HomeMy WebLinkAboutCA2018-866 August 2018
A Future With A Past
Kevin Karlin
Structured Foundation Repairs, Inc
629 West College Street
Grapevine, Texas 76051
817 789-0946
RE: HISTORIC PRESERVATION COMMISSION
CERTIFICATE OF APPROPRIATENESS #CA18-86
WESTCHESTER PLACE OFFICE CONDO
STEVEN COOK, OWNER
629 WEST COLLEGE STREET
GRAPEVINE, TEXAS 76051
This letter confirms on August 6, 2018 the Historic Preservation Commission staff approved
with conditions #CA18-86 for the property addressed 629 West College Street, legally
described as Lot D, Westchester Place Office Condo, City of Grapevine Texas. The following
was approved on this Certificate of Appropriateness:
1. Foundation repair to existing building, to include installation of 14 concrete
pressed pilings to support the foundation;
as per attached plans with the conditions that a permit be obtained from the
Building Department.
An approved Certificate of Appropriateness is not an approved building permit; a
building permit is / is not required. Contact the City of Grapevine's Building
Department at 817.410.3165 for fees and information regarding permits.
Thank you,
olyn J�L,
David Klempin
Historic Preservation Officer
cc. Property Owner
CA File
THE CITY OF GRAPEVINE
HISTORIC PRESERVATION • 636 South Main Street • Grapevine, Texas 76051
Phone 817/410-3556 - Fax 817/410-3038
Date
8/3/2018
CERTIFICATE OF APPROPRIATENESS APPLICATION
Property Owner Name, Address 8r Phone Number
Steven Cook (Investor)
627 W College Street, Grapevine, TX. 76051
Phone: 817-789-0946
Mobile:
Email:
Property Address include any suite number
629 W College Street
Grapevine, TX. 76051
446 3 6A
Applicant Name, Address & Phone Number
Kevin Karlin/ Structured Foundation Repairs Inc.
13301 Trinity Blvd. #133 Euless, TX. 76040
Phone: 972-484-1200
Mobile
Emall:
Le al Description
Block Lot
Subdivision
Tenant Name/Occupancy/Use tj i C5 S
Residence (� i' Bui -J)y 4
Request/Description of Work to Be Done
Install 14 concrete pressed pilings to support the foundation.
Drawings/Sketches Attached
V Yes o No
Material Sam les Attached lease list
Photo ra hs Attached
o Current o Historic
l hereby certify that this information is correct to the best of my knowledge and that the said work will be done in conformance
with all submissions herein set forth, and in compliance with the City of Grapevine's Historic Overlay District Ordinances and
Building Codes. APPROVAL OF A CERTIFICATE OF APPROPRIATENESS DOES NOT CONSTITUTE APPROVAL OF
OTHER REQUIRED BUILD NG PE�.
Signed x Print Name7 Kevin Karlin
OvVner or Contractor
Office Use
o Approved- Approved with Conditions:
Staff ►,
HPC 760'm > t (2-e- 0 t (L
o I Denied
Chair— Historic Preservation Commission
Date
Building Official
THIS IS NOT A BUILDING PERMIT. V
A SEPARATE BUILDING PERMIT MUST BE FILED AND APPROVED BY
THE BUILDING DEPARTMENT BEFORE STARTING WORK.
DELIVER TO: HISTORIC PRESERVATION DEPARTMENT OFFICE 817-410-3556
636 SOUTH MAIN STREET, GRAPEVINE, TEXAS
1902 Forest Glen LN
Weatherford, Texas 76087
817-948-4004
Info (c-Nortierl la com
Initial Report for Foundation Assessment
Date: July 26, 2018
Attention: Structured Foundation Repair (The Client)
Subject: Foundation Review
629 W College St., Grapevine, Texas
4NNOOTIEO ENGINEERING CON51JLiANiS LlC
Authorization and Scope:
Nortier Engineering Consultants, LLC (NEC) has been retained by the Client to perform a review of the
slab on grade foundation system of the 2 story residential building with brick veneer located at the subject
address referenced above. This report provides guidance as to whether or not the existing foundation
system is in need of repair. The report also proposes a recommended plan if repairs are needed.
Conclusions/Specific Recommendation:
NEC performed a visual examination of the foundation for the subject property on 7/26/2018. NEC also
performed a floor survey using a Zip -level Pro -2000 series, collecting relative floor elevations, to aid in
surface topography mapping of the floor(s). Elevations shown are adjusted for the type of flooring
encountered to reflect a consistent measuring plane. The map of the existing floor elevations can be seen
in the figure attached to this report.
Based on review of the foundation, and reasonable professional engineering opinion, we've determined
that settlement of the foundation has occurred and should be repaired. Although complete levelness
cannot be guaranteed, or may not be attainable, the proposed plan should improve the performance of the
foundation. It is recommended that fourteen (14) piers be installed as indicated on the figure(s) attached
to this report. Locations of internal piers [if needed] are intended to be approximate. The Contractor
should locate the beams and place internal piers accordingly. Furthermore, the proposed foundation
repairs shall meet or exceed the 2015 International Residential Code (IRC) and any local applicable
amendments to the IRC.
This report is solely based on information gathered during our site visit on 7/26/2018, and does not take
into consideration any changes in condition of the foundation or soils after the date which the information
was gathered.
1902 Forest Glen LN
Weatherford, Texas 76087
817-948-4004
Info(a-Mortierllc. corn
WIER ENGINEERING C0N511LiANiS LLC
General Recommendations:
It is recommended that the soil be graded such that the bottom portion of the foundation is below grade,
as per the governing code and a watering system be utilized around the perimeter of the house.
Fluctuations in moisture content of the soils near the foundation of the house can cause differential
settlement. If the moisture content is kept consistent, the potential for differential movement is mitigated.
It is also recommended that the plumbing systems be checked after any repairs are made to the foundation
system. Vertical movement of the foundation system can impose stresses on the plumbing infrastructure
and cause leaks.
Furthermore, grading around the perimeter of the building should be maintained as sloping away from the
foundation at a minimum of 6 inches fall within the first 10 feet from the foundation. Such grading
configuration should prevent localized water accumulating around areas of the foundation. Saturated
soils decline in bearing capacity and can result in differential settlement of the foundation.
Limitations:
This report is intended for information purposes only, and the sole use of the client and/or homeowner.
The scope of this report is limited to the items related to the foundation system only, and it is understood
that detection of all existing or potential defects is not feasible for this type of evaluation. The intent of
this report does not include judgment on any of the superstructure, detached buildings, retaining or
privacy walls, concrete reinforcement, and/or site drainage. In addition, the scope of this report excludes
material and soil sampling/testing, procedures and as such were not performed. The report is not to be
used by others for any purpose without our written consent. Compliance with any code or specification
other than as expressly noted in this report is specifically excluded. It is the responsibility of any
Contractor to abide by any other applicable codes or specifications.
No warranty for any repairs, future foundation performance, structure, vegetation, or soils at the subject
property are offered by this report, nor does this report imply any liability to NEC, nor Daneel Nortier, PE
for any work to be performed as a result of this report. It is understood that soils in this area experience
movement due to moisture fluctuations. Such soil movement could cause the foundation to move after the
recommended repairs have been made. Any provided floor elevation data and recommended actions are
based on soil conditions as they exist at the time of the evaluation. NEC does not warrant or imply that
other problems may not occur in the future. No warranty, expressed or implied, is made or intended and
the limit of liability shall be limited to the fee paid for this report at the time of evaluation.
Report Prepared by, o F . 7- +et I
Nortier Engineering Consultants LLC * • s*��
Texas Engineering Firm (F-16800) .•. ........
�•
of A EEL ORTIERgo
j
7/26/2018 o 11.• 15
... •.'
Daneel Nortier, P.E. • • �� ..
Professional Engineer (TX #113157) s� ,s
9 Photograph Label
SP Separation
Stress crack
Cleanout
New pier
0 10 2(
1 I I
All measurements shown in tenth of an inch
\\\
OFF
O�P�E •TF�IsI
•, 9
.• A EELORTIER
......... .. .. i
1
7/26/18 629 W. College Street
By: DN Grapevine, Texas
CERTIFICATE OF APPROPRIATENESS
CITY OF GRAPEVINE
RELEA
PURSU4bTCA
DATEoBY TM
OF
DEVELOPMENT SERVICES
CONTACT BUILDING INSPECTIONS
FOR PERMIT INFORMATION
SP
3P
WVCC11ER ENGINEERING CRNSiLiAN1S
Beam
=I I H I 1=11=
NOTES: —i H I I =1 =1 I_= III=
1) Piles shall be driven to refusal
2) Contractor shall install double
piers for shallow foundations
(6ft or less), or where indicated Steel Shims
3) Where double piers are used,
concrete blocks and steel shims
may be use in -leu of top cap
Concrete Top Cap
(Double Pier - See Note 3)
6" Diameter by 12" Long
yi
Precast Concrete Cylinder
W/ Reinforcing Steel
�S�PSE OF•T�+�S�l
....
A EEL ORTIER j
...................... i
0,, 11 15
6/20/2016 Precast Concrete Pier Detail Diagram �C
Firm # 16800 Not to scale HURTER ENRINEERIN6 CUNSULTANIS