HomeMy WebLinkAboutAlpha Testing - 6/28/2018 (2)Tim Begole Sr.
Our test results and reports are for the exclusive use of the Client (and designated recipients) and shall not be reproduced and/or distributed except with express approval of ALPHA. The use of our name and test results must receive our written
approval. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. Technician time is from portal to portal. MF-019(8/2/2016)
Geotechnical Engineering | Construction Materials Testing | Environmental Engineering
Respectfully Submitted,
X Sheathing
Remarks:
Correct Splicing X
Cable/Tendon Count &
Spacing
X
Based on the representative's visual observation using the provided project plans, the area was compliant
Cable/Tendon Drape
XPT Drawings X
The contractor was notified of the observation result and the engineering representative returned to the Fort Worth Office.
Stirrup Size X
Grade Beam / Column Size X
Reinforcement Tied Properly X Stirrup Spacing X
Proper Placement X
Form Clean X
Bar Length & Spacing X
Number of Reinforcement X
Dowels in Place X
Proper Cover XDrawings Approved X
Grade Reinforcement X Reinforcement Clean X
Size of Reinforcement X Proper Support X
Observation Information
Item Observed CorrectNot Correct N/A Item Observed Correct Not Correct N/A
•Detail Sheet:S3.1 / L1.2
The representative observed the reinforcing steel related items for the following areas:
•Three Light Pole Bases
The representative utilized the following provided project plans to perform the observation:
•Date:5/17/2017 / 9/15/2017
•Sidewalk: Between Lower Concourse and Upper Concourse Bleachers
•Plan Sheet:S3.1 / L1.1
30510 Ira E Woods Ave Report Date:7/5/2018
An Alpha Testing engineering representative traveled to the above referenced project to perform a reinforcing steel observation as scheduled.
1 of 1
Technician:Gasigwa, Ignace(Baziga)
Grapevine, Texas Page Number:
Project:Mustang Panther Stadium Pkg A & Pkg B Project Number:F171917
Work Order Number:417740
Grapevine, TX 76051 Weather:Clear
Client:Grapevine - Colleyville ISD Service Date:06/28/2018
Alpha Testing, Inc.
5058 Brush Creek Rd
Fort Worth, TX 76119
www.alphatesting.com
TBPE Firm No. 813
Reinforcing Steel
Observation Report