WO-05206513
Start-up and Commissioning
Table of Contents
Job #WO-05206513
PAGE
NO.
Site Location
MAYERS ELECTRICCustomer
GCISDEnd User
DeviceDesignation
Substation
Cover Letter
Main Panelboard
Main Panelboard Main Breaker 03001 - SE LOW VOLT. PWR. CKT. BKR.
Main Panelboard
Main Panelboard Main Panelboard 21001 - SE Switchboard / Switchgear Inspection
Main Panelboard
Main Panelboard PRESS BOX 03001 - SE LOW VOLT. PWR. CKT. BKR.
Grapevine, Texas
WO-05206513
Service Report
August 11, 2018
GCISD
Jimmy Hopkins
3001 IRA East Woods
Project #:
Subject:
Customer PO.:
Scope of Work Summary
Report Organization
ZONE INTLK
BREAKER TYPE
TRIP UNIT TYPE
0202343270080001
BKR INT. RATING
MOUNTING
HUMIDITY
WO-05206513
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 93 °F
PAGE
END USER
CUSTOMER
Main Panelboard
GCISD
SITE LOCATION
Main BreakerDESIGNATION
SUBSTATION Main Panelboard
DATE
END USER ASSET/ID
7/31/2018 69
MAYERS ELECTRIC JOB #
%
DBID
Main Breaker
08-638210
DEVICE 03001 - SE LOW VOLT. PWR. CKT. BKR.
TESTED BY EQUIPMENT USEDAndrew Howard
1600 A
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONR1200
K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO.RKF36160U44ASA
N/AFUSE CAT. NO.
2500 A OFF
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE DESCRIPTION CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDESCRIPTION CLEAN/LUBE
N/AAcceptable
DESCRIPTION
N/A
N/A
N/AOPERATING MECHANISM N/A
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION New
CONDITION
N/A
N/A
Acceptable
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 4/9/2015(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
18153MFR. DATE / CODE 02962163TRIP UNIT SN
SN / SO NO.Square D
6.0 A N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VGIG-OHMS 20°C
27.1 51.7
2.3 4.4
TEST 1
TEST 3
1.9076TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN:CLOSED: POLE-POLE
4.62.4
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
3.0
2.9
21.8
27.3
23.2
21.441.6
5.7
40.8
5.5 52.1
44.3
CONTACT RESISTANCE - MICRO-OHMS
22
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
2221
SHORT TIME PICKUP
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
24.16
0.02 8.48
0.070.02
0.11 0.23
LONG TIME DELAY (tr)
SHORT TIME DELAY (tsd)
LONG TIME PICKUP (Ir)
AS FOUND
SETTING
AS TESTED
SETTING
RANGE
GROUND FAULT PICKUP (lg)
GROUND FAULT DELAY (tg)
MINIMUM
TEST RESULTS
MULTIPLIER TEST AMPS MAXIMUM
PARAMETER
INVERSE DEFINITE MIN. TIME LAG (idmtl)
SHORT TIME PICKUP (Isd)
INSTANTANEOUS PICKUP (li)
GROUND FAULT PUSH TO TRIP BUTTON
LT SWITCH SETTING (Io):
SENSOR RATING (In):
CURRENT
LEVEL
Acceptable Acceptable Acceptable
PARAMETER TESTED
Test Passed
TRIP TIME
x In
x In
Sec
x lr
Sec
x In
x In
1600
1
0.5
OFF
1.5
0.1
2
0.31
0.1
0.31
2
0.1
1.5
OFF
0.5
1
1600
x In
x In
Sec
x lr
Sec
x In
x In
Sec
A
I2T ONAS LEFT
SETTING
x In
x In
Sec
x lr
Sec
x In
x In
Sec0.1
0.31
2
0.1
1.5
OFF
0.5
1
1600 A 1600
1600
2400
3200
496
A
A
A
A
A
A
Test Passed
4,000
1,000
2,133.33
2,800
A
A
A
A
A
STATUS
1.33333
1.75
2.5
0.625
x lr
x lr
x ln
x ln
11.3
Test Passed
14.56
5.05
0.03
0.13
Sec
Sec
Sec
Sec
Test Passed
0.1 Sec
LONG TIME PICKUP (Ir)
MICROLOGIC TRIP UNIT SETTINGS
TEST RESULTS BY FULL FUNCTION TEST KIT
Sec Sec
SecSec
Sec Sec
Sec Sec
TECH NOTE(S):
COMMENTS:
DEFICIENCIES:
HUMIDITY
WO-05206513
SE SWITCHBOARD / SWITCHGEAR INSPECTION
TEMPERATURE 93 °F
PAGE
END USER
CUSTOMER
Main Panelboard
GCISD
SITE LOCATION
Main PanelboardDESIGNATION
SUBSTATION Main Panelboard
DATE
END USER ASSET/ID
7/31/2018 69
MAYERS ELECTRIC JOB #
%
DBID
Main Panelboard
08-638200
DEVICE 21001 - SE Switchboard / Switchgear Inspection
TESTED BY EQUIPMENT USEDAndrew Howard
480/277 Y
65 KA
MANUFACTURER
1600 A
BUS CONNECTIONS
EXTERIOR CONDITION
CLEAN/LUBE CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
N/A
CONDITION
N/A
DESCRIPTION
N/A
Performed
INDICATORS / LAMPS
N/A
MATCHES DWG OR SPEC N/A
FUNCTIONAL CHECKS
BUS INSULATION Acceptable N/A N/A
KEY / MECH. INTERLOCKS
N/A
PLC's / HMI's N/A
CONDITION
Acceptable
Acceptable
N/A
N/A
Acceptable
NAMEPLATE
21001, REVISED 4/8/2015(888) 778-2733 www.schneider-electric.us
3 Phase 4 Wire
WITHSTAND RATING
TYPE / STYLECURRENT RATING QED-2
SN / SO NO.SYSTEM VOLTAGE
MODEL / CATALOG
A80440853
39847974-001
INSPECTION
N/A
PT'S AND CT'S
Acceptable N/A AcceptablePOWER CABLES
N/A N/A N/A INTERCONNECT WIRING InspectedRACKING / LIFTING MECHANISMS
Acceptable InspectedDOORS / COVERS / GASKETS
CPT AND CPT XFER CKT.ANCHORAGE
GROUNDING
PHASING CHECK
CONTROL WIRING
SPACE HEATERS
DESCRIPTION
N/A
N/AINTERIOR SECTIONS / CUBICLES
N/A
PHASE BARRIERS
SEQUENCE OF OPERATION
DESCRIPTION
N/A
N/A
N/A
N/A
N/A
Square D
RANGE
BARRIERS / SHUTTERS
@1000VGIG-OHMS 20°C
2.3 4.4
TEST 1
TEST 2
INSULATION RESISTANCE IN:PHASE-PHASE
4.62.4
20°CACTUALACTUAL
A - B A-GND
PHASE-GROUND
B-GND
C-GND
B - C
C - A
3.0
2.9
21.8
27.3
41.6
5.7
5.5 52.1TEST 3
N-GNDTEST 4
1.9076TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
INSULATION RESISTANCE TEST
Section 1 Section 2 8 12 9 7
NBAFROMTO
BUS SECTION TESTED RESISTANCE IN MICRO-OHMS
C
RESISTANCE IN MICRO-OHMS
G
69
N
BUSWORK CONNECTION RESISTANCE
CBAFROMTO
BUS SECTION TESTED
G
TECH NOTE(S):Ground Fault was tested through primary injection. All tests passed.
COMMENTS:
DEFICIENCIES:
ZONE INTLK
BREAKER TYPE
TRIP UNIT TYPE
0202343983430001
BKR INT. RATING
MOUNTING
HUMIDITY
WO-05206513
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 93 °F
PAGE
END USER
CUSTOMER
Main Panelboard
GCISD
SITE LOCATION
PRESS BOXDESIGNATION
SUBSTATION Main Panelboard
DATE
END USER ASSET/ID
7/31/2018 69
MAYERS ELECTRIC JOB #
%
DBID
PRESS BOX
08-638220
DEVICE 03001 - SE LOW VOLT. PWR. CKT. BKR.
TESTED BY EQUIPMENT USEDAndrew Howard
800 A
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONP800
J
MANUFACTURER
FUSE MFR.
BKR CATALOG NO.PJA36080U73AE1
N/AFUSE CAT. NO.
800 A OFF
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE DESCRIPTION CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Not Checked
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDESCRIPTION CLEAN/LUBE
N/AAcceptable
DESCRIPTION
N/A
N/A
N/AOPERATING MECHANISM N/A
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR New N/A N/AINTERLOCKS
OVERALL CONDITION New
CONDITION
N/A
N/A
Acceptable
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 4/9/2015(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
18153MFR. DATE / CODE 81140240TRIP UNIT SN
SN / SO NO.Square D
Micrologic 6.0H N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VGIG-OHMS 20°C
551.0 1,051.1
2.3 4.4
TEST 1
TEST 3
1.9076TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN:CLOSED: POLE-POLE
4.62.4
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
3.0
2.9
21.8
27.3
508.0
479.041.6
5.7
913.7
5.5 52.1
969.1
CONTACT RESISTANCE - MICRO-OHMS
34
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
4448
SHORT TIME PICKUP
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
24.16
0.02 8.48
0.070.02
LONG TIME DELAY (tr)
SHORT TIME DELAY (tsd)
LONG TIME PICKUP (Ir)
AS FOUND
SETTING
AS TESTED
SETTING
RANGE
GROUND FAULT PICKUP (lg)
GROUND FAULT DELAY (tg)
MINIMUM
TEST RESULTS
MULTIPLIER TEST AMPS MAXIMUM
PARAMETER
INVERSE DEFINITE MIN. TIME LAG (idmtl)
SHORT TIME PICKUP (Isd)
INSTANTANEOUS PICKUP (li)
GROUND FAULT PUSH TO TRIP BUTTON
LT SWITCH SETTING (Io):
SENSOR RATING (In):
CURRENT
LEVEL
Acceptable Acceptable Acceptable
PARAMETER TESTED TRIP TIME
x In
x In
Sec
x lr
Sec
x In
x In
800
1
0.5
OFF
1.5
0.1
2
0
0
0
2
0.1
1.5
OFF
0.5
1
800
x In
x In
Sec
x lr
Sec
x In
x In
Sec
A
I2T ONAS LEFT
SETTING
x In
x In
Sec
x lr
Sec
x In
x In
Sec0
0
2
0.1
1.5
OFF
0.5
1
800 A 800
800
1200
1600
0
A
A
A
A
A
A
Test Passed
2,000
1,066.67
1,400
A
A
A
A
A
STATUS
1.33334
1.75
2.5
x lr
x lr
x ln
x ln
11.3
Test Passed
13.98
4.95
0.03
Sec
Sec
Sec
Sec
Test Passed
0 Sec
LONG TIME PICKUP (Ir)
MICROLOGIC TRIP UNIT SETTINGS
TEST RESULTS BY FULL FUNCTION TEST KIT
Sec Sec
SecSec
Sec Sec
Sec Sec
TECH NOTE(S):
COMMENTS:
DEFICIENCIES: