HomeMy WebLinkAboutTerracon - 10/25/2018CONCRETE COMPRESSIVE STRENGTH TEST REPORT Irerracon
Report Number: 95181011.0505
Service Date: 10/25/18 2501 E Loop 820 N
Report Date: 10/31/18 Fort Worth, TX 76118-6978
Task: Hotel 817-268-8600 Ree No: F-3272
Client Project
Coury Hospitality
Attn: Mark Brooks
7134 S Yale, Ste 400
Tulsa, OK 74136
Grapevine Main Phase 1
815 South Main Street
Grapevine, TX 76051
Project Number: 95181011
Material Information Sample Information
Specified Strength: 7,000 psi @ 28 days
Mix ID: 9908
Supplier: Argos
Batch Time: 1218 Plant: 123
Truck No.: 5120 Ticket No.: 12333580
Field Test Data
Test
Slump (in):
Air Content (%):
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Laboratory Test Data
Result
Specification
5
3-5
1.9
0-3
75
50-95
60
1
151.0
4.00
Set Specimen Avg Diam.
No.
ID
(in)
1
A
4.00
1
B
4.00
1
C
4.00
1
D
4.00
1
E
4.00
1
F
4.00
1
G
7
Initial Cure:
Outside
10/26/18
Comments:
Samples Made By: Terracon
Sample Date:
10/25/18 Sample Time: 1315
Sampled By:
Jeremy Washington
Weather Conditions:
Clear
Accumulative Yards:
9/70 Batch Size (cy): 9
Placement Method:
Pump
Water Added Before (gal):
0
Water Added After (gal):
0
Sample Location:
Grid Line 9.8/G.6 going East
Placement Location:
Hotel, Northside, Grade Beams, Grid
4
Line 7.6 -9.8/C.5 -G.6
Age at Maximum
Area
Date
Date
Test
Load
(sq in)
Received
Tested
(days)
(lbs)
12.57
10/26/18
10/26/18
1
50,030
12.57
10/26/18
10/29/18
4
99,890
12.57
10/26/18
11/01/18
7
12.57
10/26/18
11/22/18
28
12.57
10/26/18
11/22/18
28
12.57
10/26/18
11/22/18
28
10/26/18
Hold
Final Cure: Moist Room
Compressive
Strength Fracture Tested
(psi) Type By
3,980 4
7,950 3
Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Terracon Rep.: Jeremy Washington
Reported To: David with Manhattan
Contractor: Manhattan
Report Distribution:
See attached distribution list. Reviewed By:
Senior Project Manager
Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
cx000t, 11-16-12, xev.6 Page 1 of 1
Distribution Paae
Report Number:
95181011.0505
Service Date:
10/25/18
Report Date:
10/31/18
Task:
Hotel
Distribution List
(1) Coury Hospitality, Mark Brooks
(1) AECC Inc, Lee Ledet
(1) ArchiTexas, Michael Karnowski
(1) City of Grapevine TX, Curtis A Bergthold
(1) City of Grapevine TX, Hans Strayer
(1) City of Grapevine TX, Paul M Lee
(1) City of Grapevine TX, Scott Williams
(1) City of Grapevine TX, sbatte@grapevinetexas.gov
(1) Construction Management Group of Fair Oaks CA, Blake Cearley
(1) JQ Engineering, Mike Oler
(1) Manhattan Construction Co, Ben Jensen
(1) Manhattan Construction Co, Chase Pritchard
(1) Manhattan Construction Co, Daniel Rideau
(1) Manhattan Construction Co, David Saiter
(1) Manhattan Construction Co, Frederick Moore
(1) Manhattan Construction Co, Jaehyung Ahn
(1) Manhattan Construction Co, Klint Robertson
(1) Manhattan Construction Co, Matthew Powell
(1) Manhattan Construction Co, Robert Montgomery
(1) Walker Consultants, Martha M. Villanueva
Irerracon
2501 E Loop 820 N
Fort Worth, TX 76118-6978
817-268-8600