REPORT OF FIELD COMPACTION Page 1 of I
Tested For: JLB Partners, LP Date Performed: 2/11/2017
Project Name: Grapevine Bluff Apartments Fargo Job No. M16-4962
Gra eyine, Texas
Density and Moisture: Per ASTM D-6938 Gauge Manufacturer: Humboldt
Test Mode: Direct Transmission Gauge Model: HS-5001EZ
Probe Depth: 8 Inches
Moisture -Density Relations
Proctor No. Material Description Opt. MC(%) Max DD (pcj) DD Range (°/n) MC Range
1 Light Gray SANDY CLAY 18.9 105.5 95 to 100 0 to +4
5 Reddish Brown SANDY CLAY with Brown and Tan CLAY (mix) 16.8 106.1 95 to 100 0 to +4
Field Test Results
Test Elevation
Proctor
DryDensity Percent
Percent
No. ILift Location
No
(pcfi Moisture
Density
36 1ST PARKING AREA FIRE LANE GRID POINT Q-13 (SOUTH SITE GRID)
1
102 20.6
96.7
37 1ST PARKING AREA FIRE LANE GRID POINT Q-20 (SOUTH SITE GRID)
5
103.5 16.8
97.5
38 1ST PARKING AREA FIRE LANE GRID POINT T-14 (SOUTH SITE GRID)
5
104.7 20.4
98.7
39 1ST PARKING AREA FIRE LANE GRID POINT T-19 (SOUTH SITE GRID)
5
105.1 17.7
99.1
40 9TH FIRE LANE GRID POINT K-8 (NORTH SITE GRID)
5
104.4 16.8
98.4
41 9TH FIRE LANE GRID POINT G-8 (NORTH SITE GRID)
5
1039 18.6
97.9
42 9TH FIRE LANE GRID POINT 1-8 (NORTH SITE GRID)
5
102 19.7
96.1
43 3RD FIRE LANE GRID POINT H-8 (NORTH SITE GRID)
5
105.1 16.9
99.1
Source of Compaction Requirements: Geotechnical Report
Respectfully Submitted,
Fargo onsultanls, Inc.
Test result with asterisk (*), if any, indicates non-compliance to provided guidelines.
"REVISED REPORT*
Revised Report to reflect correct location for test #40-43
Moore, CET
Test locations are referenced using an in-house system and are approximate.
�7carterials
Testing Division
The information and results shown on this report are for the exclusive use of the client and the client's designated recipients on file in our office. Test results are based
on data obtained from specific samples tested at particular locations noted and are not indicative of the qualities of apparently identical or similar specimens, composition,
performance, etc. The use of our name and test results must receive our written approval. Reports must be reproduced in their entirety.