Loading...
HomeMy WebLinkAboutSchneider Electric Services - 8/11/2018Grapevine, TX WO-05206513 Start-up and Commissioning Table of Contents Job #WO-05206513 PAGE NO. Site Location MAYERS ELECTRICCustomer GCISDEnd User DeviceDesignation Substation Cover Letter Main Panelboard Main Panelboard Main Breaker 03001 - SE LOW VOLT. PWR. CKT. BKR. Main Panelboard Main Panelboard Main Panelboard 21001 - SE Switchboard / Switchgear Inspection Main Panelboard Main Panelboard PRESS BOX 03001 - SE LOW VOLT. PWR. CKT. BKR. Grapevine, Texas WO-05206513 Service Report August 11, 2018 GCISD Jimmy Hopkins 3001 IRA East Woods Project #: Subject: Customer PO.: Scope of Work Summary Report Organization ZONE INTLK BREAKER TYPE TRIP UNIT TYPE 0202343270080001 BKR INT. RATING MOUNTING HUMIDITY WO-05206513 LOW VOLTAGE POWER CIRCUIT BREAKER TEMPERATURE 93 °F PAGE END USER CUSTOMER Main Panelboard GCISD SITE LOCATION Main BreakerDESIGNATION SUBSTATION Main Panelboard DATE END USER ASSET/ID 7/31/2018 69 MAYERS ELECTRIC JOB # % DBID Main Breaker 08-638210 DEVICE 03001 - SE LOW VOLT. PWR. CKT. BKR. TESTED BY EQUIPMENT USEDAndrew Howard 1600 A N/A N/A N/A MATCHES DWG OR SPEC GROUND CONNECTION ONR1200 K MANUFACTURER FUSE MFR. BKR CATALOG NO.RKF36160U44ASA N/AFUSE CAT. NO. 2500 A OFF B.I. THERMAL MEMORY SENSOR TAPS FRAME SIZE MAIN / ARCING CONTACTS BATTERY STATUS PRIMARY DISCONNECTS CELL AND RACKING DEV. CLEAN/LUBE DESCRIPTION CLEAN/LUBECONDITION Acceptable Acceptable Acceptable N/A N/A ARC CHUTES SECONDARY DISCONNECT CONDITIONDESCRIPTION CLEAN/LUBE N/AAcceptable DESCRIPTION N/A N/A N/AOPERATING MECHANISM N/A PHASE BARRIERS Acceptable N/A N/AAUXILIARY DEVICES BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS OVERALL CONDITION New CONDITION N/A N/A Acceptable Acceptable N/A BREAKER NAMEPLATE INSPECTION TARGETS 03001, REVISED 4/9/2015(888) 778-2733 www.schneider-electric.us D.O. N/A N/A N/A 18153MFR. DATE / CODE 02962163TRIP UNIT SN SN / SO NO.Square D 6.0 A N/A COUNTER READING AL N/A FUSE AMPS N/A COUNTER READING AF RANGE @1000VGIG-OHMS 20°C 27.1 51.7 2.3 4.4 TEST 1 TEST 3 1.9076TEMPERATURE CORRECTION FACTOR TO 20°C, TCF TEST 2 INSULATION RESISTANCE IN:CLOSED: POLE-POLE 4.62.4 20°C ACTUAL PH A ACTUALACTUAL A - B A-GND CLOSED: POLE-GROUND OPEN: LINE-LOAD 20°C PH B PH C B-GND C-GND B - C C - A 3.0 2.9 21.8 27.3 23.2 21.441.6 5.7 40.8 5.5 52.1 44.3 CONTACT RESISTANCE - MICRO-OHMS 22 POLE 1 FUSE 2FUSE 1 FUSE 3 N/A N/A N/A POLE 3POLE 2 2221 SHORT TIME PICKUP INSTANTANEOUS PICKUP GROUND FAULT PICKUP 24.16 0.02 8.48 0.070.02 0.11 0.23 LONG TIME DELAY (tr) SHORT TIME DELAY (tsd) LONG TIME PICKUP (Ir) AS FOUND SETTING AS TESTED SETTING RANGE GROUND FAULT PICKUP (lg) GROUND FAULT DELAY (tg) MINIMUM TEST RESULTS MULTIPLIER TEST AMPS MAXIMUM PARAMETER INVERSE DEFINITE MIN. TIME LAG (idmtl) SHORT TIME PICKUP (Isd) INSTANTANEOUS PICKUP (li) GROUND FAULT PUSH TO TRIP BUTTON LT SWITCH SETTING (Io): SENSOR RATING (In): CURRENT LEVEL Acceptable Acceptable Acceptable PARAMETER TESTED Test Passed TRIP TIME x In x In Sec x lr Sec x In x In 1600 1 0.5 OFF 1.5 0.1 2 0.31 0.1 0.31 2 0.1 1.5 OFF 0.5 1 1600 x In x In Sec x lr Sec x In x In Sec A I2T ONAS LEFT SETTING x In x In Sec x lr Sec x In x In Sec0.1 0.31 2 0.1 1.5 OFF 0.5 1 1600 A 1600 1600 2400 3200 496 A A A A A A Test Passed 4,000 1,000 2,133.33 2,800 A A A A A STATUS 1.33333 1.75 2.5 0.625 x lr x lr x ln x ln 11.3 Test Passed 14.56 5.05 0.03 0.13 Sec Sec Sec Sec Test Passed 0.1 Sec LONG TIME PICKUP (Ir) MICROLOGIC TRIP UNIT SETTINGS TEST RESULTS BY FULL FUNCTION TEST KIT Sec Sec SecSec Sec Sec Sec Sec TECH NOTE(S): COMMENTS: DEFICIENCIES: HUMIDITY WO-05206513 SE SWITCHBOARD / SWITCHGEAR INSPECTION TEMPERATURE 93 °F PAGE END USER CUSTOMER Main Panelboard GCISD SITE LOCATION Main PanelboardDESIGNATION SUBSTATION Main Panelboard DATE END USER ASSET/ID 7/31/2018 69 MAYERS ELECTRIC JOB # % DBID Main Panelboard 08-638200 DEVICE 21001 - SE Switchboard / Switchgear Inspection TESTED BY EQUIPMENT USEDAndrew Howard 480/277 Y 65 KA MANUFACTURER 1600 A BUS CONNECTIONS EXTERIOR CONDITION CLEAN/LUBE CLEAN/LUBECONDITION Acceptable Acceptable Acceptable Acceptable N/A CONDITION N/A DESCRIPTION N/A Performed INDICATORS / LAMPS N/A MATCHES DWG OR SPEC N/A FUNCTIONAL CHECKS BUS INSULATION Acceptable N/A N/A KEY / MECH. INTERLOCKS N/A PLC's / HMI's N/A CONDITION Acceptable Acceptable N/A N/A Acceptable NAMEPLATE 21001, REVISED 4/8/2015(888) 778-2733 www.schneider-electric.us 3 Phase 4 Wire WITHSTAND RATING TYPE / STYLECURRENT RATING QED-2 SN / SO NO.SYSTEM VOLTAGE MODEL / CATALOG A80440853 39847974-001 INSPECTION N/A PT'S AND CT'S Acceptable N/A AcceptablePOWER CABLES N/A N/A N/A INTERCONNECT WIRING InspectedRACKING / LIFTING MECHANISMS Acceptable InspectedDOORS / COVERS / GASKETS CPT AND CPT XFER CKT.ANCHORAGE GROUNDING PHASING CHECK CONTROL WIRING SPACE HEATERS DESCRIPTION N/A N/AINTERIOR SECTIONS / CUBICLES N/A PHASE BARRIERS SEQUENCE OF OPERATION DESCRIPTION N/A N/A N/A N/A N/A Square D RANGE BARRIERS / SHUTTERS @1000VGIG-OHMS 20°C 2.3 4.4 TEST 1 TEST 2 INSULATION RESISTANCE IN:PHASE-PHASE 4.62.4 20°CACTUALACTUAL A - B A-GND PHASE-GROUND B-GND C-GND B - C C - A 3.0 2.9 21.8 27.3 41.6 5.7 5.5 52.1TEST 3 N-GNDTEST 4 1.9076TEMPERATURE CORRECTION FACTOR TO 20°C, TCF INSULATION RESISTANCE TEST Section 1 Section 2 8 12 9 7 NBAFROMTO BUS SECTION TESTED RESISTANCE IN MICRO-OHMS C RESISTANCE IN MICRO-OHMS G 69 N BUSWORK CONNECTION RESISTANCE CBAFROMTO BUS SECTION TESTED G TECH NOTE(S):Ground Fault was tested through primary injection. All tests passed. COMMENTS: DEFICIENCIES: ZONE INTLK BREAKER TYPE TRIP UNIT TYPE 0202343983430001 BKR INT. RATING MOUNTING HUMIDITY WO-05206513 LOW VOLTAGE POWER CIRCUIT BREAKER TEMPERATURE 93 °F PAGE END USER CUSTOMER Main Panelboard GCISD SITE LOCATION PRESS BOXDESIGNATION SUBSTATION Main Panelboard DATE END USER ASSET/ID 7/31/2018 69 MAYERS ELECTRIC JOB # % DBID PRESS BOX 08-638220 DEVICE 03001 - SE LOW VOLT. PWR. CKT. BKR. TESTED BY EQUIPMENT USEDAndrew Howard 800 A N/A N/A N/A MATCHES DWG OR SPEC GROUND CONNECTION ONP800 J MANUFACTURER FUSE MFR. BKR CATALOG NO.PJA36080U73AE1 N/AFUSE CAT. NO. 800 A OFF B.I. THERMAL MEMORY SENSOR TAPS FRAME SIZE MAIN / ARCING CONTACTS BATTERY STATUS PRIMARY DISCONNECTS CELL AND RACKING DEV. CLEAN/LUBE DESCRIPTION CLEAN/LUBECONDITION Acceptable Acceptable Acceptable Not Checked N/A ARC CHUTES SECONDARY DISCONNECT CONDITIONDESCRIPTION CLEAN/LUBE N/AAcceptable DESCRIPTION N/A N/A N/AOPERATING MECHANISM N/A PHASE BARRIERS Acceptable N/A N/AAUXILIARY DEVICES BLOWN FUSE INDICATOR New N/A N/AINTERLOCKS OVERALL CONDITION New CONDITION N/A N/A Acceptable Acceptable N/A BREAKER NAMEPLATE INSPECTION TARGETS 03001, REVISED 4/9/2015(888) 778-2733 www.schneider-electric.us D.O. N/A N/A N/A 18153MFR. DATE / CODE 81140240TRIP UNIT SN SN / SO NO.Square D Micrologic 6.0H N/A COUNTER READING AL N/A FUSE AMPS N/A COUNTER READING AF RANGE @1000VGIG-OHMS 20°C 551.0 1,051.1 2.3 4.4 TEST 1 TEST 3 1.9076TEMPERATURE CORRECTION FACTOR TO 20°C, TCF TEST 2 INSULATION RESISTANCE IN:CLOSED: POLE-POLE 4.62.4 20°C ACTUAL PH A ACTUALACTUAL A - B A-GND CLOSED: POLE-GROUND OPEN: LINE-LOAD 20°C PH B PH C B-GND C-GND B - C C - A 3.0 2.9 21.8 27.3 508.0 479.041.6 5.7 913.7 5.5 52.1 969.1 CONTACT RESISTANCE - MICRO-OHMS 34 POLE 1 FUSE 2FUSE 1 FUSE 3 N/A N/A N/A POLE 3POLE 2 4448 SHORT TIME PICKUP INSTANTANEOUS PICKUP GROUND FAULT PICKUP 24.16 0.02 8.48 0.070.02 LONG TIME DELAY (tr) SHORT TIME DELAY (tsd) LONG TIME PICKUP (Ir) AS FOUND SETTING AS TESTED SETTING RANGE GROUND FAULT PICKUP (lg) GROUND FAULT DELAY (tg) MINIMUM TEST RESULTS MULTIPLIER TEST AMPS MAXIMUM PARAMETER INVERSE DEFINITE MIN. TIME LAG (idmtl) SHORT TIME PICKUP (Isd) INSTANTANEOUS PICKUP (li) GROUND FAULT PUSH TO TRIP BUTTON LT SWITCH SETTING (Io): SENSOR RATING (In): CURRENT LEVEL Acceptable Acceptable Acceptable PARAMETER TESTED TRIP TIME x In x In Sec x lr Sec x In x In 800 1 0.5 OFF 1.5 0.1 2 0 0 0 2 0.1 1.5 OFF 0.5 1 800 x In x In Sec x lr Sec x In x In Sec A I2T ONAS LEFT SETTING x In x In Sec x lr Sec x In x In Sec0 0 2 0.1 1.5 OFF 0.5 1 800 A 800 800 1200 1600 0 A A A A A A Test Passed 2,000 1,066.67 1,400 A A A A A STATUS 1.33334 1.75 2.5 x lr x lr x ln x ln 11.3 Test Passed 13.98 4.95 0.03 Sec Sec Sec Sec Test Passed 0 Sec LONG TIME PICKUP (Ir) MICROLOGIC TRIP UNIT SETTINGS TEST RESULTS BY FULL FUNCTION TEST KIT Sec Sec SecSec Sec Sec Sec Sec TECH NOTE(S): COMMENTS: DEFICIENCIES: