February 14, 2018
Grapevine - Colleyville ISD
30510 Ira E Woods Ave
Grapevine, TX 76051
Attention: Ms. Calva Powell
Re: Field Inspection of Structural Steel
Mustang Panther Stadium
Pkg A & Pkg B
Grapevine, Texas
ALPHA Report No. F171917-119
Alpha Testing arrived on site to perform a Visual Structural Steel Inspection for the above referenced
project. Results of the inspection are as follows:
I Type 2.0CD 20 gauge Composite Floor Deck and ¾’ Nelson Studs - Concession Stand “C” – lines
C1 to C13 & CJ to C16:
A. The decking was fastened per project specifications to the steel supports with 5/8”
puddle welds on a 36/4 pattern. Side supports were fastened with 5/8” puddle welds
every 12” o/c. Compliant.
B. Per “Floor Deck General Note” (12) on sheet S0.0, the perimeter of the decking
is to be fastened to the grade beam with Hilti Fasteners every 12” c/c. At (3)
locations the Hilti fasteners have not been installed per specifications. Areas
marked for reference. Non-Compliant.
C. The decking side laps were fastened per project specifications with #10 TEK screws
equally spaced between the supports at 36” o/c max. Compliant.
D. The ¾” nelson studs were inspected per detail 3/S7.1 and sheets S2.4 and E1.0 with
no discrepancies found at time of inspection. Compliant.
*Discrepancies, if any, are noted above in bold.
INSPECTOR:
Chris Lalic
CWI#16010691
We are pleased to be of service on this project and if you have any questions, please contact our office.
Sincerely yours,
ALPHA TESTING, INC.
Tim Begole Sr.
Project Manager
5058 Brush Creek Road
Fort Worth, Texas 76119
Geotechnical I Construction Materials I Environmental
www.alphatesting.com
TBPE Firm No. 813
Our test results and reports are for the exclusive use of the client (and their designated recipients on file in our office) and shall not be reproduced and/or distributed except
with express approval of ALPHA. The use of our name and test results must receive our written approval. Test results and reports apply only to the samples tested and/or
observed, and are not indicative of the qualities of apparently identical or similar specimens.