE). 4" PER CODE(S): NEC 2020: 706.15(C) SOLAR PV SYSTEM EQUIPPED —N s nm ware Nicnwav wo. suite mo. caarvo P-illeu nos WITH RAPID SHUTDOWN I—NE8- 72-0091 A,," -- CUSTOMER TOMER RESIDENCE: ABBEY DARKO 3318 BRIDLEWOOD DR, TURN RAPID SHUTDOWN ENERGY STORAGEDISCODISCONNEIC GRAPEVINE, TX, 76051 SWITCH TO THE "OFF" SOLAR i2orz4o TEL. (817) 682-2383 ELECTRIC PV APN: 04782968 POSITION TO SHUT DOWN PV PANELS PROJECT NUMBER: SYSTEM AND REDUCE SHOCK 351R-318DARK HAZARD IN THE ARRAY. LABEL LOCATION: DESIGNER: (415)580-6920ex3 ENERGY STORAGE SYSTEM Jean Claude IRADUKUNDA PER CODE(S): NEC 2020: 706.15(C) SHEET LABEL LOCATION: SIG NAG E ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS REV: A 5/28/2026 ARE CONNECTED PER CODE(S): NEC 2020: 690.56(C), CEC 2022: 690.56(C) PAGE PV-5.0 CAUTION: MULTIPLE SOURCES OF POWER ESS DISCONNECT LZO PV SYSTEM DISCONNECT -SERVICE ENTRANCE AND MAIN PANEL 3318 BRIDLEWOOD DR, GRAPEVINE, TX, 76051 PER CODE(S) : NEC 2020 705.10,710.10 LABELING FORMAT LABELS SHALL BE RED PLASTIC MATERIAL WITH ENGRAVED WHITE LETTERS MADE OF DURABLE ADHESIVE, WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT. LETTERS SHALL BE MINIMUM 3/8" IN SIZE. Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 SLnRLn 28447 2990 N. STATE NIGHWRV 3fi0. StME200. GpAHD PgAIP� TX ]5050 CUSTOMER RESIDENCE: ABBEY DARKO 3318 BRIDLEWOOD DR, GRAPEVINE, TX, 76051 TEL. (817) 682-2383 APN: 04782968 PROJECT NUMBER: 351 R-318DARK DESIGNER: (415) 580-6920 ex3 Jean Claude IRADUKUNDA SHEET SIGNAGE 2 REV: A 5/28/2026 PAGE PV-5.1 5/28/2028 08'.50 PM Subject Structural Certification for Proposed Residential Solar Installation. Job Number 351R-318DARK, Rei Client ABBEY DARKO Address'. 3318 Brldlewood Dr, Grapevine, TX 78051 Attnl To Vvhom It May Concern X co 6pu III •..1/ F-093M JAMES MATfHEW WALSH .q ....140542 Eep. 12,31MUS plgllelly Signed 0n'. 05292028 Astra v2.2OO CAT 1 Afield observation ofthe existing structure at the address Indicated above was performed. Structural evaluation ofthe loading was based on the site observations and the design criteria listed below, Design Crltedal • 2021 IRC/IBC/IEBC, ASCE 7-18 & 2018 NDS • Basic (Category II)Wnd Speed V=115 mph, Exposure B • Ground Snow Load = 5 psf Based on this evaluation, I certify that the alteration to the existing structure by the installation ofthe PV system meets the requirements ofthe applicable Sell and/or new building code provisions referenced above, Additionally, I certify that the PV module assembly including all attachments supporting It have been reviewed to be In accordance with the manufacturers specifications, Results Summary (Hardware Check Includes Uplift Check on AttachmenblFastener, Structure Check Considers Main Structure) Orientation Attachment Spacinguo ntllever Configuration Mae OCR Result AR41 Landscape Portred 72128 48124 Stacketl Stacketl 32% 46% Peee Paee Roofing Material Pitch Structure Check Comp Shingle 34- Paee Orientation Attachment SpacinglCantilever Configuration Max OCR Result AR42 Lantlscape Portrait 72/28 48124 Stacked Stacked 32% 46% Pass Pass Roofing Material Pitch Structure Check Comp Shingle 34- Pass Orientation Attachment SpacinglCantilevar Configuration Max OCR Result AR43 Lantlscape Po a 72128 48124 Specked Stacked 32% 47% Paee Pa.. Roofing Material Pitch Structure Check Comp Shingle 28° Peee Approved for Construction by: W. Scott Leavelle JR) 6-2-26 225 Bush St. Suite 1400 San Francisco, CA 94104 Article 220 - Service Feeder calculation for (address) 3318 Bridlewood or Grapevine TX USA 76051 Section 220.83 Existinq Dwellinq Unit Part #1 - Section 220.83(A)(1) Generatl Liqhtinq/Receptacles (a? 3 VAyer gQ ft: Building Square Footage VA (wafts) House 2424 7272 Total for Part #1: Part #2 - Section 220.83(A)(2),(4) Appliances and Dedicated Circuits Dedicated Circuit Size in VA Dedicated Circuit Dryer 5760 Oven 5760 Range 5760 Appliance Circuit 1 1500 Appliance Circuit 2 1500 Laundry 1500 N/A N/A N/A N/A N/A Total for Part # Total VA from Parts #1 and #2 combined: Total VA 29052 Job Code 351 R-318DARK Amps 30.3 Amps Box A (VAI 1 30.3 I 7272 Size in VA N/A N/A N/A N/A N/A N/A N/A N/A N/A Amps Box B (VA) 2: 90.75 I 21780 Box A + Box B = 29052 First 8000 VA @ 100 % 8000 Remaining VA @ 40 Remaining VA= 21052 21052 x40%= 8420.8 VA Adding First 8,000 VA 8000 VA Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits: 16420.8 VA Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits: 68.42 Amps Part #3 - Section 220.83(N Heatir)Q and A/C Loads: "Combine the larger loads of either the Heating or the A/C loads togther 100 % of all the Heating or A/C loads in VA: 7680 VA 100 % of all the Heating or A/C loads in Amps: 32 A Totals from all Parts VA Volts Amps Approved for Construction by: Parts #1 & #2 16420.8 240 68.42 W. Scott Leavelle (TPI) Part#3 7680 240 32 6-2-26 Total VA for all Parts: 24100.8 Totals Service/Feeder Load F100.42 Panel 1 of 1 Bus Rating: 200 Main Rating: 200 Panel % of Sq.Ft: 100% Itemized House and 240V Loads for Panel: (VA) A/C Unit -240V 7680 Dryer 5760 Oven 5760 Range 5760 Not Fed by other panels Load Calc: (This Panel) 100.42 Total Load Calc: Panel % of Total VA: 100% Appliance Circuit 1 1500 Appliance Circuit 2 1500 Laundry 1500 Approved for Construction by: W. Scott Leavelle JPI) 6-2-26 OPEAK DUO BLK IVIL-G10+ SERIES ocell; Approved for Construction by: 390-410Wp 1132Cells W. Scott Leavelle (TPI) 20.9% Maximum Module Efficiency 6-2-26 MODEL Q.PEAK DUO BLK ML-G10+it The ideal solution for: Rooftop arrays on residential buildings Breaking the 20 % efficiency barrier 1;iL� �L�LL Q.ANTUM DUO Z Technology with zero gap cell layout boosts module efficiency up to 20.9%. 25 A reliable investment La Inclusive 25-year product warranty and 25-year linear Warranty performance warranty'. Enduring high performance Long-term yield security with Anti LeTID Technology, ocells Anti PID Technologyz and Hot -Spot Protect. Extreme weather rating High-tech aluminium alloy frame, certified for high snow (5400Pa) and wind loads (4000Pa). � I . Innovative all-weather technology l2/ Optimal yields, whatever the weather with excellent low -light and temperature behaviour, n The most thorough testing �/\•J( programme in the industry Ocells is the first solar module manufacturer to pass the most comprehensive quality programme in the Industry: The new "Quality Controlled PW ofthe independent certification Institute TUV Rheinland. See cats sneer or rear for further Information. ' APT test cond*sons according to ;ECITS 628041:7015, metnoc A ;-1500 V, 96 h cm_wi�aw 2 w zou h Q.PEAK DUO BLK ML-G10+ SERIES ■ Mechanical Specification Format 74.0in x 41.11n x 1.26in (Including from a) 0879mm x 1045mm x 32 mm) Weight 48.51bs (22.Okg) Front Cover 0,13 In (3.2 mm) thermally pre-stressea glass with anti -reflection technology Back Cover Transparent composite film with black grid Frame Black anodised aluminium Cell 6 x 22 monocrystalllne O.ANTUM solar half cells Junction box 2.09-3.98in x 1,26-2.36in x 0.59-0.7tin (53-101mm x 32-60mm x 15-18mm), IP67, with bypass diodes ^ nen,•,-1 �at.a f:W mml -mot '66'?e�+=Tm; :>ta•,roomra er Mam+a Ol+l' nee m'1 -a-I-❑ +n Ol'resG rnQ s. p'emrenexs I a rro„ero uwonaLk a� Cable 4mm' Solar cable: (-) z72.041n 0830mm), (-) z72.D4in (1830mm) Connector Staubli VC4; IP68 pYe',ilsmml I-�Jala sswm; ■ Electrical Characteristics POWER CLASS 390 395 400 40S 410 MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS, STC (POWER TOLERANCE-5W/-OW) BSTC' BSTC' BSTC' BSTC' BSTC' Power at MPP' PM„ [W] 390 426,6 395 432.1 400 4375 405 443.0 410 448.5 Short Circuit Current' Isc (A] 11.01 12.05 11.04 12.08 11.07 12.11 11.10 12.15 11.13 12.18 E E Open Circuit Voltage' Vcc IV] 45.49 45.65 45.52 45.68 45.55 45.72 45.59 45.75 45.62 45.79 Current at MPP Iv„ [A] 10.39 11.37 10.45 11.43 10.50 11.49 10.56 11.55 10.61 11.61 f Voltage at MPP Vv- IV] 37.54 37.53 37.91 37.81 38.09 38.08 38.36 38.35 38.63 38.62 Efficiency' n (%] z19.9 2:20.1 2!20.4 z20,6 z20.9 Blfadallty of Pwa and IX 70% t10% - Blfadallty given for rear side irradiation on top of STC 1Yront side) - According to IEC 60904-1-2according to IEC 60904-3 ' Measurement tolerances P,u t3%; lu, Voc t5% at STC:1000W/m';'at BSTC: 1000 W/m' + tp x 135 W/m', tp = 70% 110%, 25t2 °C, AM 1.5 according to IEC 60904-3 MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS, NMOT2 Power at MPP Prus, [W] 292.6 296.3 300.1 303.8 307.6 E Short Circuit Current Is„ [A] 8.87 8.89 8.92 8.94 8.97 E Open Circuit Voltage Vcc IV] 42.90 42.93 42.96 42.99 43.03 c i Current at MPP Iv. [A] 8.16 8.21 8.26 8.31 8.36 Voltage at MPP Vv„ IV] 35.86 36.10 36.33 36.57 36.80 'Measurement tole,ances PN", 13%; leC; Vcc t5% at STC: 1000 W/m2, 25 t2 °C. AM 1.5 according to IEC 60904-3 - 'BOO W/m', \ V OT, soectrum AM 1.5 Ocells PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE At least 98%of nominal power -' u during flat year. Thereafter max. iio ss ----- 0.5% degradation per year. At least 93.5%of nominal power wo 3 up to 10 years. At least 86% of nominal power upto 25 years. of 4 All data within measurement � b tolerances. Full warranties In accordance with the warranty sp terms of the Ocells sales p o as '0 rs to organisation of your respective 200 sne eao am woo YEARS country. IRRADIANCEIWIn,j •Stardeld corms of guarantee for the 51xy companies wet, the higtlWt pnx1 ctlon camclly In 2021(February 2029 Typcalmotnunwunderlowirratllance cor�ltbns In comparison to o STTCCconditions (25°C, f000 W+m'). TEMPERATURE COEFFICIENTS Temperature Coefficient of IY a %/I -004 Temperature Coefficient of Vpc (3 [%/Ki -0.27 Temperature Coefficient of Pu„ y [%/K] -0.34 Nominal Module Operating Temperature NMOT rF] 109 t5.4 (43 z 3 °C) ■ Properties for System Design Maximum System Voltage Vers V] 1000 0EQ11000 NL) PV module classification Class II Maximum Series Fuse Rating [A DC] 20 Fire Rating based on ANSI/UL 61730 TYPE 2 Max. Design Load, Push/PulF [los/ft2] 75 (3600 Pa)/55 (266OPa) Permitted Module Temperature -40°F up to -185°F Max. Test Load, Push/Pull' (10S/ft2] 113(540OPa)/84(4000Pa) "Continuous Duty (-40-Cupto+85°C) ' See Ins:allation Manua ■ Qualifications and Certificates UL 61730, CE-compliant, Quality Controlled PV - TUV Rheinland, IEC 61215:2016, IEC 61730:2016, U.S. Patent No. 9,893,215 (solar cells), c 1 us l\ Approved for Construction by: W. Scott Leavelle JR) 6-2-26 Ocells pursues minimizing paper output In consideration of the global environment. Note; Installation Irstructbrs must be followed. confect our technical aentIm for funhar Information on approved Installation of the pn iMt. ��' I P.-h. 0 CELLS Amenca Inc. 400 spectrum Center 00ve, Sulm 1400. Irvine, CA 92618, USA I TEL -1949 748 59 961 EMAIL hgc.1mulry"cell-M I W Ee w,wv.ocells-nn Powerwall 3 Power Everything Powerwall 3 is a fully integrated solar and battery system, designed to accelerate the transition to sustainable energy. Customers can receive whole home backup, cost savings, and energy independence by producing and consuming their own energy while participating In grid services. Once installed, customers can manage their system using the Tesla App to customize system behavior to meet their energy goals. Powerwall3 achieves this by supporting up to 20 kW DC of solar and providing 11.5 kW AC of continuous power per unit. It has the ability to start heavy loads up to 185 A LRA, meaning a single unit can support the power needs of most homes. Powerwall 3 is designed for mass production, fast and efficient installations, easy system expansion, and simple connection to any electrical service. ri Battery shall be supported to the structure. Battery shall not be supported by brick. Battery installation per manufacturer specs. Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 2024 Approved for Construction by: Powerwall 3 Technical Specifications W. Scott Leavelle (TPI) 6-2-26 System Technical Model Number 1707000-xx-y Specifications Nominal Grid Voltage (Input & Output) 120/240 VAC Grid Type Split phase Frequency 80 Hz Overcurrent Protection Device 80A Solar to Battery to Home/Grid Efficiency 89%12 Solar to Home/Grid Efficiency 97.5%' Supported Islanding Devices Gateway 3, Backup Switch, Backup Gateway 2 Connectivity Wi-Fi (2A and 5 GHz), Dual -port switched Ethernet, Cellular (LTE/40^) Hardware Interface Dry contact relay, Rapid Shutdown (RED) certified switch and 2-pin connector, RS-485 for meters AC Metering Revenue Grade (+/- 0.5%) Protections Integrated arc fault circuit interrupter (AFCI), Isolation Monitor Interrupter (IMI), PV Rapid Shutdown (RED) using Teals Mid -Circuit Interrupters Customer Interface Tests Mobile ADD Solar Technical Maximum Solar STC Input Specifications Withstand Voltage PV DC Input Voltage Range PV DC MPPT Voltage Range MPPTs Maximum Current per MPPT (Imp) Maximum Short Circuit Current per MPPT (I Battery Technical Specifications 20V Nominal Battery Energy Maximum Continuous Discharge Power Maximum Continuous Charge Power Output Power Factor Rating Maximum Continuous Current Maximum Output Fault Current Load Start Capability (1 s) Power Scalability 20 kW 600 V DC 60 — 550 V DC 60 — 480 V DC 6 13 A' 15 A' 13.5 kWh AC' 11.5 kW AC 5 kW AC 0 -1 (Grid Code configurable) 48 A 10 kA 185 A LRA Up to 4 Powerwall3 units supported 'Typical solar shifting use case 'Values provided for 25QC (77°E), at beginning of life 3.3 kW charge/discharge power 'Tested using CEC weighted efficiency methodology. 41he customer Is expected to provide Internet connectivity for Powerwall3; cellular should not be used as the primary mode of connectivity Cellular connectivity subject to network operator service coverage and signal strength ' Where the DC Input current exceeds the MPPT rating, a jumper can be used to combine two MPPTs Into a single input to Intake DID current up to 26 A lap / 30 A Is, Powerwall3 Datasheet 2 Powerwall 3 Technical Specifications Environmental Operating Temperature —20°C to 50°C (-4°F to 122°F) a Specifications Operating Humidity(RH) Up to 100%,condensing Storage Temperature —20°C to 30°C (-4°F to 86°F), up to 95% RIP, non - condensing, State of Energy (SOE): 25%initial Maximum Elevation 3000 in (9843 ft) Environment Indoor and outdoor rated Enclosure Rating NEMA 3R Ingress Rating IP67 (Battery & Power Electronics) IP45 (Wiring Compartment) Pollution Rating PD3 Operating Noise @ 1 m <50 db(A) typical <62 db(A) maximum ° Performance may be de -rated at operating temperatures above 40°C (104°1`). Compliance Certifications UL 1642, UL 1699B, UL 1741, UL 1741 SA, UL 1741 SB, UL Information 1741 PCS, UL 3741, UL 1973, UL 1998, UL 9540, IEEE 1547- 2018, IEEE 1547.1, UN 38.3 Grid Connection United States Emissions FCC Part 15 Class B Environmental RoHS Directive 2011/65/EU Seismic AC156, IEEE 693-2005 (high) Fire Testing Meets the unit level performance criteria of UL 9540A Mechanical Dimensions 1099 x 609 x193 man (43.25 x 24 x 76 in) Specifications Weight 130 kg (287Is) Mounting Options Floor or wall mount Battery shall be o° supported to the 0-! structure. Battery shall 0 I� not be supported by brick. 1099 arm Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 609 man �-mm-� 20N Powerwdl 3 Datasheet 3 Solar Shutdown Device Technical Specifications The Solar Shutdown Device is a Mid -Circuit Interrupter (MCI) and is part of the PV system rapid shutdown (RSD) function in accordance with Article 690 of the applicable NEC. When paired with Powerwall 3, solar array shutdown Is Initiated by any loss of AC power. Electrical Model MCH1 MCI-2 Specifications Nominal Input DC Current Rating(1,,) 13A 13A Maximum Input Short Circuit Current (I.) 19 A Maximum System Voltage(PVHCS) 600V DC 7 Maximum System Voltage is limited by Powerwall to 600 V DC. 17A 1000 V DC7 RSD Module Maximum Number of Devices per String 5 5 Performance Control Power Line Excitation Power Line Excitation Passive State Normally Open Normally Open Maximum Power Consumption 7 W 7 W Warranty 25 years 25 years Environmental Operating Temperature -40°C to 50°C -45°C to 70°C Specifications (-40oF to 122°F) (-49°F to 158°F) Storage Temperature —300Cto701C —30°C to 70°C (-22°Fto158°F) (-22°F to 158°F) Enclosure Rating NEMA4X/IP65 NEMA 4X/IP65 Mechanical Electrical Connections MC4 Connector MC4 Connector Specifications Housing Plastic Plastic Dimensions 125 x150 x 22 man 173 x45 x 22 man (5 x6 x1 in) (6.8 x 1.8 x1 in) Weight 350 g (0.77lb) 120 g (0.26 lb) Mounting Options ZEP Home Run Clip Wire Clip M4 Screw (#10) MB Bolt (5/16") Nail / Wood screw Compliance Certifications Information RSD Initiation Method UL 3741 PV Hazard Control (and PVRSA) Compatibility See Powerwall 3 Installation Manual ILL 1741 PVRSE, ILL 3741, PVRSA (Photovoltaic Rapid Shutdown Array) External System Shutdown Switch or Powerwall3 Enable Switch Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 20N 4 Gateway 3 Teals Gateway 3 controls connection to the grid in a Powerwall system, automatically detecting outages and providing seamless transition to backup power. It provides energy monitoring that is used by Powerwall for solar self -consumption, time -based control, and backup operation. Performance Model Number 1841000-01-y AC Meter Revenue accurate (+/- 0.5%) Specifications Nominal Grid Voltage 1201240 V AC Communication CAN Grid Configuration Split phase User Interface Tesla Apia Grid Frequency 60 Hz Backup Transition Automatic disconnect for seamless backup Continuous Current 200 A Rating Overcurrent 100-200A Protection Device Service entrance rated Maximum Supply Short 22 kA with Square D or Eaton CSR, BWH, or BW, or Circuit Current Eaton main breaker 25 kA with Eaton main Square D OOM breakers breakers Internal Panelboard 200 A IEC Protective Class Class I 8-space/16 circuit breakers Eaton BR, Siemens OP, or Overvoltage Category Category IV Square D HOM breakers rated to 10-125A e Only Eaton CSR or 8W H main breakers are 25 kA rated. Warranty 10 years Environmental Operating Temperature -20°C to 50oC(- olio 1227) Specifications Operating Humidity(RH) Up to 100%,condensing Maximum Elevation 3000 m (9843 ft) Environment Indoor and outdoor rated Enclosure Type NEMA 3R Compliance Certifications UL 67, UL 869A, UL 916, UL 1741 PCS, Information CSA 22.2107.1, CSA 22.2 29 Emissions FCC Part 15, ICES 003 Mechanical Dimensions 660 x411 x149 mm Specifications (26 x 16 x 6 in) Weight 16.3 kg(36 lb) Mounting options Wall mount 660 men Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 � —411 mm1 �149-a• mm 20N Powerwoi 3nam:nesc Backup Switch The Teals Backup Switch controls connection to the grid in a Powerwall system, and can be easily installed behind the utility meter or in a standalone meter panel downstream of the utility meter. The Backup Switch automatically detects grid outages, providing a seamless transition to backup power. It communicates directly with Powerwall, allowing home energy usage monitoring from any mobile device with the Teals app. Performance Model Number 1624171-xx-y Specifications Continuous Load Rating 200 A, 1201240 V split phase Maximum Supply Short Circuit Current 22 kA with breakere Communication CAN AC Meter Revenue accurate (+1- 0.5%) Expected Service Life 21 years Warranty 10years ' Breaker maximum supply short circuit current rating must be equal to or greater than the available fault current. Environmental Operating Temperature Specifications Storage Temperature Enclosure Rating Pollution Rating Compliance Safety Standards Information Emissions —40°C to 50oC (-40oF to 122°F) —40°C to 85°C (-40°F to 185°F) NEMA 313 PD3 USA: UL 414, UL 414 SB, UL 2735, UL 916, CA Prop 65 FCC, ICES Mechanical Dimensions 176 x 205 x 74 men(6.9 x 8.1 x 2.9 in) Specifications Weight 2.81le Meter and Socket Compatibility ANSI Type 2S, ringless or ring type External Service Interface Contactor manual overnde10 Reset button Conduit Compatibility 1/2-inch NPT '° Manually overrides the contactor position during a service event Approved for Construction b,, W. Scott Leavelle (TPI) 6-2-26 20N Powerwall 3 Data:heet 6 Backup Gateway 2 Backup Gateway 2 controls connection to the grld when paired with Powerwall3, automatically detecting outages and providing seamless transition to backup power. Backup Gateway 2 also provides energy metering for solar self -consumption, time -based control, and backup operation. In this system configuration, Powerwall 3 acts as the Site Controller, with the Backup Gateway 2 Site Controller disabled. Performance Model Number 1232100-xx-y Specifications AC Voltage (Nominal) 120/240 V Feed -in Type Split phase Grid Frequency 60 Hz Currant Rating 2DOA Maximum Supply Short 10 kA11 Circuit Current Overcurrent Protection 100-200 A, Service Device entrance rated- Overvoltage Category Category IV Internal Primary Revenue accurate AC Meter (+/-0.2%) Internal Auxiliary Revenue accurate AC Meter (+/-2%) Primary Connectivity Ethernet, Wi-Fi Secondary Connectivity Cellular (3G, LTE/40)'a User Interface Tesla Apia Operating Modea Support for solar self - consumption, time -based control, and backup Backup Transition Automatic disconnect for seamless backup Modularity Supports uptolOAC- coupled Powerwalls Optional Internal 200 A 8-space / 12 circuit Panelboard. breakers Siemens OF or Square D HOM breakers rated 10 - BOA or Eaton BR breakers rated 10 -125A Warranty 10 years When protected by Class 1 fuses, Backup Gateway 21s suitable for use in circuits capable of delivering not more than 22kA symmetrical ampama Cellular connectivity subiect to network operator service coverage and signal strength. Environmental Operating Temperature -20oC to 50oC (-4°F to 122°F) Specifications Operating Humidlty(RH) Up to 100%,condensing Maximum Elevation 3000 in (9843 ft) Environment Indoor and outdoor rated Enclosure Type NEMA 313 Compliance Certifications UL 67, UL 669A, UL 916, UL 1741 PCs, Information CSA 22.2 0.19, CSA 22.2 205 Emissions FCC Part 15, ICES 003 Mechanical Dimensions BBO x 411 x149 men [1-411 man �149. Specifications (26 x16x 6 in) — — _ Inln Weight 20.4 kg (4516) I Mounting options Well mount, Semi -flush mount * 2 s u e I I Approved for Construction by: OOC man W. Scott Leavelle (TPI) 6-2-26 Ii 20N Pcwerwall3 Datasheet J_ Powerwall 3 Example System Configurations Powerwall 3 with Gateway 3 Whole Home Backup (C-2-E-S- 4 Grid Meter socket panel Gateway 3 Load center I �r Backup loads Powerwall 3 Powerwall 3 with Backup Switch I ePeoaa,— 1 Whole Home Backup \ / —��I Backup Switch I I — Solar — l ® Meter � 4 J Grid Meter socket panel Load center I J Backup loads Powerwall 3 IOPtiwral- � GT) I ♦♦/ I I I Solar -- Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 Powerwall 3 with Backup Gateway 2 Partial Home Backup \ / I�� I Utility Meter I I 0 I —Solar _ Main (V—P-- Breaker Grid Meter load center Backup Gateway 2 Load center 1 1 Non -essential loads Backuploads Powerwall 3 20N Powerwall 3 Datasheet a Solar Shutdown Device Technical Specifications The Solar Shutdown Device is a Mid -Circuit Interrupter (MCI) and is part of the PV system rapid shutdown (RSD) function in accordance with Article 690 of the applicable NEC. When paired with Powerwall+, solar array shutdown is Initiated by any loss of AC power. Electrical Model Mcl-1 MCF2 Specifications Nominal Input DC Current Rating (I"o) 13 A 13 A Maximum Input Short Circuit Current (Ise) 19 A 17 A Maximum System Voltage (PVHCS) 600 V DC 1000 V DOe 'QMaximum System Voltage Is limited by Powerwall+to 600 V DC. RSD Module Performance Environmental Specifications Mechanical Specifications Maximum Number of Devices per String Control Passive State Maximum Power Consumption Warranty Operating Temperature Storage Temperature Enclosure Rating E Power Line Excitation Normally Open 7W 25 years -40°C to 50°C (-40°F to 122°F) -30°C to 70°C (-22-F to 158°F) NEMA 4x / IP65 5 Power Line Excitation Normally Open 7W 25 years -45°C to 70°C (-49°F to 158°F) -30°C to 70°C (-22°F to 158°F) NEMA 4x / IP65 Electrical Connections MC4 Connector MC4 Connector Housing Plastic Plastic Dimensions 125 x 150 x 22 mm 173 x 45 x 22 mm (S x6 x1 in) (6.8 x 1.8 x1 in) Weight 350 g (0.77 lb) 120 g (0.26 lb) Mounting Options ZEP Home Run Clip Wire Clip M4 Screw (#10) MS Bolt (5/16") Nail / Wood screw Compliance certifications Information RSD Initiation Method UL 3741 PV Hazard Control (and PVRSA) Compatibility UL 1741 PVRSE, UL 3741, PVRSA (Photovoltaic Rapid Shutdown External System Shutdown Switch Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 See Powerwall+ Installation Manual 2024 Powerwall+Datasheat 4 i System designed with 41t All parts fit in a box for easy ` maximum versatility for any logistics arrays including staggered f+� Drop -in features make the f`Jl install process intuitive and fast Simple design allows system to be installed by single installer Listed to UL Standard 2703 for on the roof & Grounding/Bonding and Fire Classification Flash Track with Patented Umbrella Technology Single Umbrella lag screw secures flashing and flash track to roof in one complete action Umbrella technology provides weatherproofing with a long- lasting mechanical seal Flash track is designed for maximum versatility with 6 inches of North -South adjustability for all Mounts rXpP(ovea for Uonsuuouori oy: W. Scott Leavelle (TPI) Mounts 6-2-26 • Single mount used at all locations on array • Extreme time saver by eliminating link interference through the flexibility of the Mount to change orientation • Features a rock -in channel nut design for easy attachment to Flash Track • Slotted riser provides leveling for easy height adjustments `A �s Links • Simple design provides mounting platform between two to four modules • Clamps onto top of modules securing them in place while providing row -to -row bonding • Next row of modules easily slides into place as with the Mounts Skirt • Easily locks to bottom of module mounts and links for clean aesthetics • Ensures a strong structure for leveling and alignment of first row of modules • Skirt length is compatible with both portrait and landscape module orientations DESCRIPTION: SNAPNRACK, TDS, ALPHATRACK (USA) PART NUMBERS): 242-10063-USA UNITS: IN, LB, DEG [MM, KG, DEG3 I SHEET: 1:2 Approved for Construction by: W. Scott Leavelle (TPI) 6-2-26 DOC NUMBER'. SNR-DC-01452 D RAWN BY: H.WULFEKOETTER REV: PATE: A I 11/21/2024 snap adko sNR SOLAR LLc nns�®SwA 161—Tam�, oNTM, O no PARTS LIST ITEM IO-ryI DESCRIPTION 1 1 SNAPNRACK, ALPHATRACK, MILL 2 1 SNAPNRACK, BUTYL PAD, 3.75IN X 1.50IN X ,25IN MATERIALS: 6000 SERIES ALUMINUM, BUTYL DESIGN LOAD (LBS): VARIES, REFER TO SNAPNRACK ENGINEERING ULTIMATE LOAD (LBS): VARIES, REFER TO SNAPNRACK ENGINEERING TORQUE SPECIFICATION: NIA FT-LBS CERTIFICATION: UL 2703, FILE E359313, DOMESTIC CONTENT COMPLIANT WEIGHT (LBS): 0.43 DESCRIPTION: DOC NUMBER: SNAPNRACK, TDS, ALPHATRACK (USA) SNR-DC-01452 D RAWN BY: PART NUMB ER(S): H. W ULFEKOETTER 242-10063-USA REV: DATE: UNITS: IN, LB, DEG [MM, KG, DEG] I SHEET: 2:2 A 11/21/2024 -- JS [1+11 '0 j 4ss [a7.6] 1.so Snap ack@ 3.)0 [76.2] SNR SOLAR LLC s.,®'e 'A' .R.oH..E 3.78 [95.9] 5J5 [145.11 Approved for Construction by: W. Scott Leavelle (TPI) 1.10 —� � [28.01 1.27 .15 [321.21 [11z I } 2.44 �[62.02.0] FOR SNAPNRACK ENGINEERING TO APPLY, THE EMBEDMENT CRITERIA SHOWN HEREIN MUST BE MET (IF CRITERIA CANNOT BE MET OR SPANS ARE NOT SUFFICIENT, CONTACT SNAPNRACK FOR SUPPORT). REFER TO SNAPNRACK INSTALLATION MANUAL FOR '&" 0 HARDWARE TORQUE SPECIFICATIONS. REFER TO MANUFACTUER SPECIFICATIONS FOR OTHER FASTENER TORQUE REQUIREMENTS. BUTYL DETAIL (DECKANCHOR SHOWN) TRP TYL ROOF DECKING STRUCTURAL ROOF MEMBER��' (RAFTER) TYP. REVISION: A 8/9/2024 D0004258 MKW A 9/16/2024 DC004258 MKW DMCI - M-DIAI ND COMPLETED DECK INSTALLATION Approved for Construction by: 05/6" S.S. LAG SCREW W. Scott Leavelle (TPI) ROOFING MATERIAL, TYP. 6-2-26 ALPHATRACK� ALPHATRACK / 2-1/2" MIN. EMBEDMENT INTO STRUCTURAL MEMBER, RAFTER TYP. � ROOF DECKING ROOF DECKING AND ROOFING MATERIAL, TYP. �RAFTER,YP COMPLETED RAFTER INSTALLATION ����nn���n S Su_ru2ouuthLLCoGwm DESIGNER: M.WATKINS ISM NTS DRAWING NUMBER: DESCRIPTION: REV: llll\\UII k- „�„EI," •F °„�„�, DRAFTER: M.WATKINS SNR-DC-00370 TOPSPEED UNIVERSAL, ATTACHMENT DETAIL, ^ Solar Mounting Solution:, E,o gppROVED BY: M.AFFENTRANGER I DATE: 9/16/2024 ALPHATRACK /`1