HomeMy WebLinkAboutTerracon - 11/13/2018 (3)CONCRETE COMPRESSIVE STRENGTH TEST REPORT Irerracon
Report Number: 95181011.0538
Service Date: 11/09/18 2501 E Loop 820 N
Report Date: 11/13/18 Fort Worth, TX 76118-6978
Task: Parking Garage 817-268-8600 Reg No: F-3272
Client
Coury Hospitality
Attn: Mark Brooks
7134 S Yale, Ste 400
Tulsa, OK 74136
Material Information
Specified Strength: 5,000 psi @ 28 days
Mix ID: 9041
Supplier: Argos
Batch Time: 1125 Plant: 123
Truck No.: 7096 Ticket No.: 12333982
Field Test Data
Test
Slump (in):
Air Content (%):
Concrete Temp. (F):
Ambient Temp. (F):
Plastic Unit Wt. (pcf):
Yield (Cu. Yds.):
Laboratory Test Data
Result Specification
9 5-9
4.4 3-6
64
52
146.8
Set
Specimen
Avg Diam.
Area
Date
No.
ID
(in)
(sq in)
Received
1
A
4.00
12.57
11/10/18
1
B
4.00
12.57
11/10/18
Project
Grapevine Main Phase 1
815 South Main Street
Grapevine, TX 76051
Project Number: 95181011
Sample Information
Sample Date:
Sampled By:
Weather Conditions:
Accumulative Yards:
Placement Method:
Water Added Before (gal):
Water Added After (gal):
Sample Location:
Placement Location:
Age at Maximum
Date
Test Load
Tested
(days) (lbs)
11/12/18
3 73,290
11/16/18
7
1 C 4.00 12.57 11/10/18 12/07/18 28
1 D 4.00 12.57 11/10/18 12/07/18 28
1 E 4.00 12.57 11/10/18 12/07/18 28
1 F 11/10/18 Hold
Initial Cure: Outside Final Cure: Moist Room
Comments:
11/09/18 Sample Time: 1157
Christopher Thompson
Clear
6/12 Batch Size (cy): 6
Pump
Grid Line L2-L3
Garage Pour Strips Ramp, Grid Line
L2-L3 and L3 East
Compressive
Strength Fracture Tested
(psi) Type By
5,830 2
Samples Made By: Terracon
Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength
samples.
Terracon Rep.: Christopher Thompson
Reported To:
Contractor:
Report Distribution:
See attached distribution list.
Reviewed By:
Senior Project Manager
Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Cx000t, 11-16-12, xev.6 Page 1 of 1
Distribution Page Irerracon
Report Number: 95181011.0538
Service Date: 11/09/18 2501 E Loop 820 N
Report Date: 11/13/18 Fort Worth, TX 76118-6978
Task: Parking Garage 817-268-8600
Distribution List
(1) Coury Hospitality, Mark Brooks
(1) AECC Inc, Lee Ledet
(1) ArchiTexas, Michael Karnowski
(1) City of Grapevine TX, Curtis A Bergthold
(1) City of Grapevine TX, Hans Strayer
(1) City of Grapevine TX, Paul M Lee
(1) City of Grapevine TX, Scott Williams
(1) City of Grapevine TX, sbatte@grapevinetexas.gov
(1) JQ Engineering, Mike Oler
(1) Manhattan Construction Co, Ben Jensen
(1) Manhattan Construction Co, Chase Pritchard
(1) Manhattan Construction Co, Daniel Rideau
(1) Manhattan Construction Co, David Saiter
(1) Manhattan Construction Co, Frederick Moore
(1) Manhattan Construction Co, Klint Robertson
(1) Manhattan Construction Co, Matthew Powell
(1) Manhattan Construction Co, Robert Montgomery
(1) Walker Consultants, Martha M. Villanueva