CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: FX Concrete LLC
Ticket No.: 3963663
Ambient Temp. (OF): 52
Concrete Temp. (OF): 70
Time Batched: 4:50 AM
Time Sampled: 5:30 AM
Weather Condition: Clear
SAMPLE DATE 5/6/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: Martin Marietta
Plant/Truck: 141 / 0000
Mix Id Number: F9506
Air Content (%): 1.6 (ASTM C231)
Water Added (gal): 10
Slump (inches) 5 1/2 (ASTM C143)
Location of Placement: Floor Slab, Bldg. 11 Pour 1 -Grid Point 1A-35
Mix Design Strength of Concrete (3000 psi/28 days)
Cylinder Number Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
1A
3
5/9/2017
33050
2630 77
1B
7
5/13/2017
41520
3300
1 C 28 6/3/2017
47515
3780
1D
28
6/3/2017
55415
4410
1E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Concrete was conveyed via concrete pump truck.
Test locations are referenced using an in-house system and are approximate.
Technician A. Poor
Fargo Consultants, Inc.
P' �1
Checked I v I
Davis Udeo
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.dallasfargo.com
WO
r R00 aa'NsvLxnnrxs. INC -
2324 Fabens Rd. • Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: FX Concrete LLC
Ticket No.: 3963669
Ambient Temp. ff ): 52
Concrete Temp. (°F): 70
Time Batched: 5:26 AM
Time Sampled: 6:10 AM
Weather Condition: Clear
SAMPLE DATE 5/6/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: Martin Marietta
Plant/Truck: 141 / 0000
Mix Id Number: F9506
Air Content (%): 1.6 (ASTM C231)
Water Added (gal): 10
Slump (inches) 5 1/2 (ASTM C143)
Location of Placement: Floor Slab, Bldg. 11 Pour 1 -Grid Point Y-34
Mix Design Strength of Concrete (3000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
I Total Load
(pounds)
Compressive
Strength (psi)
2A
3
5/9/2017
29695
2360
2 B
7
5/13/2017
37000
2940
2C
28
6/3/2017
49105
3910
2D
28
6/3/2017
53405
4250
2E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Concrete was conveyed via concrete pump truck.
Test locations are referenced using an in-house system and are approximate.
Technician A. Poor
Fargo Consultants, Inc.
Checked By
Davis 'OS ��
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www, dallasfatgo. com
R157
FARO CONSULTANTS. INC.
2324 Fabens Rd. • Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
CONCRETE INFORMATION
Contractor: FX Concrete LLC
Ticket No.: 3963773
Ambient Temp. (OF): 52
Concrete Temp. (°F): 71
Time Batched: 6:11 AM
Time Sampled: 6:40 AM
Weather Condition: Clear
SAMPLE DATE 5/6/2017
JOB NO.: M16-4962
Concrete Supplier: Martin Marietta
Plant/Truck: 141 / 0000
Mix Id Number: F9506
Air Content (%): 1.5 (ASTM C231)
Water Added (gal): 10
Slump (inches) 5 3/4 (ASTM C143)
Location of Placement: Floor Slab, Bldg. 11 Pour 1 -Grid Point V-33
Mix Design Strength of Concrete (3000 psi/28 days)
Cylinder Number Age Date Tested Total Load Compressive
(days) (pounds) Strength (psi)
3A
3
5/9/2017
35035
2790
3B
7
5/13/2017
43035
3420
3C
28
6/3/2017
54140 4310
3D
28
6/3/2017
49745
3960
3E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Concrete was conveyed via concrete pump truck.
Test locations are referenced using an in-house system and are approximate.
Technician A. Poor
Fargo Consultants, Inc.
Checked By
Davis Ude , u
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.daBasfargo.com
FWGO
FARGO CONBULTANTB, INC.
2324 Fabens Rd. • Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: FX Concrete LLC
Ticket No.: 3963779
Ambient Temp. (OF): 53
Concrete Temp. (°F): 74
Time Batched: 6:42 AM
Time Sampled: 7:10 AM
Weather Condition: Clear
SAMPLE DATE 5/6/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: Martin Marietta
Plant/Truck: 141 / 0000
Mix Id Number: F9506
Air Content (%): 1.6 (ASTM C231)
Water Added (gal): 10
Slump (inches) 6 (ASTM C143)
Location of Placement: Floor Slab, Bldg. 11 Pour 1 -Grid Point Y-36
Mix Design Strength of Concrete (3000 psi/28 days)
Cylinder Number
Age
(days)
I Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
4A
3
5/9/2017
33530
2670
4B
7
5/13/2017
35580
2830
4 C
28
6/3/2017
53450
4250
4D
28
6/3/2017
50135
3990
4 E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Concrete was conveyed via concrete pump truck.
Test locations are referenced using an in-house system and are approximate.
Technician A. Poor
Fargo Consultants, Inc.
Checked By
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
wwww dallasfargo. com
F,9700
FARGID 0ONSULTANTS. INC.
2324 Fabens Rd. • Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: FX Concrete LLC
Ticket No.: 3964033
Ambient Temp. (°F): 54
Concrete Temp. (°F): 76
Time Batched: 7:26 AM
Time Sampled: 8:00 AM
Weather Condition: Clear
SAMPLE DATE 5/6/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: Martin Marietta
Plant/Truck: 141 / 0000
Mix Id Number: F9506
Air Content (%): 1.5 (ASTM C231)
Water Added (gal): 10
Slump (inches) 5 1/2 (ASTM C143)
Location of Placement: Floor Slab, Bldg. 11 Pour 1 -Grid Point W-35
Mix Design Strength of Concrete (3000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
5A
3
5/9/2017
33150
2640
5B
7
5/13/2017
45715
3640
5C
28
6/3/2017
47765
3800
5D
28
6/3/2017
50645
4030
5E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Concrete was conveyed via concrete pump truck.
Test locations are referenced using an in-house system and are approximate.
Technician A. Poor
Fargo Consultants, Inc.
Checked By
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.dabasfatgo.com
FWGG
f ARGO CONSULTANTS, iNC
2324 Fabens Rd. • Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: FX Concrete LLC
Ticket No.: 3964160
Ambient Temp. (°F): 62
Concrete Temp. (°F): 80
Time Batched: 7:59 AM
Time Sampled: 8:30 AM
Weather Condition: Clear
SAMPLE DATE 5/6/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: Martin Marietta
Plant/Truck: 141 / 0000
Mix Id Number: F9506
Air Content (%): 1.7 (ASTM C231)
Water Added (gal): 20
Slump (inches) 6 (ASTM C143)
Location of Placement: Floor Slab, Bldg. 11 Pour 1 -Grid Point U-34
Mix Design Strength of Concrete ( 3000 psi/28 days)
Cylinder Number
Age I
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
6 A
3
5/9/2017
26970
2150
6 B
7
5/13/2017
35395
2820
6 C
28
6/3/2017
46085
3670
6 D
28
6/3/2017
47535
3780
6 E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Concrete was conveyed via concrete pump truck.
Test locations are referenced using an in-house system and are approximate.
Technician A. Poor
Fargo Consultants, Inc.
Checked By
Davis Udeogu
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Setvices
www dallasfargo. com
L1Vja0M=16_
FAROO CONSULTANTS, INC.
2324 Fabens Rd. • Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: FX Concrete LLC
Ticket No.: 378
Ambient Temp. (OF): 70
Concrete Temp. (OF): 84
Time Batched: 7:50 AM
Time Sampled: 8:55 AM
Weather Condition: Clear
SAMPLE DATE 5/6/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: Fx Materials, LLC
Plant/Truck: 1 / 1004
Mix Id Number: F9506
Air Content (%): 1.4 (ASTM C231)
Water Added (gal): 10
Slump (inches) 6 (ASTM C143)
Location of Placement: Floor Slab, Bldg. 11 Pour 1 -Grid Point X.5-37.5
Mix Design Strength of Concrete (3000 psi/28 days)
Cylinder Number
Age
(days)
I Date Tested
Total Load Compressive
(pounds) Strength (psi)
7 A
3
5/9/2017
32660
2600
7 B
7
5/13/2017
40905
3260
7 C
28
6/3/2017
53100
4230
7 D
28
6/3/2017
48370
3850
7 E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Concrete was conveyed via concrete pump truck.
Test locations are referenced using an in-house system and are approximate.
Technician A. Poor
Fargo Consultants, Inc.
Checked 13
Davis Ude u
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www.daZfasfatgo.com
R9760
FARGO CONS 11 UTANTS. INC:
2324 Fabens Rd. • Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: FX Concrete LLC
Ticket No.: 380
Ambient Temp. (OF): 73
Concrete Temp. (OF): 85
Time Batched: 8:59 AM
Time Sampled: 10:00 AM
Weather Condition: Clear
SAMPLE DATE 5/6/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: Fx Materials, LLC
Plant/Truck: 1 / 1005
Mix Id Number: F9506
Air Content (%): 1.5 (ASTM C231)
Water Added (gal): 10
Slump (inches) 5 1/2 (ASTM C143)
Location of Placement: Floor Slab, Bldg. 11 Pour 1 -Grid Point W-36
Mix Design Strength of Concrete (3000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested Total Load
(pounds)
I Compressive
Strength (psi)
8A
3
5/9/2017
31890
2540
8B
7
5/13/2017
37945
302077
8C
28
6/3/2017
53805
4280
8 D
28
6/3/2017
50890
4050
8 E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Concrete was conveyed via concrete pump truck.
Test locations are referenced using an in-house system and are approximate.
Technician A. Poor
Fargo Consultants, Inc.
Checked Iiy
Davis Udeo
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engmeedng • Construction Materials Testing • Environmental Services
www. dallasfargo. com
M70
i AR00 CONSULTANTS, FNC
2324 Fabens Rd. • Dallas, Texas 75229
Tel. 214-352-4100 Fax. 214-352-4811
CONCRETE COMPRESSIVE STRENGTH REPORT
CLIENT: JLB Partners, LP
PROJECT: Grapevine Bluffs
Grapevine, Texas
Contractor: FX Concrete LLC
Ticket No.: 386
Ambient Temp. (°F): 77
Concrete Temp. (°F): 87
Time Batched: 10:03 AM
Time Sampled: 11:00 AM
Weather Condition: Clear
SAMPLE DATE 5/6/2017
JOB NO.: M16-4962
CONCRETE INFORMATION
Concrete Supplier: Fx Materials, LLC
Plant/Truck: 1 / 1003
Mix Id Number: F9506
Air Content (%): 1.5 (ASTM C231)
Water Added (gal): 10
Slump (inches) 6 (ASTM C143)
Location of Placement: Floor Slab, Bldg. 11 Pour 1 -Grid Point U-35
Mix Design Strength of Concrete (3000 psi/28 days)
Cylinder Number
Age
(days)
Date Tested
Total Load
(pounds)
Compressive
Strength (psi)
9A
1 3
1 5/9/2017
32150 1 2560
9B
7
1 5/13/2017
1 38800 3090
9C
28 1 6/3/2017
1 49820
1 3960
9D
28
1 6/3/2017
1 55325
1 4400
9E
Hold
Cylinder Type: Nominal Cylinder Size (ASTM C39) 4 -inch by 8 -inch
Test Methods: Making and Curing (ASTM C31) Testing Methods (ASTM C39)
Remarks: Concrete was conveyed via concrete pump truck.
Test locations are referenced using an in-house system and are approximate.
Technician A. Poor
Fargo Consultants, Inc.
y -�
Checked By
Davis Udea U'z
Project Manager
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based on
data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.
Geotechnical Engineering • Construction Materials Testing • Environmental Services
www dallasfargo. com