HomeMy WebLinkAboutTerracon - 10/11/2018CONCRETE COMPRESSIVE STRENGTH TEST REPORT Irerracon
Report Number: 95181011.0491
Service Date: 10/11/18 2501 E Loop 820 N
Report Date: 10/26/18 Fort Worth, TX 76118-6978
Task: Parkine Garace 817-268-8600 Ree No: F-3272
Client Project
Coury Hospitality
Attn: Mark Brooks
7134 S Yale, Ste 400
Tulsa, OK 74136
Grapevine Main Phase 1
815 South Main Street
Grapevine, TX 76051
Project Number: 95181011
Material Information
Sample Information
Specified Strength: 5,000
psi @ 28
days
Sample Date:
10/11/18 Sample Time: 1550
Sampled By:
Kristopher McGarry
Mix ID: 9041
Weather Conditions:
Clear, low wind
Supplier: ARGOS
Accumulative Yards:
9/34 Batch Size (cy): 9
Batch Time: 1450
Plant:
123
Placement Method:
Bucket & lift
Truck No.: 6288
Ticket No.:
12333343
Water Added Before (gal):
0
Water Added After (gal):
0
Field Test Data
Sample Location:
Beam on level 4 of parking @ P13/16
Test
Result
Specification
Placement Location:
Beams on level 4 parking, line P 13
Slump (in):
9
5-9
from 15-18 and line 18 from P12 -P13
Air Content (%):
3.0
3-6
Concrete Temp. (F):
73
Ambient Temp. (F):
68
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Laboratory Test Data
Age at Maximum
Compressive
Set Specimen Avg Diam. Area
Date Date
Test Load
Strength Fracture Tested
No. ID (in)
(sq in)
Received Tested
(days) (lbs)
(psi) Type By
1 A 4.00
12.57
10/15/18
4 66,500
5,290 4
1 B 4.00
12.57
10/18/18
7 73,090
5,820 3
1 C 4.00
12.57
11/08/18
28
1 D 4.00
12.57
11/08/18
28
1 E 4.00
12.57
11/08/18
28
Initial Cure: Outside
Final Cure: Moist
Room
Comments: Not tested for plastic unit weight.
3 day break requested after testing and samples made. One 3 day break, one 7 day break, three 28 day breaks requested by
David with Manhattan.
Samples Made By: Terracon
Services:
Terracon Rep.: Kristopher McGarry
Reported To: David w/ Manhattan
Contractor:
Report Distribution:
See attached distribution list.
Reviewed By:
Senior Project Manager
Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
cx000t, 11-16-12, xev.6 Page 1 of 1
Distribution Page Irerracon
Report Number: 95181011.0491
Service Date: 10/11/18 2501 E Loop 820 N
Report Date: 10/26/18 Fort Worth, TX 76118-6978
Task: Parking Garage 817-268-8600
Distribution List
(1) Coury Hospitality, Mark Brooks
(1) AECC Inc, Lee Ledet
(1) ArchiTexas, Michael Karnowski
(1) City of Grapevine TX, Curtis A Bergthold
(1) City of Grapevine TX, Hans Strayer
(1) City of Grapevine TX, Paul M Lee
(1) City of Grapevine TX, Scott Williams
(1) City of Grapevine TX, sbatte@grapevinetexas.gov
(1) Construction Management Group of Fair Oaks CA, Blake Cearley
(1) JQ Engineering, Mike Oler
(1) Manhattan Construction Co, Ben Jensen
(1) Manhattan Construction Co, Chase Pritchard
(1) Manhattan Construction Co, Daniel Rideau
(1) Manhattan Construction Co, David Saiter
(1) Manhattan Construction Co, Frederick Moore
(1) Manhattan Construction Co, Jaehyung Ahn
(1) Manhattan Construction Co, Klint Robertson
(1) Manhattan Construction Co, Matthew Powell
(1) Manhattan Construction Co, Robert Montgomery
(1) Walker Consultants, Martha M. Villanueva