July 13, 2018
Grapevine - Colleyville ISD
30510 Ira E Woods Ave
Grapevine, TX 76051
Attention: Ms. Calva Powell
Re: Field Inspection of Structural Steel
Mustang Panther Stadium
Pkg A & Pkg B
Grapevine, Texas
ALPHA Report No. F171917-333
Alpha Testing arrived on site to perform a Visual Structural Steel Inspection for the above referenced
project. Results of the inspection are as follows:
I Column anchor bolted connections – lines 11-0.12 and F-A.01 – Press box Upper Concourse
A. Connections were inspected per details on S3.1 and were properly tensioned at the
time of inspection. Compliant.
II Beam to column, beam to beam A325 bolted connections – lines 11-0.12 and F-A.01 – Press box
Upper Concourse:
A. Bolted Connections were inspected per sheet S6.7 and “Connections” general notes
6(B) and 6(E). Connections have been tensioned to a snug tight condition. Compliant.
III Brace frame welded connections – lines 11-0.12 and F-A.01 – Press box Upper Concourse:
A. Connections were inspected per erection sheet E12 and E13 and are visually
acceptable per AWS D1.1-15. Compliant.
*Discrepancies, if any, are noted above in bold.
INSPECTOR:
Kevin Ellis
CWI#17020871
We are pleased to be of service on this project and if you have any questions, please contact our office.
Sincerely yours,
ALPHA TESTING, INC.
Tim Begole Sr.
Project Manager