HomeMy WebLinkAboutFargo Consultants, Inc. - 6/14/20172324 Fabens Rd. • Dallas, Texas 75229
r
Fnxaa CONSULTANTS, INC. Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: Fx Concrete
Ticket No.: 4037299
Ambient Temp. (°F): 79
Concrete Temp. (°F): 78
Time Batched: 5:17 AM
Time Sampled: 5:45 AM
SAMPLE DATE 6/14/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: Martin Marietta
Plant/Truck: 342 / 0000
Mix Id Number: F8205
Air Content (%): 4.4 (ASTM C231)
Water Added (gal): 20
Slump (inches) 6 (ASTM C143)
Weather Condition: Cloudy
Location of Placement: Fire Lane - North Site Grid Point 0-12
Mix Design Strength of Concrete ( 4000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
1A
3
6/17/2017
38830
3090
1B
7
6/21/2017
41910
3340
1 C
28
7/12/2017
61590
4900
1D
28
7/12/2017
59505
4740
1E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Informed superintendent of all field test results.
Test locations are referenced using an in-house system and are approximate.
Technician M. Strom
Fargo Consultants, Inc.
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.dagasfargo.com
2324 Fabens Rd. • Dallas, Texas 75229
r
Fnxaa CONSULTANTS, INC. Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: Fx Concrete
Ticket No.: 4037530
Ambient Temp. (°F): 80
Concrete Temp. (°F): 84
Time Batched: 6:41 AM
Time Sampled: 7:15 AM
SAMPLE DATE 6/14/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: Martin Marietta
Plant/Truck: 267 / 0000
Mix Id Number: F8205
Air Content (%): 4.9 (ASTM C231)
Water Added (gal): 15
Slump (inches) 7 (ASTM C143)
Weather Condition: Cloudy
Location of Placement: Fire Lane - North Site Grid Point Q-17
Mix Design Strength of Concrete ( 4000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
2A
3
6/17/2017
26400
2100
2B
7
6/21/2017
34200
2720
2C
28
7/12/2017
57265
4560
2D
28
7/12/2017
56630
4510
2E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Informed superintendent of all field test results.
Test locations are referenced using an in-house system and are approximate.
Technician M. Strom
Fargo Consultants, Inc.
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.dagasfargo.com
2324 Fabens Rd. • Dallas, Texas 75229
r
Fnxaa CONSULTANTS, INC. Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
CONCRETE INFORMATION
Contractor: Fx Concrete
Ticket No.: 4037774
Ambient Temp. (°F): 83
Concrete Temp. (°F): 86
Time Batched: 7:45 AM
Time Sampled: 9:16 AM
Weather Condition: Cloudy
Location of Placement: Fire Lane - North Site Grid Point Y-22
SAMPLE DATE 6/14/2017
JOB NO.: M16-4962
Concrete Supplier: Martin Marietta
Plant/Truck: 267 / 0000
Mix Id Number: F8205
Air Content (%): 3.8 (ASTM C231)
Water Added (gal): 15
Slump (inches) 6 1/2 (ASTM C143)
Mix Design Strength of Concrete ( 4000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
3A
3
6/17/2017
28270
2250
313
7
6/21/2017
43685
3480
3C
28
7/12/2017
58895
4690
3D
28
7/12/2017
59850
4760
3E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Informed superintendent of all field test results.
Test locations are referenced using an in-house system and are approximate.
Technician M. Strom
Fargo Consultants, Inc.
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.dagasfargo.com
2324 Fabens Rd. • Dallas, Texas 75229
r
Fnxaa CONSULTANTS, INC. Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: Fx Concrete
Ticket No.: 1036
Ambient Temp. (°F): 85
Concrete Temp. (°F): 85
Time Batched: 7:49 AM
Time Sampled: 10:00 AM
SAMPLE DATE 6/14/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: FX Material
Plant/Truck: 01 / 1005
Mix Id Number: F8205
Air Content (%): 3.4 (ASTM C231)
Water Added (gal): 10
Slump (inches) 2 1/4 (ASTM C143)
Weather Condition: Cloudy
Location of Placement: Fire Lane - North Site Grid Point U-24
Mix Design Strength of Concrete ( 4000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
4A
3
6/17/2017
37270
2970
413
7
6/21/2017
47270
3760
4C
28
7/12/2017
54570
4340
4D
28
7/12/2017
51575
4100
4E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Informed superintendent of all field test results.
Test locations are referenced using an in-house system and are approximate.
Technician M. Strom
Fargo Consultants, Inc.
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.dagasfargo.com
2324 Fabens Rd. • Dallas, Texas 75229
r
Fnxaa CONSULTANTS, INC. Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
CONCRETE INFORMATION
SAMPLE DATE 6/14/2017
JOB NO.: M16-4962
Contractor: Fx Concrete Concrete Supplier: FX Material
Ticket No.: 1042 Plant/Truck: 01 / Osbur
Ambient Temp. (°F): 87 Mix Id Number: F8205
Concrete Temp. (°F): 92 Air Content (%): 5.8 (ASTM C231)
Time Batched: 10:00 AM Water Added (gal): 0
Time Sampled: 11:19 AM Slump (inches) 6 1/2 (ASTM C143)
Weather Condition: Cloudy
Location of Placement: Fire Lane - North Site Grid Point T-22
Mix Design Strength of Concrete ( 4000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
5A
3
6/17/2017
28325
2250
513
7
6/21/2017
39495
3140
5C
28
7/12/2017
56440
4490
5D
28
7/12/2017
57980
4610
5E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Informed superintendent of all field test results.
Test locations are referenced using an in-house system and are approximate.
Technician M. Strom
Fargo Consultants, Inc.
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.dagasfargo.com
2324 Fabens Rd. • Dallas, Texas 75229
r
Fnxaa CONSULTANTS, INC. Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
CONCRETE INFORMATION
SAMPLE DATE 6/14/2017
JOB NO.: M16-4962
Contractor: Fx Concrete Concrete Supplier: Martin Marietta
Ticket No.: 4039422 Plant/Truck: 1001 / 0000
Ambient Temp. (°F): 90 Mix Id Number: F8205
Concrete Temp. (°F): 90 Air Content (%): 3.8 (ASTM C231)
Time Batched: 12:48 PM Water Added (gal): 15
Time Sampled: 1:35 PM Slump (inches) 5 1/4 (ASTM C143)
Weather Condition: Cloudy
Location of Placement: Fire Lane - North Site Grid Point S-26
Mix Design Strength of Concrete ( 4000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
6A
3
6/17/2017
30220
2400
613
7
6/21/2017
42420
3380
6C
28
7/12/2017
55320
4400
6D
28
7/12/2017
55295
4400
6E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Informed superintendent of all field test results.
Test locations are referenced using an in-house system and are approximate.
Technician M. Strom
Fargo Consultants, Inc.
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.dagasfargo.com
2324 Fabens Rd. • Dallas, Texas 75229
r
Fnxaa CONSULTANTS, INC. Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
CONCRETE INFORMATION
SAMPLE DATE 6/14/2017
JOB NO.: M16-4962
Contractor: Fx Concrete Concrete Supplier: FX Material
Ticket No.: 1062 Plant/Truck: 01 / Osbur
Ambient Temp. (°F): 92 Mix Id Number: F8205
Concrete Temp. (°F): 93 Air Content (%): 5.4 (ASTM C231)
Time Batched: 2:25 PM Water Added (gal): 0
Time Sampled: 3:20 PM Slump (inches) 7 (ASTM C143)
Weather Condition: Cloudy
Location of Placement: Fire Lane - North Site Grid Point S-29
Mix Design Strength of Concrete ( 4000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
7A
3
6/17/2017
29985
2390
7B
7
6/21/2017
41105
3270
7C
28
7/12/2017
62870
5000
7D
28
7/12/2017
61840
4920
7E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Informed superintendent of all field test results.
Test locations are referenced using an in-house system and are approximate.
Technician M. Strom
Fargo Consultants, Inc.
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.dagasfargo.com
2324 Fabens Rd. • Dallas, Texas 75229
r
Fnxaa CONSULTANTS, INC. Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
CONCRETE INFORMATION
Contractor: Fx Concrete
Ticket No.: 1068
Ambient Temp. (°F): 92
Concrete Temp. (°F): 93
Time Batched: 2:53 PM
Time Sampled: 3:45 PM
Weather Condition: Cloudy
Location of Placement: Fire Lane - North Site Grid Point S-31
SAMPLE DATE 6/14/2017
JOB NO.: M16-4962
Concrete Supplier: FX Material
Plant/Truck: 01 / 1005
Mix Id Number: F8205
Air Content (%): 4.6 (ASTM C231)
Water Added (gal): 0
Slump (inches) 5 1/4 (ASTM C143)
Mix Design Strength of Concrete ( 4000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
8A
3
6/17/2017
39975
3180
813
7
6/21/2017
48800
3880
8C
28
7/12/2017
68240
5430
8D
28
7/12/2017
65055
5180
SE
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Informed superintendent of all field test results.
Test locations are referenced using an in-house system and are approximate.
Technician M. Strom
Fargo Consultants, Inc.
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.