HomeMy WebLinkAboutAlpha Testing - 1/9/2019Concrete Compression Test Report 5058 Brush Creek Rd. Fort Worth, TX 76119 (817)496-5600 Alpha Testing, Inc. TBPE Firm No. 813 FIELD DATA Placement Location:WALKWAY ENTRANCE Project Desc:MUSTANG PANTHER STADIUM PKG A & PKG B Our Report #:F171917-489718-S1 GRAPEVINE - COLLEYVILLE ISD 30510 IRA E WOODS AVE GRAPEVINE, TX 76051 CALVA POWELLATTN: Fax Number: Date Placed:12/12/2018 Time Placed:7:15 AM 4.0 4.7 48.0 61.0 Date Received:12/14/2018 Concrete Supplier:MARTIN MARIETTA Submitted By:Powell, Charles Plant Number:131 Delivery Ticket No.:5120182 151 Batch Time:N/A Tested For: Lab No.: Cure Type: Date Tested: Age (Days): Max Load: Area: Sq. In.PSI: Cap Spec: CYLINDER COMPRESSION TEST RESULTS (ASTM C-231) Avg. Length Avg. Width Avg Depth/ Diameter Cast By:ALPHA Cured Specification:ASTM C-31 Mix ID:TT2418 Break Type: Sample Location:15' N AND 50' W FROM SE CORNER OF TICKETBOOTH PM:TIM BEGOLE SR. Date Issued:01/09/2019 Specified Strength:3000 Result Air Content: Ambient Temp (F): Concrete Temp (F): Unit Weight: Slump (ASTM C-143): 759 12/19/20187 5930012.56 4720LABC-1231 8 N/A 45 760 1/9/2019 28 7296012.56 5810LABC-1231 8 N/A 45 761 1/9/2019 28 7371012.56 5870LABC-1231 8 N/A 45 762 1/9/2019 28 7371012.56 5870LABC-1231 8 N/A 43 Average 28-day Compressive Strength is compliant with project specifications CC: 5850 Respectfully Submitted By:__________________________________________________________ of Alpha Testing, Inc. Geotechnical Engineering * Construction Materials Testing * Environmental Engineering * Consulting 344177 Break Types: 1: Cone 2: Cone and Split 3: Cone and Shear 4: Shear 5: Columnar * = Specification out of spec Test Method: Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231, C173, C1064, C31, C1231 and C138. Compression strength tests per ASTM C39. Concrete Compression Test Report 5058 Brush Creek Rd. Fort Worth, TX 76119 (817)496-5600 Alpha Testing, Inc. TBPE Firm No. 813 FIELD DATA Placement Location:WALKWAY ENTRANCE Project Desc:MUSTANG PANTHER STADIUM PKG A & PKG B Our Report #:F171917-489718-S2 GRAPEVINE - COLLEYVILLE ISD 30510 IRA E WOODS AVE GRAPEVINE, TX 76051 CALVA POWELLATTN: Fax Number: Date Placed:12/12/2018 Time Placed:1:39 PM 4.5 5.2 59.0 68.0 Date Received:12/14/2018 Concrete Supplier:MARTIN MARIETTA Submitted By:Powell, Charles Plant Number:131 Delivery Ticket No.:5122314 150 Batch Time:N/A Tested For: Lab No.: Cure Type: Date Tested: Age (Days): Max Load: Area: Sq. In.PSI: Cap Spec: CYLINDER COMPRESSION TEST RESULTS (ASTM C-231) Avg. Length Avg. Width Avg Depth/ Diameter Cast By:ALPHA Cured Specification:ASTM C-31 Mix ID:TT2417 Break Type: Sample Location:5' N AND 20' W FROM SE CORNER OF TICKET BOOTH PM:TIM BEGOLE SR. Date Issued:01/09/2019 Specified Strength:3000 Result Air Content: Ambient Temp (F): Concrete Temp (F): Unit Weight: Slump (ASTM C-143): 763 12/19/20187 6002012.56 4780LABC-1231 8 N/A 42 764 1/9/2019 28 7548012.56 6010LABC-1231 8 N/A 43 765 1/9/2019 28 7600012.56 6050LABC-1231 8 N/A 45 766 1/9/2019 28 7691012.56 6120LABC-1231 8 N/A 45 Average 28-day Compressive Strength is compliant with project specifications CC: 6060 Respectfully Submitted By:__________________________________________________________ of Alpha Testing, Inc. Geotechnical Engineering * Construction Materials Testing * Environmental Engineering * Consulting 344178 Break Types: 1: Cone 2: Cone and Split 3: Cone and Shear 4: Shear 5: Columnar * = Specification out of spec Test Method: Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231, C173, C1064, C31, C1231 and C138. Compression strength tests per ASTM C39.